Inspections for the day of: Tuesday, July 28, 2015.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR15-00223 INSP-Sprinkler Rough-in7/27/20157/28/20157/28/2015 3:17:54 PMPPASS
Sprinkler rough-in and tenting inspection passed. Piping can be covered.
FIR15-00420 INSP-Final Inspection7/27/20157/28/20157/28/2015 2:38:34 PMPFAIL
Missing part of the city approved plans, on ceiling mounted strobe was overspace on the upper level, missing document box. The single strobe in the basement is overspaced and will not provide coverage in a pocket at the bottom of the stairs and in the area under the stairs. These two areas are not shown on the plans. Also the ceiling mounted duct work in the basement cuases an obstruction to the smoke detectors due to exceeding 10% of the ceiling height so spacing needs to be adjusted. I spoke to Lee and there is a possibility that the fire alarm system can be deleted from the basement if the contractor chooses not to provide modifications. Permission and as-builts will be needed prior to a final inspection. Also the address is incorrect. No actual testing was performed.
BLD15-01443 FIRE-Final Inspection7/24/20157/28/20157/28/2015 12:13:51 PMAPASS
life safety passed
FIR11-00296 FIR-Aging Inspection7/28/20157/28/20157/28/2015 10:37:54 AM NR
Per Scott the city of boise is working toward a resolution on the separate address monitoring
FIR15-00434 INSP-Final Inspection7/28/20157/28/20157/28/2015 10:34:14 AMPPASS
Permit finaled
FIR15-00434 INSP-Sprinkler Rough-in/Hydro7/24/20157/28/20157/28/2015 10:33:10 AMAPASS
Rough-in passed
BLD15-00478 FIRE-Final Inspection7/27/20157/28/20157/28/2015 10:28:37 AMAFAIL
See the city approved plans for location of deficiencies. They include tagging fire extinguisher, repairing exit sign, provide arrow on exit sign and correct door hardware.
FIR15-00455 INSP-Sprinkler Rough-in7/27/20157/28/20157/28/2015 10:13:19 AMAPASS
Overhead piping is ok to cover
FIR15-00415 INSP-Sprinkler Rough-in/Hydro7/27/20157/28/20157/28/2015 10:12:03 AMAPASS
Overhead hydro test passed
FIR15-00335 INSP-Sprinkler Rough-in7/27/20157/28/20157/28/2015 9:43:21 AMAPASS
The underground supply piping is ok to cover.
BLD15-01513 FIRE-Final Inspection7/27/20157/28/20157/28/2015 9:22:14 AMACANC
Life Safety sign off not required.
FIR15-00222 INSP-Sprinkler Rough-in7/27/20157/28/20157/28/2015 9:21:43 AMPCANC
And tenting Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball
BLD15-00199 FIRE-Final Inspection7/27/20157/28/20157/28/2015 9:20:29 AMAPART
Phase 3 life safety passed
BLD13-03584 FIRE-Final Inspection7/27/20157/28/20157/28/2015 9:13:35 AMAPASS
Life Safety Passed
BLD13-03585 FIRE-Final Inspection7/27/20157/28/20157/28/2015 8:12:54 AMAPASS
Life Safety Passed
BLD15-01273 FIRE-Final Inspection7/27/20157/28/20157/28/2015 7:45:36 AMAPASS
Life safety passed