Inspections for the day of: Monday, January 13, 2020.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00703 INSP-Sprinkler Rough-in1/13/20201/13/20201/13/2020 3:34:46 PMPPART
Rough to cover inspection for remaining level 5 overhead fire sprinkler piping complete, level 5 approved for cover.

Mike Phone #: ###-####
FIR20-00020 INSP-Final Inspection1/13/20201/13/20201/13/2020 3:34:02 PMPPART
Rough to cover inspection for stub up and approximately 8 feet of pipe from footing complete, piping inspected approved for cover, remainder of piping to be installed at a later date.

Underground inspection for cover. Phone #: ###-#### Inspection requested via web by Jessia Maxwell
BLD19-00727 FIRE-Final Inspection1/13/20201/13/20201/13/2020 3:32:36 PMPPASS
Previously noted items have been corrected, final life fire safety inspection for area of work complete.
FIR20-00010 INSP-Final Inspection1/13/20201/13/20201/13/2020 3:31:52 PMPPASS
Final fire alarm inspection for scope of work complete.

BLD19-03974 FIRE-Final Inspection1/10/20201/13/20201/13/2020 12:24:44 PMAPASS
No fire sprinkler modifications, no fire alarm modifications, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for area of work complete.

AJ Phone #: ###-####
FIR18-00224 INSP-Final Inspection1/10/20201/13/20201/13/2020 12:00:21 PMAPASS
Final inspection for AES communicator complete.

Please check in at School office. District and alarm personnel will be on site. Phone #: ###-#### Inspection requested via web by Jeff Gooch
BLD19-02053 FIRE-Final Inspection1/13/20201/13/20201/13/2020 11:32:54 AMPCANC
Cancelled per conversation with point of contact, will be requested for a later date.

ronald Phone #: ###-####
FIR20-00020 INSP-Final Inspection1/13/20201/13/20201/13/2020 11:14:40 AMPCANC
Please call Chris Ford Phone #: ###-#### >> Inspection requested via web by Jessia Maxwell Inspection cancelled from web by: Jessia Maxwell
FIR19-00601 INSP-Sprinkler Rough-in1/12/20201/13/20201/13/2020 11:05:23 AMAFAIL
Appears that no corrections to tenting have been made, reference notes entered on the 09JAN2020 inspection.

Tenting. Call James when heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR17-00178 INSP-Final Inspection1/10/20201/13/20201/13/2020 10:37:10 AMAFAIL
Overspaced audio visual devices in electrical room area, section 10 area 90. Notated city approved draiwngs areas where candella setting was incorrect, inspection was stopped after 6 deficiencies.

Dillion Phone #: ###-####
BLD19-03650 FIRE-Conference1/10/20201/13/20201/13/2020 9:04:53 AMADONE
Fire conference complete, discussed temporary install of elevator lobby doors due to finish doors being on order, advised point of contact to discuss with structural, if no issue with structural inspector then doors/frames can be used for temp.

Zach Phone #: ###-####