BLD20-02578
| FIRE-Final Inspection | 7/30/2020 | 7/31/2020 | 7/31/2020 2:08:35 PM | A | PASS |
|
|
life safety passed.
Screened- Sam Phone #: ###-#### please after 9am
|
BLD20-00330
| FIRE-Final Inspection | 7/31/2020 | 7/31/2020 | 7/31/2020 11:48:13 AM | P | FAIL |
|
|
Remove deadbolt at the west door, provide exit discharge light at the south facing door per approved plans, install duct smoke detector per installation guide (narrow side) and provide testing, provide tagged and mounted fire extinguisher up stairs.
SCREENED // Bob Phone #: ###-####
|
FIR20-00484
| INSP-Final Inspection | 7/31/2020 | 7/31/2020 | 7/31/2020 11:13:34 AM | P | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Don Kartchner Inspection cancelled from web by: Don Kartchner
|
FIR20-00139
| INSP-Final Inspection | 7/30/2020 | 7/31/2020 | 7/31/2020 9:21:24 AM | A | PASS |
|
|
verified function of the new voice evac hand set.
ermit finaled. Buck Tom Phone #: ###-#### Inspection requested via web by Ken Webster
|
FIR19-00766
| INSP-Final Inspection | 7/29/2020 | 7/31/2020 | 7/31/2020 9:19:32 AM | A | FAIL |
|
|
I stopped the inspection when I found that the underground supply piping to the riser was 1" instead of the 2" shown on the plans. Also this 1" piping has alot of 1" 90's before it gets to the riser and none are shown on the plans. Also the plans indicate a rvs-1 residential valve but none is installed. Also there was no way to verify if the yard sprinklers are connected to the main supply and if so that they are shutting off upon activation of the sprinkler system. No other items looked at or tested.
Contact Perly Daniel ###-#### 30 min prior to Fire Final Insp start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|