Inspections for the day of: Wednesday, April 1, 2015.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorDaryl DeGrange
TitleELE-INSPECTION SUPV
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-00053 ELE-Aging Inspection4/1/20154/1/20154/9/2015 2:07:16 PM FAIL
NEC 334.30 NM cable shall be secured within 12 in. of conductor enter panel.
Shall protect MN cable from phyical damage.
Shall not terminate neutral of GFCI breaker in ground bar of four wire system.
Loose connection has caused burn damage to branch circuit neutral conductor, non-temper proof receptacles below. NEC 406.11 All 15 and 20 ampere120 volt receptacles shall be listed tamper-resistant receptacle, if install.ed at time of service upgrade
ELE15-00840 Rough-In Permanent Service4/1/20154/1/20154/1/2015 3:14:23 PMPFAIL
Phone #: ###-#### Inspection requested via web by Shaun Kirkman Fire chaulk outside soffit lumunaire wiring penetrations.
ELE14-02108 Final4/1/20154/1/20154/1/2015 2:37:05 PMPPASS
Inspection requested via web by Mike Cole correction done, final ok
ELE14-03229 Final4/1/20154/1/20154/1/2015 2:10:30 PMPPASS
The access code is 1130 Phone #: ###-#### Inspection requested via web by Stephen Kren correction done, final ok
ELE15-00856 Electrical Rough-In4/1/20154/1/20154/1/2015 2:02:30 PMPPASS
Phone #: ###-#### Inspection requested via web by John VanZandt rough-in ok cover master bedroom addition
ELE15-00795 Permanent Service3/25/20154/1/20154/1/2015 1:35:10 PMPPASS
Phone #: ###-#### Inspection requested via web by Eric Schroeder p/s u/g rec ok
ELE13-00686 ELE-Aging Inspection4/1/20154/1/20154/1/2015 12:59:11 PM DONE
Left message with contractor
ELE15-00828 Temporary Service3/31/20154/1/20154/1/2015 12:53:40 PMAPASS
Temp Pole Phone #: ###-#### Inspection requested via web by Rowdy Monroe t/s u/g n ok
ELE15-00715 Electrical Rough-In3/31/20154/1/20154/1/2015 12:31:23 PMPPART
Will meet you onsite to explain set up. Have Scheduled to coordinate with other electrical rough in on different permit at same address. Phone #: ###-#### Inspection requested via web by Matthew Dunay partial rough-in ok cover ceiling and walls
ELE15-00699 Electrical Rough-In3/31/20154/1/20154/1/2015 12:29:37 PMPPASS
Rough in inspection for garage and service conduits. Thank you Phone #: ###-#### Inspection requested via web by Thomas Jenkins rough-in garage and underground ok cover
ELE15-00855 Electrical Rough-In3/31/20154/1/20154/1/2015 11:55:26 AMAPASS
Underground conduit for elec. service Phone #: ###-#### Inspection requested via web by HZ ZAHIC Rough-in ok cover underground service feeder to house and detacted garage
ELE13-03208 Final4/1/20154/1/20154/1/2015 12:00:00 AMPCANC
Late as possible - Jenny Phone #: ###-####