Inspections for the day of: Friday, July 5, 2019.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD18-02795 FIRE-Final Inspection7/2/20197/5/20197/5/2019 12:35:07 PMPPASS
life safety passed

Frankie-elevator only Phone #: ###-####
FIR19-00421 INSP-Final Inspection7/2/20197/5/20197/5/2019 12:29:57 PMAPASS
Permit finaled. As-builts received.

As early as possible Phone #: 2089853303 >> Inspection requested via mobile web by Mike Kroll
FIR18-00801 INSP-Final Inspection7/5/20197/5/20197/5/2019 10:37:58 AMPPART
Fire alarm panel verified, phone lines verified, batteries verified, interconnection with tamper switches, PIV switch and flow switches verified. Per Lee the CO detectors need to annunciate in the area covered.


Brandon Phone #: ###-####
BLD19-01268 FIRE-Final Inspection7/5/20197/5/20197/5/2019 10:32:04 AMPFAIL
Provide exit discharge lights at both exits as per the approved plans, repair the emergency light over the sink, provide single action hardware at the interior south facing exit door, provide mounted and tagged fire extinguisher as discussed.

Lance Phone #: ###-####
BLD19-01839 FIRE-Final Inspection7/2/20197/5/20197/5/2019 8:49:36 AMAPASS
Life safety passed

Randy-1 hour notice-need to call for access code Phone #: ###-####
FIR19-00414 INSP-Final Inspection7/5/20197/5/20197/5/2019 8:49:07 AMPPASS
Permit finaled.

Charles Phone #: ###-####
FIR19-00321 INSP-Sprinkler Rough-in7/2/20197/5/20197/5/2019 8:19:22 AMAFAIL
I tried calling the contact phone number three times but it won't even ring. I tried calling Clarence but it just goes to voice mail. I went to job site and made no contact. I however walked and looked at the tenting. On the main level laundry room the cpvc piping disappears behind the insulation on the wall (not sure what is going on here) and the ladder has been removed so I have no access to the upper floor to look at tenting. I walked around the house but I'm unsure it the roofing is approved to walk on. No piping can be covered. Sticker left on site.

Please call James Mair ###-#### Phone #: ###-#### Inspection requested via web by Jessia Maxwell