Inspections for the day of: Tuesday, July 30, 2019.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00359 INSP-Sprinkler Rough-in7/29/20197/30/20197/30/2019 2:43:41 PMPFAIL
Provide plan modifications/hydraulic calculations showing the actual piping layout now that two pendant heads are being piped from a single 1" outlet. Contact Tanner Loomis ###-#### 30 min prior to RTC Insp start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
BLD16-03428 FIRE-Final Inspection7/30/20197/30/20197/30/2019 2:35:38 PMPPASS
Life safety passed. Dave Phone #: ###-####
BLD19-02776 FIRE-Final Inspection7/29/20197/30/20197/30/2019 2:16:32 PMAPASS
life safety passed.

Darleen Phone #: ###-####
BLD19-02115 FIRE-Final Inspection7/30/20197/30/20197/30/2019 2:01:40 PMPFAIL
Life safety will be ok for a sign off when fire alarm modifications have been submitted/approved.

Dwayne Phone #: ###-####
BLD18-04514 FIRE-Final Inspection7/30/20197/30/20197/30/2019 11:54:31 AMPFAIL
Provide small documents, repair the exit signs and emergency lights, relocate the main exit discharge light to be installed below the canopy.

Please call ahead for access - Pat Phone #: ###-####
BLD18-04580 FIRE-Final Inspection7/30/20197/30/20197/30/2019 10:10:31 AMAPASS
life safety passed

Call Jon Craft Phone #: ###-#### Inspection requested via web by Jonathan Craft
FIR19-00328 INSP-Final Inspection7/29/20197/30/20197/30/2019 10:08:53 AMAPASS
permit finaled

Phone #: ###-#### Inspection requested via web by Sam Ball
FIR18-00237 INSP-Sprinkler Rough-in7/29/20197/30/20197/30/2019 10:07:49 AMAFAIL
The AES functioned but the main fire alarm system has provlems such as display and notification output. This permit can be finaled when the fire alarm system has been repaired. Depending of the required work this AES may need to be retested.

Jacob Phone #: ###-####
FIR18-00246 INSP-Sprinkler Rough-in7/29/20197/30/20197/30/2019 10:04:06 AMAPASS
permit finaled

Jacob Phone #: ###-####
FIR18-00155 INSP-Sprinkler Rough-in7/29/20197/30/20197/30/2019 10:03:22 AMAPASS
Permit finaled.

Jacob Phone #: ###-####
NAF18-00128 INSP-Final7/24/20197/30/20197/30/2019 12:00:00 AMAPASS
**Hydro passed at well pump pressure. Bell needs to be mounted in relocated location I marked on approved plans, Not at the location submitted. Some patching needs to be done around escutcheons, and all painting needs to be completed before final inspection. MAS***
Call prior to going Phone #: 2084212181 >> Inspection requested via mobile web by Brian
FIR19-00440 INSP-Sprinkler Rough-in/Hydro7/29/20197/30/20197/30/2019 12:00:00 AMAPASS
**Hydro and rough-in passed. MAS**
r/i and OH hydro // Kerry ###-####