Inspections for the day of: Wednesday, August 31, 2016.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD16-00142 FIRE-Final Inspection8/31/20168/31/20168/31/2016 3:06:29 PMPFAIL
No approved plans or small documents on site. I went over general life safety requirements with the Operations Manager. It appears a racking permit will be required.

James Phone #: ###-####
BLD15-04293 FIRE-Final Inspection8/31/20168/31/20168/31/2016 1:28:39 PMPFAIL
Life safety will be ok to pass the existing fire alarm system has been modified for the new area. This work will require a permit.
BLD16-02309 FIRE-Final Inspection8/31/20168/31/20168/31/2016 1:07:10 PMPPASS
Life safety passed. Exit signs repaired.
FIR11-00296 FIR-Aging Inspection8/31/20168/31/20168/31/2016 11:24:33 AM NR
BLD16-01406 FIRE-Final Inspection8/30/20168/31/20168/31/2016 9:57:25 AMAFAIL
Need the project related fire alarm permit finaled. Need emergency lights and exit discharge lights repaired and tested. Fire extinguishers, door hardware and address appear ok. Need a permit applied for on the high piled/storage racks. Greg Phone #: ###-####
BLD16-02890 FIRE-Final Inspection8/30/20168/31/20168/31/2016 9:48:26 AMAFAIL
Provide single action hardware for all doors per the approved plans, remove the deadbolts from the south exit doors, provide exit sign per the approved plans.
FIR16-00460 INSP-Final Inspection8/30/20168/31/20168/31/2016 9:22:17 AMAFAIL
Resubmit plans showing the wire guage change, added strobes, changed candellas. Plans need to address the different NAC panel. I did test the sync which was ok. I did test the interconnection with the new dry pipe riser which was ok. I did not test the duct smoke detectors. Per general contractor security is being installed on the doors but will not hinder exiting in a single motion.
FIR16-00344 INSP-Final Inspection8/30/20168/31/20168/31/2016 9:18:59 AMAPASS
Permit finaled
FIR16-00496 INSP-Final Inspection8/30/20168/31/20168/31/2016 9:18:38 AMAPASS
Permit finaled
BLD16-02309 FIRE-Final Inspection8/30/20168/31/20168/31/2016 9:18:13 AMAFAIL
Repair exit signs and emergency lights as marked on the plans. Provide passage hardware as discussed through the Server Room
FIR16-00552 INSP-Sprinkler Rough-in/Hydro8/31/20168/31/20168/31/2016 12:00:00 AMPCANC
Cole Phone #: ###-####