Inspections for the day of: Wednesday, August 30, 2017.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD17-00013 FIRE-Final Inspection8/29/20178/30/20178/30/2017 3:38:06 PMAFAIL
No city approved plans or small documents on site. No record of fire alarm permit for the relocation of the remote annunciator, pull station or horn strobe. Will need exit discharge light

Lori Phone #: ###-####
BLD17-00442 FIRE-Final Inspection8/29/20178/30/20178/30/2017 3:36:03 PMAFAIL
No inspection performed due to not city approved plans or small documents on site. Entire canopy has been relocated across parking lot and now may be interferring with an existing fire hydrant.

Lori Phone #: ###-####
BLD17-02218 FIRE-Final Inspection8/30/20178/30/20178/30/2017 2:27:29 PMPPASS
life safety passed
FIR17-00368 INSP-Final Inspection8/29/20178/30/20178/30/2017 2:27:03 PMPPASS
Permit finaled
FIR17-00472 INSP-Final Inspection8/30/20178/30/20178/30/2017 2:24:04 PMPCANC
Phone #: ###-#### Inspection requested via web by Don Kartchner
FIR17-00288 INSP-Final Inspection8/29/20178/30/20178/30/2017 2:23:51 PMACANC
Matt Phone #: ###-####
BLD16-02899 FIRE-Final Inspection8/29/20178/30/20178/30/2017 12:32:36 PMAFAIL
Todays inspection was just for a conference for the center portion of the building. I noted acouple of smoke detectors with issues.

Herb Phone #: ###-####
BLD17-03097 FIRE-Final Inspection8/29/20178/30/20178/30/2017 12:05:40 PMAPASS
life safety passed

Jorge Phone #: ###-####
BLD17-02754 FIRE-Final Inspection8/29/20178/30/20178/30/2017 10:32:05 AMAFAIL
No city approved plans on site. I performed a courtesy inspection and noted expired fire extinguisher and non-functional exit sign/emergency light in corridor. I also noted that the existing sprinkler system needs modifications to meet current code. There is exposed cpvc piping with pendants that are located too far from deck since the ceiling has been removed.

David Phone #: ###-####
BLD17-02828 FIRE-Final Inspection8/29/20178/30/20178/30/2017 10:30:28 AMAFAIL
No city approved plans on site. I performed a courtesy inspection and noted expired fire extinguisher and non-functional exit sign/emergency light in corridor.

David Phone #: ###-####