FIR17-00368
| INSP-Final Inspection | 8/28/2017 | 8/29/2017 | 8/29/2017 2:05:52 PM | P | FAIL |
|
|
No testing performed today. We went over strobe spacing and some modifications are needed which will require as-builts given to plan review prior to a final sign off.
|
BLD17-02635
| FIRE-Final Inspection | 8/28/2017 | 8/29/2017 | 8/29/2017 10:58:14 AM | A | PASS |
|
|
Life safety passed
|
FIR17-00390
| INSP-Final Inspection | 8/28/2017 | 8/29/2017 | 8/29/2017 10:05:53 AM | A | CANC |
|
|
Matt Clark Phone #: ###-####
|
BLD17-02438
| FIRE-Final Inspection | 8/25/2017 | 8/29/2017 | 8/29/2017 10:05:23 AM | A | FAIL |
|
|
Provide correct building number and suite number, provide information/submittals to plan review for the two powder coating booths, provide correct hardware at the exterior exits as discussed and repair the exit sign on the north exit door. Provide annual inspection of the fire sprinkler system and provide fire sprinkler monitoring.
Chad Phone #: ###-####
|
BLD17-02437
| FIRE-Final Inspection | 8/25/2017 | 8/29/2017 | 8/29/2017 10:03:21 AM | A | FAIL |
|
|
Provide correct address and suite number, provide the missing sprinkler coverage under two of the three overhead doors, mount and tag fire extinguishers, provide missing fire sprinkler coverage near Offices, provide racking permits and high piled storage permits (encapsulated insulation (bags of insulation)), provide single action hardware on the Building Utility Room and provide a fire extinguisher in the same room, provide single action hardware and sticker at the main exit. provide exit discharge lighting as per plan. Provide annual inspection of the fire sprinkler system and provide fire sprinkler monitoring.
Chad Phone #: ###-####
|
BLD17-02439
| FIRE-Final Inspection | 8/25/2017 | 8/29/2017 | 8/29/2017 9:59:06 AM | A | FAIL |
|
|
Remove the thumbturn deadbolt and provide single action hardware. Keyed is ok on the main exit as discussed. Provide annual inspection tag for fire extinguishers. Provide correct building address and suite number.
Provide annual inspection of the fire sprinkler system and provide fire sprinkler monitoring. Chad Phone #: ###-####
|
BLD17-02436
| FIRE-Final Inspection | 8/25/2017 | 8/29/2017 | 8/29/2017 9:58:47 AM | A | FAIL |
|
|
Remove the thumbturn deadbolt. Keyed is ok on main exit with sticker and provide single action hardware. Provide correct building address and suite number.
Provide annual inspection of the fire sprinkler system and provide fire sprinkler monitoring. Chad Phone #: ###-####
|
BLD17-02435
| FIRE-Final Inspection | 8/25/2017 | 8/29/2017 | 8/29/2017 9:58:22 AM | A | FAIL |
|
|
Provide correct building address and suite number, remove thumbturn deadbolts and provide single action hardware. Keyed is ok at main exit. Sprinklers are too low in both Rest Rooms. Provide sprinkler coverage under the Mezzanine and under the overhead door. Provide racking permit for racks over 8' and storage over 12' in height.
Provide annual inspection of the fire sprinkler system and provide fire sprinkler monitoring. Chad Phone #: ###-####
|
BLD17-02434
| FIRE-Final Inspection | 8/25/2017 | 8/29/2017 | 8/29/2017 9:57:06 AM | A | FAIL |
|
|
Provide building address and correct suit number, provide missing sprinkler coverage in Server Room, replace painted head outside of Server Room at roof deck, straighten head under overhead door at northwest loction, delete pendant and provide sprinkler coverage under both northeast overhead doors, provide sprinkler coverage under stairs to mezzanine, provide racking permit for all racking over 8' or storage over 12', remove tape from sprinkler head in Office, replace bent sprinkler head in Restroom, remove thumbturn deadbolts from all doors, main exit can be keyed both sides with sticker as discussed. Provide submittals to plan review for the Spraying Operation that is taking place and provide sprinkler coverage for makeshift plastic booth. Provide annual inspection of the fire sprinkler system and provide fire sprinkler monitoring.
Chad Phone #: ###-####
|
NAF17-00007
| INSP-Final | 8/28/2017 | 8/29/2017 | 8/29/2017 12:00:00 AM | P | DONE |
|
|
Phone #: 2086150950 >> Inspection requested via mobile web by Roy
|
FIR17-00436
| INSP-Final Inspection | 8/28/2017 | 8/29/2017 | 8/28/2017 2:25:02 PM | A | PASS |
|
|
Permit finaled. Hood suppression system functioned correctly.
|