FIR19-00325
| INSP-Sprinkler Rough-in | 9/10/2019 | 9/11/2019 | 9/11/2019 3:45:44 PM | P | PASS |
|
|
Sprinkler coverage has been adjusted in the corridors. Sprinkler piping is ok for cover. Call Paul Vaughn an hour before heading to the site at Phone #: ###-#### Inspection requested via web by Matt Barnard
|
GRD18-00063
| FIRE-Final Inspection | 9/11/2019 | 9/11/2019 | 9/11/2019 2:39:04 PM | P | PASS |
|
|
Life safety passed. Phone #: ###-#### Inspection requested via web by Todd Landvatter
|
FIR19-00369
| INSP-Sprinkler Rough-in | 9/11/2019 | 9/11/2019 | 9/11/2019 2:37:41 PM | P | PASS |
|
|
Rough-in for the main piping re-route to the low ceiling area passed. As-builts are required prior to a final sign off. Piping can be covered. Rick Phone #: ###-####
|
FIR19-00290
| INSP-Sprinkler Rough-in | 9/10/2019 | 9/11/2019 | 9/11/2019 2:26:19 PM | P | PART |
|
|
Todays inspection was for a general rough-in. Piping for ceiling drops and overhead doors not installed yet and will require a separate inspection prior to cover. I noted several small deficiencies as noted on plans but mostly the rough-in is fine. Plan modifications are required showing the main piping routing changes which is to include the additional fitings and elevation changes.
Todd Ketterling is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00280
| INSP-Supply line flush | 9/11/2019 | 9/11/2019 | 9/11/2019 1:46:48 PM | P | CANC |
|
|
Could not perform inspection due to time constraints. Please call troy with time frame. Phone #: ###-#### Inspection requested via web by Jeff Packham
|
FIR19-00091
| INSP-Final Inspection | 9/11/2019 | 9/11/2019 | 9/11/2019 1:46:26 PM | P | CANC |
|
|
Could not perform inspection due to time constraints. Please call troy with time frame. Phone #: ###-#### Inspection requested via web by Jeff Packham
|
FIR19-00269
| INSP-Final Inspection | 9/11/2019 | 9/11/2019 | 9/11/2019 1:45:44 PM | P | CANC |
|
|
Could not perform inspection due to time constraints. Please call troy with time frame. Phone #: ###-#### Inspection requested via web by Jeff Packham
|
FIR19-00470
| INSP-Final Inspection | 9/11/2019 | 9/11/2019 | 9/11/2019 1:41:53 PM | P | CANC |
|
|
Not ready for final yet.
Darius Phone #: ###-####
|
FIR19-00470
| INSP-Sprinkler Rough-in | 9/11/2019 | 9/11/2019 | 9/11/2019 1:41:18 PM | P | FAIL |
|
|
Sprigs exceed 4' so they need bracing.
|
BLD19-03417
| FIRE-Final Inspection | 9/10/2019 | 9/11/2019 | 9/11/2019 12:58:37 PM | A | FAIL |
|
|
Need fire extinguishers as discussed, need hardware reversed as discussed. David Phone #: ###-#### PLEASE CALL FOR ACCESS- main office is just accross the street
|
FIR19-00475
| INSP-Sprinkler Rough-in | 9/10/2019 | 9/11/2019 | 9/11/2019 12:57:30 PM | A | FAIL |
|
|
Remove tape from heads, in a southwest office it appears a new upright head is blocked by round duct, in a northwest office a pendant head exceeds 9'-0" from a wall, an upright head needs to be added as per plans above a cloud ceiling assembly as marked on the plans.
Jon Beazer is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD19-00188
| FIRE-Final Inspection | 9/10/2019 | 9/11/2019 | 9/11/2019 10:53:35 AM | A | FAIL |
|
|
Relocate the building address so that it is viewable, provide additional exit sign as per approved plans, repair the east end exit discharge light.
Melvin Phone #: ###-####
|
BLD19-03466
| FIRE-Final Inspection | 9/10/2019 | 9/11/2019 | 9/11/2019 9:50:49 AM | A | PASS |
|
|
Life safety passed. No signature card on site .
call ahead // Kristin Winspear Phone #: ###-####
|
BLD19-03279
| FIRE-Final Inspection | 9/10/2019 | 9/11/2019 | 9/11/2019 9:16:14 AM | A | PASS |
|
|
Life safety passed.
Charlie- please CALL AND HOUR PRIOR, THANK YOU Phone #: ###-####
|
BLD18-02799
| FIRE-Final Inspection | 9/10/2019 | 9/11/2019 | 9/11/2019 8:57:11 AM | A | PASS |
|
|
Life safety passed. Phone #: ###-#### Inspection requested via web by Todd Landvatter
|
FIR19-00527
| INSP-Final Inspection | 9/10/2019 | 9/11/2019 | 9/11/2019 8:44:30 AM | A | PASS |
|
|
Permit finaled. Call Anthony before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR18-00866
| INSP-Final Inspection | 9/10/2019 | 9/11/2019 | 9/11/2019 8:27:58 AM | A | PASS |
|
|
Permit finaled. Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR18-00789
| INSP-Final Inspection | 9/10/2019 | 9/11/2019 | 9/11/2019 8:27:31 AM | A | PASS |
|
|
Permit finaled. Phone #: ###-#### Inspection requested via web by Sam Ball
|