Inspections for the day of: Thursday, September 5, 2019.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD19-03279 FIRE-Final Inspection9/3/20199/5/20199/6/2019 6:21:37 AMPCANC
Rescheduled for tomorrow. call for access- Charlie Phone #: ###-####
NAF19-00100 INSP-Sprinkler Rough-in9/5/20199/5/20199/5/2019 2:32:34 PMPPASS
Rough-in passed. Piping is ok for cover.

Jon Beazer is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
NAF19-00085 INSP-Sprinkler Rough-in/Hydro9/4/20199/5/20199/5/2019 2:30:01 PMPPART
Plan mods need to be submitted showing the actual pipe routing, fittings and additional supply to second floor. Need tenting inspection when complete. Rough-in appears ok, just need the plans to match. Also the short piece at the top of the riser has been installed 3/4" instead of 1". No piping to be covered yet.

Call Anthony before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
BLD18-03121 FIRE-Final Inspection9/5/20199/5/20199/5/2019 1:22:00 PMPPART
The six apartments, 1st through 3rd floors at the very north end of this building have the life safety passed. The FDC needs the required clearance as discussed prior to a final inspection. Matt Phone #: ###-####
FIR19-00309 INSP-Final Inspection9/4/20199/5/20199/5/2019 12:41:07 PMAPART
The fire sprinkler work in the six north end apartments is complete. 1st - 3rd floors. The fire alarm interconnect is complete. FDC nees relocated from the air conditioner condenser.

Gabe Garduno is the contact for this final inspection. Thank you for your help. Phone #: ###-#### Inspection requested via web by Stan Beus
BLD19-03360 FIRE-Final Inspection9/4/20199/5/20199/5/2019 10:35:00 AMAPASS
Life safety passed. Songa Phone #: ###-####
BLD19-03309 FIRE-Final Inspection9/4/20199/5/20199/5/2019 9:24:51 AMAFAIL
Provide annual inspection for the fire extinguisher, remove thumbturn dead bolt at main exit (keyed is ok) and provide sticker, remove round knob at main exit (single action lever type ok). Before 11 // Merinda Phone #: ###-####
FIR18-00697 INSP-Final Inspection9/4/20199/5/20199/5/2019 8:53:27 AMAPASS
Permit finaled
FIR19-00203 INSP-Final Inspection9/4/20199/5/20199/5/2019 8:25:26 AMAPASS
Permit finaled. Eric Phone #: ###-####
BLD19-00228 FIRE-Final Inspection9/4/20199/5/20199/5/2019 8:24:53 AMAPART
A temporary for life safety is ok per boise fire until the upgrade agreement for the fire alarm system has been finalized. Phone #: ###-#### Inspection requested via web by Russell Valline