BLD19-03329
| FIRE-Final Inspection | 9/13/2019 | 9/16/2019 | 9/17/2019 3:01:53 PM | A | FAIL |
|
|
Provide certification for the hood suppression system, provide annual inspections for the fire extinguishers, lower the fire extinguisher on the main floor, repair the two exit signs/emergency lights, provide occupant load sign
Call ahead // Tony Phone #: ###-####
|
BLD17-02262
| FIRE-Final Inspection | 9/16/2019 | 9/16/2019 | 9/17/2019 2:07:35 PM | P | FAIL |
|
|
See the Fire Life Safety Plan Review Comments for items marked in red that need addressed which include finishing the fire alarm permit (added notification devices/elevator testing), fire dept access signage, additional fire extinguishers in common areas such as Laundry Rooms/Mail Rooms/Mechanical Rooms, Single action hardware for the common use rooms with sliding doors, verification that the Riser Room is one hour.....ect.
Curtis Phone #: ###-####
|
BLD17-02261
| FIRE-Final Inspection | 9/16/2019 | 9/16/2019 | 9/17/2019 2:07:02 PM | P | FAIL |
|
|
See the Fire Life Safety Plan Review Comments for items marked in red that need addressed which include finishing the fire alarm permit (added notification devices/elevator testing), fire dept access signage, additional fire extinguishers in common areas such as Laundry Rooms/Mail Rooms/Mechanical Rooms, Single action hardware for the common use rooms with sliding doors, verification that the Riser Room is one hour.....ect.
Curtis Phone #: ###-####
|
FIR18-00510
| INSP-Final Inspection | 9/13/2019 | 9/16/2019 | 9/17/2019 1:21:20 PM | A | CANC |
|
|
Cancel per Jason (job super) We would like to final 2nd and 3rd floor Phone #: ###-#### Inspection requested via web by Sam Ball
|
BLD17-03345
| FIRE-Final Inspection | 9/12/2019 | 9/16/2019 | 9/17/2019 1:20:40 PM | A | CANC |
|
|
Cancel per Jason Phone #: ###-####
|
NAF18-00146
| INSP-Final | 9/12/2019 | 9/16/2019 | 9/17/2019 9:45:48 AM | A | DONE |
|
|
life safety passed.
Call prior to going - around 10 am please-Phone #: 2088032461 >> Inspection requested via mobile web by Alan
|
BLD19-01077
| FIRE-Final Inspection | 9/16/2019 | 9/16/2019 | 9/16/2019 2:10:09 PM | P | CANC |
|
|
Please call 30 mins ahead of time so I can meet you there. Phone #: ###-#### >> Inspection requested via web by Gerome Fries Inspection cancelled from web by: Gerome Fries
|
NAF19-00060
| INSP-Final | 9/12/2019 | 9/16/2019 | 9/16/2019 12:00:00 AM | A | FAIL |
|
|
Chris Siewert, Technician. Phone #: ###-#### >> Inspection requested via web by John Siewert
Detectors pull stations and all notification tested. Notification had no problems. Detectors and ull stations did not report to the monitoring station.
|
FIR18-00503
| INSP-Final Inspection | 9/13/2019 | 9/16/2019 | 9/16/2019 12:00:00 AM | A | FAIL |
|
|
Audibility levels tested. Most areas exceeded the maximum allowable volume of 110 dB and peaked between 112 and 116. All areas need to be reduced to below 110 dB. jonathan Phone #: ###-####.
|
FIR19-00619
| INSP-Final Inspection | 9/13/2019 | 9/16/2019 | 9/16/2019 12:00:00 AM | A | CANC |
|
|
*Inspection was done on 9/16/2019* MAS**
Charles Lamb is the contact. Thank you for your hard work! Phone #: ###-#### >> Inspection requested via web by Stan Beus
|
FIR19-00309
| INSP-Final Inspection | 9/13/2019 | 9/16/2019 | 9/16/2019 12:00:00 AM | A | FAIL |
|
|
**Failed FDC piping that is exposed needs to be galvanzied. Location approved.*MAS**
Gabe Garduno is the contact for this final inspection. Thank you for your help. Have a nice day. Phone #: ###-#### >> Inspection requested via web by Stan Beus
|
FIR19-00619
| INSP-Final Inspection | 9/16/2019 | 9/16/2019 | 9/16/2019 12:00:00 AM | P | PASS |
|
|
*Passed * MAS**
Charles Lamb is the contact for this final inspection. He would like the soonest time slot you have. We appreciate your help. Thank you. Phone #: ###-#### >> Inspection requested via web by Stan Beus
|
FIR18-00934
| INSP-Final Inspection | 9/16/2019 | 9/16/2019 | 9/16/2019 12:00:00 AM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Ken Webster
Tested duct detectors and fan shutdown. All functioned properly. Verified all detectors previously too close to HVAC registers had been moved.
|
NAF19-00095
| INSP-Sprinkler Rough-in/Hydro | 9/15/2019 | 9/16/2019 | 9/16/2019 12:00:00 AM | P | PASS |
|
|
**Hydro passed*MAS**
Hydro only, tenting and rough passed last week. Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello
|
NAF19-00090
| INSP-Sprinkler Rough-in/Hydro | 9/15/2019 | 9/16/2019 | 9/16/2019 12:00:00 AM | P | PASS |
|
|
*Hydro passed * MAS**
Hydro only, tenting and rough passed last week. Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello
|
NAF19-00089
| INSP-Sprinkler Rough-in/Hydro | 9/15/2019 | 9/16/2019 | 9/16/2019 12:00:00 AM | P | PASS |
|
|
**Hydro passed * MAS**
Hydro only, tenting and rough passed last week. Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello
|
NAF19-00088
| INSP-Sprinkler Rough-in/Hydro | 9/15/2019 | 9/16/2019 | 9/16/2019 12:00:00 AM | P | PASS |
|
|
*Hydro passed * MAS**
Hydro only, tenting and rough passed last week. Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello
|
NAF19-00087
| INSP-Sprinkler Rough-in/Hydro | 9/15/2019 | 9/16/2019 | 9/16/2019 12:00:00 AM | P | PASS |
|
|
*Hydro passed* MAS**
Hydro only, tenting and rough passed last week. Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello
|
NAF19-00094
| INSP-Sprinkler Rough-in | 9/15/2019 | 9/16/2019 | 9/16/2019 12:00:00 AM | P | PASS |
|
|
**Tenting passed*MAS**
Tenting only, hydro and rough passed last week. Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello
|
NAF19-00091
| INSP-Sprinkler Rough-in | 9/15/2019 | 9/16/2019 | 9/16/2019 12:00:00 AM | P | PASS |
|
|
**Tenting passed*MAS**
Tenting only, hydro and rough passed last week. Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello
|
NAF19-00092
| INSP-Sprinkler Rough-in/Hydro | 9/15/2019 | 9/16/2019 | 9/16/2019 12:00:00 AM | P | PASS |
|
|
**Rough-in, hydro, and tenting passed *MAS**
Overhead rough, hydro and tenting. Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello
|
NAF19-00086
| INSP-Sprinkler Rough-in/Hydro | 9/15/2019 | 9/16/2019 | 9/16/2019 12:00:00 AM | P | PASS |
|
|
**Hydro and tenting passed * MAS**
Hydro and tenting needed, rough passed last week. Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello
|
NAF19-00085
| INSP-Sprinkler Rough-in/Hydro | 9/15/2019 | 9/16/2019 | 9/16/2019 12:00:00 AM | P | PASS |
|
|
**Hydro and Tenting passed* MAS**
Hydro and tenting needed, rough passed last week. Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello
|