Inspections for the day of: Wednesday, September 6, 2017.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR17-00307 INSP-Final Inspection9/5/20179/6/20179/6/2017 2:15:54 PMPPASS
Permit finaled for the scope of work.
BLD16-02899 FIRE-Conference9/6/20179/6/20179/6/2017 2:04:34 PMPDONE
Performed the rest of the life safety today. I need the project related fire alarm pemit finaled, NFPA signs for the oxygen room, provide fire dept access signage at the south entrance.
FIR17-00040 INSP-Final Inspection9/5/20179/6/20179/6/2017 11:17:18 AMAFAIL
Need the correct as-builts, map at the facp, test security doors interface, and record of completion.
FIR14-00701 INSP-Final Inspection9/5/20179/6/20179/6/2017 11:13:52 AMAFAIL
Not ready for final yet. Today we tested the additional strobe in the short corridor that was added. Hvac unit would not shut down upon activation of the smoke detector.