Inspections for the day of: Monday, September 16, 2019.
Number of inspections: 23
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD19-03329 FIRE-Final Inspection9/13/20199/16/20199/17/2019 3:01:53 PMAFAIL
Provide certification for the hood suppression system, provide annual inspections for the fire extinguishers, lower the fire extinguisher on the main floor, repair the two exit signs/emergency lights, provide occupant load sign

Call ahead // Tony Phone #: ###-####
BLD17-02262 FIRE-Final Inspection9/16/20199/16/20199/17/2019 2:07:35 PMPFAIL
See the Fire Life Safety Plan Review Comments for items marked in red that need addressed which include finishing the fire alarm permit (added notification devices/elevator testing), fire dept access signage, additional fire extinguishers in common areas such as Laundry Rooms/Mail Rooms/Mechanical Rooms, Single action hardware for the common use rooms with sliding doors, verification that the Riser Room is one hour.....ect.

Curtis Phone #: ###-####
BLD17-02261 FIRE-Final Inspection9/16/20199/16/20199/17/2019 2:07:02 PMPFAIL
See the Fire Life Safety Plan Review Comments for items marked in red that need addressed which include finishing the fire alarm permit (added notification devices/elevator testing), fire dept access signage, additional fire extinguishers in common areas such as Laundry Rooms/Mail Rooms/Mechanical Rooms, Single action hardware for the common use rooms with sliding doors, verification that the Riser Room is one hour.....ect.

Curtis Phone #: ###-####
FIR18-00510 INSP-Final Inspection9/13/20199/16/20199/17/2019 1:21:20 PMACANC
Cancel per Jason (job super)
We would like to final 2nd and 3rd floor Phone #: ###-#### Inspection requested via web by Sam Ball
BLD17-03345 FIRE-Final Inspection9/12/20199/16/20199/17/2019 1:20:40 PMACANC
Cancel per Jason Phone #: ###-####
NAF18-00146 INSP-Final9/12/20199/16/20199/17/2019 9:45:48 AMADONE
life safety passed.

Call prior to going - around 10 am please-Phone #: 2088032461 >> Inspection requested via mobile web by Alan
BLD19-01077 FIRE-Final Inspection9/16/20199/16/20199/16/2019 2:10:09 PMPCANC
Please call 30 mins ahead of time so I can meet you there. Phone #: ###-#### >> Inspection requested via web by Gerome Fries Inspection cancelled from web by: Gerome Fries
NAF19-00060 INSP-Final9/12/20199/16/20199/16/2019 12:00:00 AMAFAIL
Chris Siewert, Technician. Phone #: ###-#### >> Inspection requested via web by John Siewert

Detectors pull stations and all notification tested. Notification had no problems. Detectors and ull stations did not report to the monitoring station.
FIR18-00503 INSP-Final Inspection9/13/20199/16/20199/16/2019 12:00:00 AMAFAIL
Audibility levels tested. Most areas exceeded the maximum allowable volume of 110 dB and peaked between 112 and 116. All areas need to be reduced to below 110 dB. jonathan Phone #: ###-####.
FIR19-00619 INSP-Final Inspection9/13/20199/16/20199/16/2019 12:00:00 AMACANC
*Inspection was done on 9/16/2019* MAS**
Charles Lamb is the contact. Thank you for your hard work! Phone #: ###-#### >> Inspection requested via web by Stan Beus
FIR19-00309 INSP-Final Inspection9/13/20199/16/20199/16/2019 12:00:00 AMAFAIL
**Failed FDC piping that is exposed needs to be galvanzied. Location approved.*MAS**
Gabe Garduno is the contact for this final inspection. Thank you for your help. Have a nice day. Phone #: ###-#### >> Inspection requested via web by Stan Beus
FIR19-00619 INSP-Final Inspection9/16/20199/16/20199/16/2019 12:00:00 AMPPASS
*Passed * MAS**
Charles Lamb is the contact for this final inspection. He would like the soonest time slot you have. We appreciate your help. Thank you. Phone #: ###-#### >> Inspection requested via web by Stan Beus
FIR18-00934 INSP-Final Inspection9/16/20199/16/20199/16/2019 12:00:00 AMPPASS
Phone #: ###-#### >> Inspection requested via web by Ken Webster

Tested duct detectors and fan shutdown. All functioned properly. Verified all detectors previously too close to HVAC registers had been moved.
NAF19-00095 INSP-Sprinkler Rough-in/Hydro9/15/20199/16/20199/16/2019 12:00:00 AMPPASS
**Hydro passed*MAS**
Hydro only, tenting and rough passed last week. Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello
NAF19-00090 INSP-Sprinkler Rough-in/Hydro9/15/20199/16/20199/16/2019 12:00:00 AMPPASS
*Hydro passed * MAS**
Hydro only, tenting and rough passed last week. Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello
NAF19-00089 INSP-Sprinkler Rough-in/Hydro9/15/20199/16/20199/16/2019 12:00:00 AMPPASS
**Hydro passed * MAS**
Hydro only, tenting and rough passed last week. Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello
NAF19-00088 INSP-Sprinkler Rough-in/Hydro9/15/20199/16/20199/16/2019 12:00:00 AMPPASS
*Hydro passed * MAS**
Hydro only, tenting and rough passed last week. Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello
NAF19-00087 INSP-Sprinkler Rough-in/Hydro9/15/20199/16/20199/16/2019 12:00:00 AMPPASS
*Hydro passed* MAS**
Hydro only, tenting and rough passed last week. Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello
NAF19-00094 INSP-Sprinkler Rough-in9/15/20199/16/20199/16/2019 12:00:00 AMPPASS
**Tenting passed*MAS**
Tenting only, hydro and rough passed last week. Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello
NAF19-00091 INSP-Sprinkler Rough-in9/15/20199/16/20199/16/2019 12:00:00 AMPPASS
**Tenting passed*MAS**
Tenting only, hydro and rough passed last week. Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello
NAF19-00092 INSP-Sprinkler Rough-in/Hydro9/15/20199/16/20199/16/2019 12:00:00 AMPPASS
**Rough-in, hydro, and tenting passed *MAS**
Overhead rough, hydro and tenting. Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello
NAF19-00086 INSP-Sprinkler Rough-in/Hydro9/15/20199/16/20199/16/2019 12:00:00 AMPPASS
**Hydro and tenting passed * MAS**
Hydro and tenting needed, rough passed last week. Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello
NAF19-00085 INSP-Sprinkler Rough-in/Hydro9/15/20199/16/20199/16/2019 12:00:00 AMPPASS
**Hydro and Tenting passed* MAS**
Hydro and tenting needed, rough passed last week. Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello