BLD18-00277
| FIRE-Final Inspection | 7/6/2018 | 7/6/2018 | 7/6/2018 1:57:36 PM | P | PASS |
|
|
life safety passed
Kenna Phone #: ###-####
|
BLD17-04338
| FIRE-Final Inspection | 7/6/2018 | 7/6/2018 | 7/6/2018 1:38:37 PM | P | FAIL |
|
|
Provide the missing exit sign, provide single action hardware on the new restroom door and the east facing exterior exit door.
Troy Phone #: ###-####
|
FIR18-00119
| INSP-Sprinkler Rough-in | 7/6/2018 | 7/6/2018 | 7/6/2018 1:36:46 PM | P | FAIL |
|
|
Per the plumbing inspector the underground piping being used is not listed. LIsted piping needs to be installed and re-inspected.
Contact Brad Westbrook - ###-#### 30 min prior to UG RTC Start please, hew would prefer to schedule this inspection for 2pm today.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
BLD17-04467
| FIRE-Final Inspection | 7/5/2018 | 7/6/2018 | 7/6/2018 11:33:29 AM | A | PART |
|
|
The remodeled area life safety is passed. Before a final the exit lights/emergency lights/exit discharge lights for the north side bay and the south side bay garage door needs to be installed and tested, also the main exit will need its discharge light, sticker, and indicator.
Brian Phone #: ###-####
|
FIR18-00300
| INSP-Sprinkler Rough-in/Hydro | 7/5/2018 | 7/6/2018 | 7/6/2018 10:56:53 AM | A | PASS |
|
|
Hydro test for system #3, below mezzanine, piping passed.
Please call Chris Ford
Thank you Phone #: ###-#### Inspection requested via web by Jessia Maxwell
|
NAF18-00061
| INSP-Sprinkler Rough-in | 7/5/2018 | 7/6/2018 | 7/6/2018 10:10:49 AM | A | PASS |
|
|
Rough-in passed for the center section of the building. The dry system piping for the front canopy is not installed yet. Tenting is not done yet. I noted a missing earthquake brace on the main just before it will exit to the front canopy. I noted revised piping and fittings for the supply to the front canopy tht will need to be included in calculations. The low point drain the the janitors closet has not been installed yet.
Phone #: ###-#### Inspection requested via web by Matthew Lewis
|
BLD18-02394
| FIRE-Final Inspection | 7/5/2018 | 7/6/2018 | 7/6/2018 10:05:58 AM | A | PASS |
|
|
Life safety passed. I noted that the side glass at the exit door is loose in its frame. It appears to be a rated assembly
call 20 mins ahead Phone #: ###-####
|