BLD17-02478
| FIRE-Final Inspection | 9/25/2018 | 9/25/2018 | 9/26/2018 7:17:36 AM | P | PART |
|
|
Life safety passed in the 03 and 04 apartments
Cody Phone #: ###-####
|
BLD18-02410
| FIRE-Final Inspection | 9/25/2018 | 9/25/2018 | 9/25/2018 3:03:58 PM | P | PART |
|
|
Partial on life safety until the demo permit for the fire alarm is scheduled.
Sid Phone #: ###-####
|
BLD17-02643
| FIRE-Final Inspection | 9/21/2018 | 9/25/2018 | 9/25/2018 3:02:47 PM | A | FAIL |
|
|
Need plans and small documents, need fire alarm notification modifications, need to repair exit sign
Lin Waterman Phone #: ###-####
|
NAF18-00074
| INSP-Final | 9/25/2018 | 9/25/2018 | 9/25/2018 2:01:37 PM | P | FAIL |
|
|
Life safety will be ok to final when a fire alarm permit is issued/passed for the required fire alarm modifications
Call prior to going Phone #: 9712757578 >> Inspection requested via mobile web by Deardry
|
NAF17-00065
| INSP-Final | 9/25/2018 | 9/25/2018 | 9/25/2018 2:00:34 PM | P | DONE |
|
|
Life safety passed
Call prior to going Phone #: 2088660325 >> Inspection requested via mobile web by Brett
|
BLD18-01515
| FIRE-Final Inspection | 9/24/2018 | 9/25/2018 | 9/25/2018 1:35:07 PM | A | FAIL |
|
|
Provide single action ADA hardware for the beer cooler, provide the duct smoke detectors per the approved drawings or get engineer approval to delete since the units are only 1600cfm, provide the CO ventilation and detection system as per review note #11
Phone #: ###-#### Inspection requested via web by Kenny Elumbaugh
|
FIR18-00385
| INSP-Final Inspection | 9/24/2018 | 9/25/2018 | 9/25/2018 12:43:34 PM | A | FAIL |
|
|
no approved plans or small documents
terry nelson Phone #: ###-#### Inspection requested via web by Brodie Stenquist
|
BLD17-01452
| FIRE-Final Inspection | 9/25/2018 | 9/25/2018 | 9/25/2018 12:41:26 PM | P | PASS |
|
|
Life safety passed. Bob is going to install a fire exitinguisher which I will verify on next inspection.
Call me when you head this way. Phone #: ###-#### Inspection requested via web by Bob Thornton
|
NAF18-00068
| INSP-Final | 9/24/2018 | 9/25/2018 | 9/25/2018 11:20:28 AM | A | FAIL |
|
|
Change the smoke detector to a heat and provide the CO detectors as per Lee's comments. Provide as-builts and document box. Provide testing of the type 1 hood suppression system and testing of the door mag interconnection.
Phone #: 2089196887 >> Inspection requested via mobile web by Derek
|
BLD18-02546
| FIRE-Final Inspection | 9/24/2018 | 9/25/2018 | 9/25/2018 10:59:10 AM | A | FAIL |
|
|
No plans or small documents on site. I did a quick inspection and noted that fire alarm modifications will be needed due to the new walls. Sprinkler protection appears ok.
Call before and please see front office for access. Thanks. Phone #: ###-#### Inspection requested via web by Vaughn Pruett
|
NAF18-00061
| INSP-Final | 9/24/2018 | 9/25/2018 | 9/25/2018 10:17:16 AM | A | DONE |
|
|
Permit finaled
FInal inspection to coincide with Fire Alarm Final. Jerermiah Robison is point of contact Phone #: ###-#### Inspection requested via web by Randy Knutson
|
FIR18-00546
| INSP-Sprinkler Rough-in/Hydro | 9/24/2018 | 9/25/2018 | 9/25/2018 10:13:34 AM | A | PASS |
|
|
Remaining piping rough-in for the northwest corner of the system where the ELO heads are located passed. Overhead hydro passed. I discussed the need for a forward flush test and permanant devices installed for this test.
Phone #: ###-#### Inspection requested via web by Connie Danes
|