Inspections for the day of: Friday, July 31, 2020.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD20-02578 FIRE-Final Inspection7/30/20207/31/20207/31/2020 2:08:35 PMAPASS
life safety passed.

Screened- Sam Phone #: ###-#### please after 9am
BLD20-00330 FIRE-Final Inspection7/31/20207/31/20207/31/2020 11:48:13 AMPFAIL
Remove deadbolt at the west door, provide exit discharge light at the south facing door per approved plans, install duct smoke detector per installation guide (narrow side) and provide testing, provide tagged and mounted fire extinguisher up stairs.


SCREENED // Bob Phone #: ###-####
FIR20-00484 INSP-Final Inspection7/31/20207/31/20207/31/2020 11:13:34 AMPCANC
Phone #: ###-#### >> Inspection requested via web by Don Kartchner Inspection cancelled from web by: Don Kartchner
FIR20-00139 INSP-Final Inspection7/30/20207/31/20207/31/2020 9:21:24 AMAPASS
verified function of the new voice evac hand set.

ermit finaled. Buck Tom Phone #: ###-#### Inspection requested via web by Ken Webster
FIR19-00766 INSP-Final Inspection7/29/20207/31/20207/31/2020 9:19:32 AMAFAIL
I stopped the inspection when I found that the underground supply piping to the riser was 1" instead of the 2" shown on the plans. Also this 1" piping has alot of 1" 90's before it gets to the riser and none are shown on the plans. Also the plans indicate a rvs-1 residential valve but none is installed. Also there was no way to verify if the yard sprinklers are connected to the main supply and if so that they are shutting off upon activation of the sprinkler system. No other items looked at or tested.


Contact Perly Daniel ###-#### 30 min prior to Fire Final Insp start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank