FIR19-00359
| INSP-Sprinkler Rough-in | 7/29/2019 | 7/30/2019 | 7/30/2019 2:43:41 PM | P | FAIL |
|
|
Provide plan modifications/hydraulic calculations showing the actual piping layout now that two pendant heads are being piped from a single 1" outlet. Contact Tanner Loomis ###-#### 30 min prior to RTC Insp start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
BLD16-03428
| FIRE-Final Inspection | 7/30/2019 | 7/30/2019 | 7/30/2019 2:35:38 PM | P | PASS |
|
|
Life safety passed. Dave Phone #: ###-####
|
BLD19-02776
| FIRE-Final Inspection | 7/29/2019 | 7/30/2019 | 7/30/2019 2:16:32 PM | A | PASS |
|
|
life safety passed.
Darleen Phone #: ###-####
|
BLD19-02115
| FIRE-Final Inspection | 7/30/2019 | 7/30/2019 | 7/30/2019 2:01:40 PM | P | FAIL |
|
|
Life safety will be ok for a sign off when fire alarm modifications have been submitted/approved.
Dwayne Phone #: ###-####
|
BLD18-04514
| FIRE-Final Inspection | 7/30/2019 | 7/30/2019 | 7/30/2019 11:54:31 AM | P | FAIL |
|
|
Provide small documents, repair the exit signs and emergency lights, relocate the main exit discharge light to be installed below the canopy.
Please call ahead for access - Pat Phone #: ###-####
|
BLD18-04580
| FIRE-Final Inspection | 7/30/2019 | 7/30/2019 | 7/30/2019 10:10:31 AM | A | PASS |
|
|
life safety passed
Call Jon Craft Phone #: ###-#### Inspection requested via web by Jonathan Craft
|
FIR19-00328
| INSP-Final Inspection | 7/29/2019 | 7/30/2019 | 7/30/2019 10:08:53 AM | A | PASS |
|
|
permit finaled
Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR18-00237
| INSP-Sprinkler Rough-in | 7/29/2019 | 7/30/2019 | 7/30/2019 10:07:49 AM | A | FAIL |
|
|
The AES functioned but the main fire alarm system has provlems such as display and notification output. This permit can be finaled when the fire alarm system has been repaired. Depending of the required work this AES may need to be retested.
Jacob Phone #: ###-####
|
FIR18-00246
| INSP-Sprinkler Rough-in | 7/29/2019 | 7/30/2019 | 7/30/2019 10:04:06 AM | A | PASS |
|
|
permit finaled
Jacob Phone #: ###-####
|
FIR18-00155
| INSP-Sprinkler Rough-in | 7/29/2019 | 7/30/2019 | 7/30/2019 10:03:22 AM | A | PASS |
|
|
Permit finaled.
Jacob Phone #: ###-####
|
NAF18-00128
| INSP-Final | 7/24/2019 | 7/30/2019 | 7/30/2019 12:00:00 AM | A | PASS |
|
|
**Hydro passed at well pump pressure. Bell needs to be mounted in relocated location I marked on approved plans, Not at the location submitted. Some patching needs to be done around escutcheons, and all painting needs to be completed before final inspection. MAS***
Call prior to going Phone #: 2084212181 >> Inspection requested via mobile web by Brian
|
FIR19-00440
| INSP-Sprinkler Rough-in/Hydro | 7/29/2019 | 7/30/2019 | 7/30/2019 12:00:00 AM | A | PASS |
|
|
**Hydro and rough-in passed. MAS**
r/i and OH hydro // Kerry ###-####
|