Inspections for the day of: Tuesday, September 12, 2017.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00793 INSP-Sprinkler Rough-in/Hydro9/11/20179/12/20179/12/2017 2:50:59 PMPPASS
Overhead hydro test passed.

Jonathan Phone #: ###-####
BLD17-00525 FIRE-Final Inspection9/11/20179/12/20179/12/2017 2:36:48 PMPFAIL
No city approved plans on site. I spoke to Matt and deferred him to plan review, (Carl) on the use of security grills, thumbturn dead bolts and 2x4's. I noted that the fire extinguisher was expired.

Matt Phone #: ###-####
BLD17-02315 FIRE-Final Inspection9/12/20179/12/20179/12/2017 12:43:28 PMPPASS
life safety passed
BLD17-01932 FIRE-Final Inspection9/12/20179/12/20179/12/2017 10:45:39 AMPFAIL
Provide wheel stops as per review note #8 and provide grounds house keeping as per review note #9.

Rick Phone #: ###-####-you will find Rick at the rear of the property
FIR17-00515 INSP-Sprinkler Rough-in9/11/20179/12/20179/12/2017 10:18:51 AMAPART
Piping is ok to cover. The fitter only had a piping plan and none of the other documentation that is needed. No final sign off until as-builts are provided showing the actual pipe routing and all of the small documents for the submittal package. Installation will need to meet all requirements of the small documents for a sign off.
FIR17-00297 INSP-Final Inspection9/12/20179/12/20179/12/2017 9:27:47 AMPPASS
permit finaled
FIR17-00429 INSP-Final Inspection9/11/20179/12/20179/12/2017 9:26:13 AMPCANC
closer to 5 the better- Bill Phone #: ###-####
FIR16-00821 INSP-Sprinkler Rough-in9/11/20179/12/20179/12/2017 8:42:52 AMAPASS
Remaining rough-in for the piping in the east most building is passed. Hat track is ok to install but sheet rock is not ok to be installed until insulation in the combustible concealed spaces can be verified.
BLD17-01632 FIRE-Final Inspection9/11/20179/12/20179/12/2017 7:49:03 AMAPASS
Life safety passed. Suite number to be installed prior to a building inspection

Quinton Phone #: ###-####
FIR17-00386 INSP-Final Inspection9/11/20179/12/20179/12/2017 7:47:19 AMAPASS
Permit finaled
FIR17-00387 INSP-Final Inspection9/11/20179/12/20179/12/2017 7:46:46 AMAPASS
Permit finaled
FIR17-00406 INSP-Final Inspection9/11/20179/12/20179/12/2017 7:45:23 AMAPASS
Permit finaled