Inspections for the day of: Monday, January 14, 2019.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR18-00382 INSP-Final Inspection1/11/20191/14/20191/14/2019 4:56:23 PMPPASS
Final fire sprinkler inspection complete.

POC is Zack Grasmick Phone #: ###-#### Inspection requested via web by Brett Lawatch
FIR18-00617 INSP-Final Inspection1/11/20191/14/20191/14/2019 1:28:39 PMPPASS
Final fire sprinkler inspection for area of work complete.

POC is Zack Grasmick Phone #: ###-#### Inspection requested via web by Brett Lawatch
FIR17-00474 INSP-Sprinkler Rough-in/Hydro1/11/20191/14/20191/14/2019 1:27:36 PMPDONE
Hydrostatic test for overehad fire sprinkler piping witnessed, no pressure loss observed.

Hydrostatic test. Jeff Chaney is the contact. Phone #: ###-#### Inspection requested via web by Stan Beus
BLD18-00884 FIRE-Final Inspection1/11/20191/14/20191/14/2019 1:26:54 PMPFAIL
Spoke with fire alarm contractor, in duct detectors on RTU's suppling main open area are not hooked to fire panel, FIR permit for fire alarms needs to be finaled before life fire safety inspection.

Kevin Phone #: ###-####
FIR18-00610 INSP-Sprinkler Rough-in/Hydro1/14/20191/14/20191/14/2019 12:28:11 PMPPART
Rough to cover inspection for overhead fire sprinkler piping located above hardlids on level 1 complete, level 1 hardlids approved for cover.

Mike Phone #: ###-####
FIR19-00006 INSP-Sprinkler Rough-in1/14/20191/14/20191/14/2019 11:52:33 AMPPART
Rough in inspection for overhead fire sprinkler piping complete, piping between conditioned spaces approved for cover, areas requiring tenting not approved for cover until tenting install is inspected and approved.
FIR19-00006 INSP-Sprinkler Rough-in/Hydro1/11/20191/14/20191/14/2019 11:50:37 AMPDONE
Hydrostatic test for overhead fire sprinkler piping witnessed with antifreeze puped up to city pressure, no pressure loss observed.

Call before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR18-00382 INSP-Sprinkler Rough-in1/14/20191/14/20191/14/2019 11:02:56 AMAPASS
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.
FIR18-00382 INSP-Sprinkler Rough-in/Hydro1/11/20191/14/20191/14/2019 11:01:50 AMADONE
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed.

Hydro Test for Overhead System. POC is Zack Grasmick Phone #: ###-#### Inspection requested via web by Brett Lawatch
FIR18-00623 INSP-Final Inspection1/11/20191/14/20191/14/2019 10:21:36 AMAFAIL
Hood suppression system did not report to the fire panel on system activation. Power to lights and outlets did not shunt when test link was cut.

Seth Phone #: ###-####
BLD19-00058 FIRE-Final Inspection1/11/20191/14/20191/14/2019 9:43:56 AMAPASS
No fire sprinkler modifications, no fire alarm modifications, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for area of work complete.

Matt Phone #: ###-####
BLD19-00060 FIRE-Final Inspection1/11/20191/14/20191/14/2019 9:43:38 AMAPASS
No fire sprinkler modifications, no fire alarm modifications, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for area of work complete.

Matt Phone #: ###-####
FIR18-00862 INSP-Sprinkler Rough-in1/14/20191/14/20191/14/2019 9:15:47 AMAPASS
Rough in inspection for dry system complete.

Contact Noemi Carrero ###-#### 30 min prior to RTC Insp on DRY SYSTEM start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
FIR18-00862 INSP-Supply line flush1/11/20191/14/20191/14/2019 9:14:49 AMADONE
Underground main line flush complete.

Contacts will be Tanner Loomis - PFP ###-#### ; Stacy Stuart - SUEZ ###-####..All Parties would like to request a 9:00AM start time if possible, if not please let them know.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
BLD18-02027 FIRE-Final Inspection1/11/20191/14/20191/14/2019 8:11:05 AMAPASS
Final life fire safety inspection for area of work complete.

Daryl Phone #: ###-####
FIR18-00382 INSP-Sprinkler Rough-in/Hydro1/11/20191/14/20191/11/2019 2:34:02 PMPCANC
Hydro test to be performed same time as permit FIR18-00617. POC is Zack Grasmick Phone #: ###-#### >> Inspection requested via web by Brett Lawatch Inspection cancelled from web by: Brett Lawatch
FIR18-00617 INSP-Sprinkler Rough-in/Hydro1/11/20191/14/20191/11/2019 2:33:41 PMPCANC
Hydro test to be perfromed same time as permit FIR18-00382. POC is Zack Grasmick Phone #: ###-#### >> Inspection requested via web by Brett Lawatch Inspection cancelled from web by: Brett Lawatch