ELE19-00589
| Conference | 3/21/2019 | 3/22/2019 | 3/22/2019 3:47:04 PM | P | DONE |
|
|
Could you please meet us at 2:30 in the back of the store for a conference with fire guys and all involved. Thank you, Greg. Phone #: ###-#### Inspection requested via web by Greg Idsinga Discuss fire separation from domestic service gear and fire pump equipment
|
ELE16-02437
| ELE-Request for Extension | 3/22/2019 | 3/22/2019 | 3/22/2019 1:39:49 PM | P | PASS |
|
|
Mr. Seeliger has requested an Extension to complete his project. Extension ok
|
ELE18-01391
| Electrical Rough-In | 3/21/2019 | 3/22/2019 | 3/22/2019 12:39:11 PM | A | FAIL |
|
|
Contact Tony for level 3 area C above ceiling and casework. Phone #: ###-#### Inspection requested via web by Tom Betty NEC 330.12(1) MC cable shall not be installed where subject to physical damage. Raceway shall not be supported by luminair seismic wire.
|
ELE19-00940
| Electrical Rough-In | 3/21/2019 | 3/22/2019 | 3/22/2019 11:05:25 AM | A | PASS |
|
|
Please call Mike Cole ###-#### with any questions. Thank you! Phone #: ###-#### Inspection requested via web by Bonnie Page Rough-in ok cover entry, livingroom area
|
ELE19-00498
| Final | 3/22/2019 | 3/22/2019 | 3/22/2019 10:41:04 AM | A | PASS |
|
|
Home owners will be home, sub panel with arc fault breaker is in furnace room Phone #: ###-#### Inspection requested via web by steve sellers final ok
|
ELE18-04479
| Final | 3/21/2019 | 3/22/2019 | 3/22/2019 10:07:43 AM | A | FAIL |
|
|
Jay Phone #: ###-#### Chico sealant not poured in sealoffs
|
ELE19-00889
| Rough-In Permanent Service | 3/22/2019 | 3/22/2019 | 3/22/2019 9:21:43 AM | A | PASS |
|
|
Darryn Phone #: ###-#### Duplex rough-in p/s u/g n ok
|