Inspections for the day of: Monday, August 26, 2013.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR12-00610 INSP-Sprinkler Rough-in/Hydro8/26/20138/26/20138/26/2013 3:50:33 PMPCANC
Overbooked
FIR13-00187 INSP-Alarm Testing8/23/20138/26/20138/26/2013 3:44:50 PMPDONE
See the small version of the city approved plans for areas inspected today. Todays inspection took place in the Administration Building. No signals were tested, only verification of spacing, candellas and testing of smoke detectors. Devices tested have been marked "ok" in red on the plans. See plans for items needing corrected which include door closures, additional notification in the Kitchen and additional notification in the Lunch Room seating area where the visual notification is blocked by banners hanging from the ceiling.
BLD13-00789 FIRE-Final Inspection8/26/20138/26/20138/26/2013 1:12:59 PMPPASS
Life safety passed
FIR13-00250 INSP-Sprinkler Rough-in/Hydro8/23/20138/26/20138/26/2013 12:42:25 PMPCANC
Per Nate cant get water on site. Will reschedule for tomorrow.
BLD13-01583 FIRE-Final Inspection8/23/20138/26/20138/26/2013 12:05:00 PMAFAIL
Could not find the city approved plans on site. I noted a fire extinguisher will be required for the mezzanine. Door hardware, exit sign and emergency lights functioned correctly.
FIR13-00309 INSP-Final Inspection8/23/20138/26/20138/26/2013 12:03:11 PMAPASS
Permit finaled
BLD13-00543 FIRE-Final Inspection8/22/20138/26/20138/26/2013 9:43:05 AMAPASS
Life safety passed. Per Zoo management they are utilizing the door hardware exemption signed by Jason to allow the round knobs.
BLD13-02005 FIRE-Final Inspection8/23/20138/26/20138/26/2013 8:40:56 AMAFAIL
No city approved plans on site. I did a quick walk through with Craig on the phone and I found pendant sprinkler heads overspaced on the west side of the new wall at the Lobby (small room rule can not be used in a merchantile space), one pendant in the restroom may be too close to the wall, provide one fire extinguisher in the new space since the other exceed 75' travel distance, and remove the keyed hardware from the main exit door in the new space and provide single action or get plan review approval to delete the store front door.