Inspections for the day of: Tuesday, September 5, 2017.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD16-02899 FIRE-Conference9/5/20179/5/20179/5/2017 3:23:30 PMPDONE
Started on life safety this morning. We tested exit signs and emergency lighting. I noted the two Garden area devices did not function. On a afternoon return trip the electrician had repaired the devices. No other items have been inspected yet since the bulk of time has been spent on the project related fire alarm permit.
FIR17-00040 INSP-Final Inspection9/4/20179/5/20179/5/2017 3:21:24 PMAFAIL
Arrived first thing in the morning to begin testing and found that the central station had not made the required changes to the device descriptions. I went back in the afternoon and was able to verify that the sprinkler system interconnections now are correct.
BLD17-01531 FIRE-Final Inspection8/30/20179/5/20179/5/2017 2:43:17 PMPFAIL
Provide city approved plans and review comments, remove the exit sign, provide sticker at main exit, remove thumbturn dead bolt, provide tag for fire extinguisher.
BLD17-01487 FIRE-Final Inspection9/5/20179/5/20179/5/2017 2:34:29 PMPPASS
Life safety passed
FIR16-00738 INSP-Final Inspection9/5/20179/5/20179/5/2017 2:34:03 PMPPASS
Permit finaled
FIR17-00327 INSP-Final Inspection9/5/20179/5/20179/5/2017 1:18:17 PMPPASS
Permit finaled
BLD17-01665 FIRE-Final Inspection8/29/20179/5/20179/5/2017 11:13:11 AMAFAIL
Provide verification of annual inspections on the fire alarm and fire sprinkler systems, Provide exiting paths, exit signs and emergency lighting as per approved plans.
FIR17-00467 INSP-Sprinkler Rough-in9/1/20179/5/20179/5/2017 10:22:10 AMAPASS
Rough-in passed. Piping can be covered.
FIR16-00284 INSP-Sprinkler Rough-in9/1/20179/5/20179/5/2017 10:21:44 AMAPASS
The fire sprinkler work in Suites 203, 204, 205, 206 and 302 is passed. The Closet light in Suite 106 still needs rotated. The Pantry head in Suite 101 has been corrected. I noted that a pendant is painted in Suite 208.
FIR17-00125 INSP-Final Inspection9/5/20179/5/20179/5/2017 12:00:00 AMPCANC
Rick Phone #: ###-#### Permit voided