Inspections for the day of: Tuesday, October 13, 2015.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorDaryl DeGrange
TitleELE-INSPECTION SUPV
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-02093 Final10/12/201510/13/201510/13/2015 12:47:26 PMAFAIL
Andy Phone #: ###-#### Reverse polarity in first receptacle on left at front door NEC 210.8(A)(1) All 15 and 20 ampere 120 volt receptacles in bathrooms of and dwelling unit require GFCI protection. NEC 406.12(A) All 15 and 20 ampere receptacles are required to be Listed Tamper resistant, (pantry) NEC 408.7 Unsued openings for circuit breakers and switches shall be closed using identified closures
ELE15-01478 Final10/12/201510/13/201510/13/2015 11:33:21 AMAPASS
Call for garage code Phone #: ###-#### Inspection requested via web by Neal Rumsey final ok
ELE15-02907 Final10/13/201510/13/201510/13/2015 10:37:25 AMAFAIL
Please call Ron Chaney Phone #: ###-#### Inspection requested via web by Kevin Perez NEC 356.30 Securing and supporting
ELE12-02633 Final10/13/201510/13/201510/13/2015 10:34:06 AMAPASS
Job complete, final ok
ELE15-02910 Final10/13/201510/13/201510/13/2015 9:49:55 AMAPASS
Please Call Ron Chaney Phone #: ###-#### Inspection requested via web by Kevin Perez final ok