Inspections for the day of: Tuesday, September 25, 2018.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD17-02478 FIRE-Final Inspection9/25/20189/25/20189/26/2018 7:17:36 AMPPART
Life safety passed in the 03 and 04 apartments


Cody Phone #: ###-####
BLD18-02410 FIRE-Final Inspection9/25/20189/25/20189/25/2018 3:03:58 PMPPART
Partial on life safety until the demo permit for the fire alarm is scheduled.

Sid Phone #: ###-####
BLD17-02643 FIRE-Final Inspection9/21/20189/25/20189/25/2018 3:02:47 PMAFAIL
Need plans and small documents, need fire alarm notification modifications, need to repair exit sign

Lin Waterman Phone #: ###-####
NAF18-00074 INSP-Final9/25/20189/25/20189/25/2018 2:01:37 PMPFAIL
Life safety will be ok to final when a fire alarm permit is issued/passed for the required fire alarm modifications


Call prior to going Phone #: 9712757578 >> Inspection requested via mobile web by Deardry
NAF17-00065 INSP-Final9/25/20189/25/20189/25/2018 2:00:34 PMPDONE
Life safety passed


Call prior to going Phone #: 2088660325 >> Inspection requested via mobile web by Brett
BLD18-01515 FIRE-Final Inspection9/24/20189/25/20189/25/2018 1:35:07 PMAFAIL
Provide single action ADA hardware for the beer cooler, provide the duct smoke detectors per the approved drawings or get engineer approval to delete since the units are only 1600cfm, provide the CO ventilation and detection system as per review note #11


Phone #: ###-#### Inspection requested via web by Kenny Elumbaugh
FIR18-00385 INSP-Final Inspection9/24/20189/25/20189/25/2018 12:43:34 PMAFAIL
no approved plans or small documents

terry nelson Phone #: ###-#### Inspection requested via web by Brodie Stenquist
BLD17-01452 FIRE-Final Inspection9/25/20189/25/20189/25/2018 12:41:26 PMPPASS
Life safety passed. Bob is going to install a fire exitinguisher which I will verify on next inspection.

Call me when you head this way. Phone #: ###-#### Inspection requested via web by Bob Thornton
NAF18-00068 INSP-Final9/24/20189/25/20189/25/2018 11:20:28 AMAFAIL
Change the smoke detector to a heat and provide the CO detectors as per Lee's comments. Provide as-builts and document box. Provide testing of the type 1 hood suppression system and testing of the door mag interconnection.


Phone #: 2089196887 >> Inspection requested via mobile web by Derek
BLD18-02546 FIRE-Final Inspection9/24/20189/25/20189/25/2018 10:59:10 AMAFAIL
No plans or small documents on site. I did a quick inspection and noted that fire alarm modifications will be needed due to the new walls. Sprinkler protection appears ok.


Call before and please see front office for access. Thanks. Phone #: ###-#### Inspection requested via web by Vaughn Pruett
NAF18-00061 INSP-Final9/24/20189/25/20189/25/2018 10:17:16 AMADONE
Permit finaled

FInal inspection to coincide with Fire Alarm Final.
Jerermiah Robison is point of contact Phone #: ###-#### Inspection requested via web by Randy Knutson
FIR18-00546 INSP-Sprinkler Rough-in/Hydro9/24/20189/25/20189/25/2018 10:13:34 AMAPASS
Remaining piping rough-in for the northwest corner of the system where the ELO heads are located passed. Overhead hydro passed. I discussed the need for a forward flush test and permanant devices installed for this test.

Phone #: ###-#### Inspection requested via web by Connie Danes