FIR12-00610
| INSP-Sprinkler Rough-in/Hydro | 8/26/2013 | 8/26/2013 | 8/26/2013 3:50:33 PM | P | CANC |
|
|
Overbooked
|
FIR13-00187
| INSP-Alarm Testing | 8/23/2013 | 8/26/2013 | 8/26/2013 3:44:50 PM | P | DONE |
|
|
See the small version of the city approved plans for areas inspected today. Todays inspection took place in the Administration Building. No signals were tested, only verification of spacing, candellas and testing of smoke detectors. Devices tested have been marked "ok" in red on the plans. See plans for items needing corrected which include door closures, additional notification in the Kitchen and additional notification in the Lunch Room seating area where the visual notification is blocked by banners hanging from the ceiling.
|
BLD13-00789
| FIRE-Final Inspection | 8/26/2013 | 8/26/2013 | 8/26/2013 1:12:59 PM | P | PASS |
|
|
Life safety passed
|
FIR13-00250
| INSP-Sprinkler Rough-in/Hydro | 8/23/2013 | 8/26/2013 | 8/26/2013 12:42:25 PM | P | CANC |
|
|
Per Nate cant get water on site. Will reschedule for tomorrow.
|
BLD13-01583
| FIRE-Final Inspection | 8/23/2013 | 8/26/2013 | 8/26/2013 12:05:00 PM | A | FAIL |
|
|
Could not find the city approved plans on site. I noted a fire extinguisher will be required for the mezzanine. Door hardware, exit sign and emergency lights functioned correctly.
|
FIR13-00309
| INSP-Final Inspection | 8/23/2013 | 8/26/2013 | 8/26/2013 12:03:11 PM | A | PASS |
|
|
Permit finaled
|
BLD13-00543
| FIRE-Final Inspection | 8/22/2013 | 8/26/2013 | 8/26/2013 9:43:05 AM | A | PASS |
|
|
Life safety passed. Per Zoo management they are utilizing the door hardware exemption signed by Jason to allow the round knobs.
|
BLD13-02005
| FIRE-Final Inspection | 8/23/2013 | 8/26/2013 | 8/26/2013 8:40:56 AM | A | FAIL |
|
|
No city approved plans on site. I did a quick walk through with Craig on the phone and I found pendant sprinkler heads overspaced on the west side of the new wall at the Lobby (small room rule can not be used in a merchantile space), one pendant in the restroom may be too close to the wall, provide one fire extinguisher in the new space since the other exceed 75' travel distance, and remove the keyed hardware from the main exit door in the new space and provide single action or get plan review approval to delete the store front door.
|