NAF18-00061
| INSP-Sprinkler Rough-in | 8/6/2018 | 8/6/2018 | 8/6/2018 2:13:18 PM | P | PASS |
|
|
Porte-Coche rough-in passed. Piping can be covered.
Phone #: ###-#### Inspection requested via web by Matthew Lewis
|
FIR18-00511
| INSP-Sprinkler Rough-in/Hydro | 8/6/2018 | 8/6/2018 | 8/6/2018 1:37:23 PM | A | PART |
|
|
A partial hydro for the piping below the mezzanine passed. Piping above the hardlids below the mezzanine are ok to cover. I will need verification that the wood is rated or piping will need to be modified for upright coverage.
Call Anthony to schedule, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
BLD17-00339
| FIRE-Final Inspection | 8/3/2018 | 8/6/2018 | 8/6/2018 1:00:46 PM | P | PASS |
|
|
Life safety passed
Please final fire life safety permit once the fire alarm permit is signed off (FIR17-00683). Contact Dominick Fery - ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Jackie Phelps
|
FIR17-00683
| INSP-Final Inspection | 8/6/2018 | 8/6/2018 | 8/6/2018 12:59:59 PM | P | PASS |
|
|
Permit finaled
Phone #: ###-#### Inspection requested via web by Gary Gambino
|
BLD18-01694
| FIRE-Final Inspection | 8/3/2018 | 8/6/2018 | 8/6/2018 11:28:55 AM | A | PASS |
|
|
life safety passed
Phone #: ###-#### Inspection requested via web by Todd Landvatter
|
FIR18-00484
| INSP-Final Inspection | 8/6/2018 | 8/6/2018 | 8/6/2018 11:28:14 AM | P | PASS |
|
|
Permit finaled
Bryan Phone #: ###-####
|
NAF18-00013
| INSP-Final | 8/5/2018 | 8/6/2018 | 8/6/2018 9:36:59 AM | A | FAIL |
|
|
The elevator did not recall when the machine room detectyor was activated. The first and second floor levator lobby doors do not close/latch. Still need to test the shunt in the machine room.
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|