Inspections for the day of: Friday, September 6, 2019.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00662 INSP-Sprinkler Rough-in9/6/20199/6/20199/6/2019 2:12:46 PMPPART
See the city approved plans for the underground supply piping that is ok for cover.

Jon Beazer is the contact. Please call ahead of time so someone can meet the inspector out there. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR19-00325 INSP-Sprinkler Rough-in9/5/20199/6/20199/6/2019 1:55:06 PMPPART
Only the individual rooms are ok for cover. The corridors can not be covered due to overspaced pendant heads.

Approved Plans are onsite with the contractor. Please call Paul Vaughn before heading to job site at Phone #: ###-#### Inspection requested via web by Matt Barnard
FIR18-00789 INSP-Final Inspection9/6/20199/6/20199/6/2019 12:21:18 PMPCANC
Final on shell and pump run with capital pump. Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball
FIR19-00619 INSP-Final Inspection9/3/20199/6/20199/6/2019 11:38:56 AMAFAIL
Need the existing insulation secured back to the deck, need ceiling tile and T bar installed. I also noted that two heads outside of the scope of work are not the min. 6' apart. This will need to be addressed prior to a final building sign off. Kyle Koepnick is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR19-00612 INSP-Final Inspection9/3/20199/6/20199/6/2019 10:48:53 AMAPASS
Permit finaled. Later morning if possible. Please call Damien ###-#### to coordinate. Phone #: ###-#### Inspection requested via web by Kristin Dolan
NAF19-00065 INSP-Final9/5/20199/6/20199/6/2019 10:45:01 AMAFAIL
Two pendant heads are blocked in the southeast lower ceiling/room by surface mounted lights. One pendant in the high is still covered with tape. All other items appear okThank you have a nice day Phone #: ###-#### Inspection requested via web by jeremiah robison
FIR19-00251 INSP-Supply line flush9/5/20199/6/20199/6/2019 9:35:25 AMAPASS
Underground flush witnessed. 2,100 gallons of water flow verified with pitot guage.

Todd Ketterling is the contact. He would like this in the late AM. I''ve talked to Stacey with Suez and he is aware of this inspection. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
BLD19-03279 FIRE-Final Inspection9/5/20199/6/20199/6/2019 8:09:33 AMAFAIL
Provide street cacing address as discussed, remove thumbturn deadbolt at main exit (keyed ok), repair the exit sign at the main exit.

call for access- Charlie Phone #: ###-####
FIR19-00325 INSP-Final Inspection9/5/20199/6/20199/5/2019 4:08:49 PMPCANC
Approved Plans are onsite with the Contractor. Please Contact Paul Vaughn Before Heading to Job Site at Phone #: ###-#### >> Inspection requested via web by Matt Barnard Inspection cancelled from web by: Matt Barnard Inspection cancelled from web by: Matt Barnard