BLD18-00567
| FIRE-Final Inspection | 7/25/2018 | 7/27/2018 | 7/27/2018 4:10:18 PM | P | FAIL |
|
|
Need the project related fire alarm permit finaled then life safety can be passed
Fire/Life safety. Please call Tucker when on the way. Phone #: ###-#### Inspection requested via web by Tucker Robb
|
FIR18-00585
| INSP-Final Inspection | 7/26/2018 | 7/27/2018 | 7/27/2018 4:09:33 PM | P | FAIL |
|
|
Need the as-builts sent to/accepted by plan review
Contact is Sean. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
FIR18-00265
| INSP-Sprinkler Rough-in | 7/27/2018 | 7/27/2018 | 7/27/2018 4:02:29 PM | P | PASS |
|
|
See the city approved plans for locations marked "ok" where piping is ok for cover.
Adam Chitwood Phone #: ###-#### Inspection requested via web by Nathan Stenquist
|
FIR18-00589
| INSP-Final Inspection | 7/27/2018 | 7/27/2018 | 7/27/2018 12:52:35 PM | P | PASS |
|
|
Permit finaled
Please call Troy with time frame. Phone #: ###-#### Inspection requested via web by Jeff Packham
|
FIR17-00700
| INSP-Final Inspection | 7/26/2018 | 7/27/2018 | 7/27/2018 12:52:12 PM | P | CANC |
|
|
No water on system so fire alarm contractor could not pre-test or test with me.
Phone #: ###-#### Inspection requested via web by Connie Danes
|
FIR18-00584
| INSP-Final Inspection | 7/26/2018 | 7/27/2018 | 7/27/2018 12:51:19 PM | P | CANC |
|
|
Cancel per Matt. System has not been pre-tested and no water on system.
Anytime after 1230 thank you Phone #: ###-#### Inspection requested via web by Matt Casey
|
NAF18-00087
| INSP-Sprinkler Rough-in | 7/27/2018 | 7/27/2018 | 7/27/2018 12:50:32 PM | P | FAIL |
|
|
Todays inspection was for tenting. Half of the piping has already been covered with sheet rock so I can't check tenting. The half that has not been covered looks good. There were no ladders on site to get high enough to look across the ceiling.
Tenting inspection, ready when you have time. Thank you! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR17-00603
| INSP-Sprinkler Rough-in | 7/26/2018 | 7/27/2018 | 7/27/2018 10:50:23 AM | A | PASS |
|
|
See the city approved plans for locations marked "ok" in red where the piping is ok for cover.
Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00426
| INSP-Final Inspection | 7/25/2018 | 7/27/2018 | 7/27/2018 10:43:47 AM | P | PASS |
|
|
Permit finaled
Phone #: ###-#### Inspection requested via web by Sam Ball
|
BLD18-01423
| FIRE-Final Inspection | 7/26/2018 | 7/27/2018 | 7/27/2018 10:42:11 AM | A | PART |
|
|
The Star Bucks is being given a temp with Ron's permission until a fire alarm permit is issued/inspected for the over spaced ceiling mounted 30cd horn/strobe in this space. No other areas inspected.
Phone #: ###-#### Inspection requested via web by Mike Teeter
|
BLD18-02530
| FIRE-Final Inspection | 7/24/2018 | 7/27/2018 | 7/27/2018 10:07:02 AM | A | FAIL |
|
|
Provide one, 2A10BC, fire extinguisher with current inspection tag and mount between 5' and 4", remove the thumbturn deadbolt, keyed is ok,and provide sticker. Remove the round knob on the exit door and provide single action lever type as discussed.
Tammy Phone #: ###-####
|
FIR18-00558
| INSP-Final Inspection | 7/26/2018 | 7/27/2018 | 7/27/2018 8:35:36 AM | A | PASS |
|
|
Permit finaled
Phone #: ###-#### Inspection requested via web by Robert Gobler
|
NAF18-00099
| INSP-Final | 7/26/2018 | 7/27/2018 | 7/27/2018 8:03:27 AM | A | FAIL |
|
|
Provide strobe for exterior, provide as-builts, change candellas
Phone #: ###-#### Inspection requested via web by Robert Gobler
|
NAF18-00058
| INSP-Final | 7/26/2018 | 7/27/2018 | 7/27/2018 7:59:58 AM | A | FAIL |
|
|
Provide strobe for exterior, provide as-builts, change candellas
Phone #: ###-#### Inspection requested via web by Robert Gobler
|