Inspections for the day of: Wednesday, July 31, 2019.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
NAF18-00077 INSP-Final7/29/20197/31/20198/1/2019 8:14:50 AMAFAIL
Life safety will be ok to final when the project related fire alarm permit is passed.

Call prior to going Phone #: 2089571097 >> Inspection requested via mobile web by Todd
NAF19-00006 INSP-Final7/30/20197/31/20198/1/2019 12:00:00 AMAPASS
As late as possible Phone #: 2089417514 >> Inspection requested via mobile web by Matt.

All tests passed. Once as built drawings are received, permit will be final.
BLD19-00911 BLD-Conference7/30/20197/31/20197/31/2019 3:58:46 PMPDONE
The stage and the sound booth floors have both been filled with non-combustible insulation. They are ok for cover. We also spoke about the need for a fire alarm permit for the modifications.

as late as possible - fire conference // Matt Phone #: ###-####
FIR19-00353 INSP-Sprinkler Rough-in7/31/20197/31/20197/31/2019 2:42:00 PMPPASS
Hanger inspection for pre-rock on 1st, 2nd and third floors passed. Also hangers are ok for cover in the riser room and mechanical room.

Nick Curtis is the contact. Phone #: ###-#### Inspection requested via web by jeremiah robison
FIR19-00484 INSP-Final Inspection7/29/20197/31/20197/31/2019 1:32:53 PMPCANC
To be rescheduled per contact.

Phone #: ###-#### Inspection requested via web by Nathan Schneider
BLD17-03168 FIRE-Final Inspection7/31/20197/31/20197/31/2019 1:31:53 PMPFAIL
Still need some of the exit signs and emergency lights repaired. Also need a FIR permit for the duct detector and mag lock interface.

CHIP Phone #: ###-####
BLD18-02261 FIRE-Final Inspection7/31/20197/31/20197/31/2019 12:45:35 PMPFAIL
Need the city approved plans and small documents, provide sprinkler and fire alarm protection as per upgrade agreement.

Call ahead // Gavin Phone #: ###-####
BLD19-00763 FIRE-Final Inspection7/31/20197/31/20197/31/2019 11:29:43 AMPFAIL
FIre alarm notification needs to be provided in the new corridor/elevator lobby area. All other items appear ok.

Please call 30 mins before coming- Sean Phone #: ###-####
BLD18-04514 FIRE-Final Inspection7/30/20197/31/20197/31/2019 11:27:15 AMAPASS
Life safety passed. The exit discharge light at the main exit to be relocated to below the canopy and the south exit door exit sign/emergency light repaired prior to a building inspection

Pat Phone #: ###-####
FIR19-00221 INSP-Sprinkler Rough-in7/30/20197/31/20197/31/2019 12:00:00 AMPPART
**Unit V only on 2nd floor ok to cover. MAS**
Tom Phone #: ###-####