Inspections for the day of: Friday, July 6, 2018.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD18-00277 FIRE-Final Inspection7/6/20187/6/20187/6/2018 1:57:36 PMPPASS
life safety passed

Kenna Phone #: ###-####
BLD17-04338 FIRE-Final Inspection7/6/20187/6/20187/6/2018 1:38:37 PMPFAIL
Provide the missing exit sign, provide single action hardware on the new restroom door and the east facing exterior exit door.


Troy Phone #: ###-####
FIR18-00119 INSP-Sprinkler Rough-in7/6/20187/6/20187/6/2018 1:36:46 PMPFAIL
Per the plumbing inspector the underground piping being used is not listed. LIsted piping needs to be installed and re-inspected.


Contact Brad Westbrook - ###-#### 30 min prior to UG RTC Start please, hew would prefer to schedule this inspection for 2pm today.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
BLD17-04467 FIRE-Final Inspection7/5/20187/6/20187/6/2018 11:33:29 AMAPART
The remodeled area life safety is passed. Before a final the exit lights/emergency lights/exit discharge lights for the north side bay and the south side bay garage door needs to be installed and tested, also the main exit will need its discharge light, sticker, and indicator.

Brian Phone #: ###-####
FIR18-00300 INSP-Sprinkler Rough-in/Hydro7/5/20187/6/20187/6/2018 10:56:53 AMAPASS
Hydro test for system #3, below mezzanine, piping passed.

Please call Chris Ford

Thank you Phone #: ###-#### Inspection requested via web by Jessia Maxwell
NAF18-00061 INSP-Sprinkler Rough-in7/5/20187/6/20187/6/2018 10:10:49 AMAPASS
Rough-in passed for the center section of the building. The dry system piping for the front canopy is not installed yet. Tenting is not done yet. I noted a missing earthquake brace on the main just before it will exit to the front canopy. I noted revised piping and fittings for the supply to the front canopy tht will need to be included in calculations. The low point drain the the janitors closet has not been installed yet.


Phone #: ###-#### Inspection requested via web by Matthew Lewis
BLD18-02394 FIRE-Final Inspection7/5/20187/6/20187/6/2018 10:05:58 AMAPASS
Life safety passed. I noted that the side glass at the exit door is loose in its frame. It appears to be a rated assembly

call 20 mins ahead Phone #: ###-####