Inspections for the day of: Wednesday, August 14, 2019.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD18-00776 FIRE-Final Inspection8/14/20198/14/20198/14/2019 3:39:25 PMPFAIL
Need the project related fire alarm and fire sprinkler permits finaled, need the fire hydrant addressed, need the west exit discharge light addressed. Ron Phone #: ###-####
FIR13-00187 INSP-Final Inspection8/13/20198/14/20198/14/2019 2:20:51 PMPFAIL
Two of the three sets of doors did not latch due to positive air pressure from the classroom wings. The roll down fire door functioned with activation on the control box test function. So to final this permit the classroom wing doors need to be adjusted to overcome the air pressure and latch automatically.

Jeff Phone #: ###-####
FIR17-00400 INSP-Final Inspection8/13/20198/14/20198/14/2019 2:18:23 PMPFAIL
No approved plans or small documents available. No inspection for this permit performed.

Jeff Gooch will be on site with thumb drive of plans Phone #: ###-#### Inspection requested via web by Jeff Gooch
BLD18-00105 FIRE-Final Inspection8/14/20198/14/20198/14/2019 1:26:08 PMPPART
A temporary for this permit is being given for one week. Work that needs completed is: cover the cpvc piping in the riser rooms and in the storage closets, provide one hour riser room, provide heat in the riser room, move smoke alarms.

Phone #: ###-#### Inspection requested via web by Andy Thompson
FIR19-00061 INSP-Final Inspection8/13/20198/14/20198/14/2019 1:25:40 PMAPART
A temporary for this permit is being given for one week. Work that needs completed is: cover the cpvc piping in the riser rooms and in the storage closets, provide one hour riser room, provide heat in the riser room.
nick Phone #: ###-####
FIR19-00436 INSP-Final Inspection8/13/20198/14/20198/14/2019 12:08:49 PMAPASS
Permit finaled.

Brandon Phone #: ###-####
FIR19-00327 INSP-Final Inspection8/13/20198/14/20198/14/2019 11:30:43 AMAPASS
permit finaled

Colton-wants at 10 Phone #: ###-####
FIR19-00592 INSP-Final Inspection8/13/20198/14/20198/14/2019 9:55:04 AMAPASS
Permit finaled.

Contact is Nick Phone #: ###-#### Inspection requested via web by Chris Green
FIR19-00592 INSP-Sprinkler Rough-in8/13/20198/14/20198/14/2019 9:54:41 AMAPASS
Contact is Nick Phone #: ###-#### Inspection requested via web by Chris Green
NAF19-00071 INSP-Sprinkler Rough-in/Hydro8/13/20198/14/20198/14/2019 12:00:00 AMAFAIL
*Areas that need additional tenting marked in red on approved drawings. Hydro failed dropped from 210 to 182 psi. Underground piping not installed yet.**MAS**
Gabe Garduno is the contact. Thank you for your hard work! Phone #: ###-#### >> Inspection requested via web by Stan Beus