Inspections for the day of: Tuesday, October 29, 2019.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorMike Jordan
TitleBLD-COM/RES INSPECTOR
Phone #794-9473
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD19-01486 BLD-Wall Bracing10/28/201910/29/201910/29/2019 4:18:41 PMPPASS
Phone #: ###-#### Inspection requested via web by Joel Hirtle
BLD19-02676 BLD-Final10/29/201910/29/201910/29/2019 3:03:39 PMPPASS
Please call if you have any questions. Phone #: ###-#### Inspection requested via web by Todd Morrison
BLD19-02676 DOC - Permit Finaled10/29/201910/29/201910/29/2019 3:03:38 PMPPASS
BLD19-02876 BLD-Final10/29/201910/29/201910/29/2019 2:34:40 PMPPASS
plans and permit are inside unit. Phone #: ###-#### Inspection requested via web by Todd Landvatter
BLD19-03643 BLD-Footing10/28/201910/29/201910/29/2019 1:28:14 PMPPASS
Phone #: 2089109404 >> Inspection requested via mobile web by Ricardo aggregate constru
MIS19-00337 BLD-Conference10/15/201910/29/201910/29/2019 12:45:50 PMADONE
Check on status... Spoke to Dave with Zer0rez carpet cleaning. (###-####). Noted he is working on getting plans from sundance and calcs for racking from materials handling.
BLD19-01682 BLD-Other10/29/201910/29/201910/29/2019 11:20:01 AMAPASS
Fire wall layer 2 inspection Phone #: ###-#### Inspection requested via web by Shawn Plimmer
BLD19-02307 BLD-Wall Bracing10/28/201910/29/201910/29/2019 10:57:15 AMAPASS
Phone #: ###-#### Inspection requested via web by Joel Hirtle
BLD19-02238 BLD-Ceiling Grid Inspection10/28/201910/29/201910/29/2019 10:26:16 AMAPASS
Chris Phone #: ###-####
BLD19-03111 BLD-Framing/Rough-in10/28/201910/29/201910/29/2019 9:46:15 AMAFAIL
Gari Phone #: ###-####. Repair notched 2x10 for 2nd. floor at tub drain. Provide additional stud under T7 2 ply truss. Nail webs on 2ply T10 truss per the engineering. Fireblock furred walls at double top plates in hallway @main entry. Can not verify tempered glazing in bathroom. Foam under tub in masterbedroom and pex in bottom plate at master shower. Complete lateral bracing on M11 and M12 trusses. Corection notice posted. ok to insulate.