FIR19-00478
| INSP-Final Inspection | 9/9/2019 | 9/10/2019 | 9/11/2019 7:02:09 AM | P | PASS |
|
|
Permit finaled.
All of the bent piping appears to meet NFPA 13 6.3.8. Contact: Steven Vaughn Phone #: ###-#### Inspection requested via web by Hunter Fillmore
|
FIR19-00637
| INSP-Final Inspection | 9/9/2019 | 9/10/2019 | 9/10/2019 4:13:31 PM | P | PASS |
|
|
Permit finaled. Lee performed the inspection.
Call prior to going Phone #: 2086810381 >> Inspection requested via mobile web by Doug Lessa
|
FIR19-00626
| INSP-Final Inspection | 9/10/2019 | 9/10/2019 | 9/10/2019 4:09:26 PM | P | PASS |
|
|
permit finaled.
Zack Phone #: ###-####
|
FIR19-00653
| INSP-Final Inspection | 9/10/2019 | 9/10/2019 | 9/10/2019 4:08:55 PM | P | PASS |
|
|
permit finaled. Zack Phone #: ###-####
|
FIR18-00789
| INSP-Final Inspection | 9/6/2019 | 9/10/2019 | 9/10/2019 1:22:25 PM | P | FAIL |
|
|
Project is not ready for final yet. Todays inspection was to witness the fire pump certification. Final on shell and pump run with capital pump Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR19-00372
| INSP-Final Inspection | 9/9/2019 | 9/10/2019 | 9/10/2019 10:58:53 AM | P | CANC |
|
|
Call James before heading out, thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
|
FIR19-00290
| INSP-Sprinkler Rough-in | 9/10/2019 | 9/10/2019 | 9/10/2019 10:34:30 AM | P | PASS |
|
|
See the city approved plans for piping above the hardlids on first and second floors where piping is ok to cover. Todd Ketterling is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00374
| INSP-Sprinkler Rough-in | 9/9/2019 | 9/10/2019 | 9/10/2019 9:06:24 AM | A | PASS |
|
|
This is a duplicate inspection for approval to cover the two east most third floor apartments.
Gabe Garduno is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00662
| INSP-Sprinkler Rough-in | 9/10/2019 | 9/10/2019 | 9/10/2019 9:05:09 AM | P | PASS |
|
|
The underground supply piping is ok to cover from the point of connection to the last 45 fitting. The IBR, when installed, will need cover inspection.
Jon Beazer is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00478
| INSP-Sprinkler Rough-in | 9/9/2019 | 9/10/2019 | 9/10/2019 8:46:47 AM | A | PART |
|
|
The deflector distance from the ceiling has been corrected but the hydro test failed due to visible leakage. Contact: Steven Vaughn Phone #: ###-#### Inspection requested via web by Hunter Fillmore
|
FIR19-00221
| INSP-Sprinkler Rough-in | 9/9/2019 | 9/10/2019 | 9/10/2019 8:45:25 AM | A | PASS |
|
|
See the city approved plans for first floor piping locations that are ok for cover. Tom Phone #: ###-####
|