Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR17-00612 INSP-Sprinkler Rough-in1/14/20191/15/20191/15/2019 4:25:43 PMPPASS
Rough to cover inspection for dry system in new canopy complete, approved for cover.

Gabe is the contact Phone #: ###-#### Inspection requested via web by Stan Beus
FIR18-00605 INSP-Final Inspection1/15/20191/15/20191/15/2019 2:12:17 PMPPASS
Final fire sprinkler inspection for area of work complete.

don forester Phone #: ###-#### Inspection requested via web by Brodie Stenquist
BLD18-03429 FIRE-Final Inspection1/14/20191/15/20191/15/2019 10:42:03 AMAFAIL
Provide fire sprinkler in new restroom. Fire sprinkler heads are to close to beam that has been covered with sheetrock, need a minimum of 4 inches from center of sprinkler head to wall. Install addressing for tenant space.

Call 30 min before for access. Phone #: ###-#### Inspection requested via web by Tyson Jardine
BLD18-01329 FIRE-Final Inspection1/14/20191/15/20191/15/2019 10:20:27 AMAPASS
Final life fire safety inspection for area of work complete.

Todd-please call 30 minutes prior for access Phone #: ###-####
BLD18-02596 FIRE-Final Inspection1/14/20191/15/20191/15/2019 9:55:16 AMAPART
Fire sprinkler inspection complete, fire alarms to be completed at a later date, fire exitnguishers are placed with current inspection tags. TCO authorized for life fire safety for 30 days per conversation with Ron Johnson.

Doug Phone #: ###-####
FIR18-00725 INSP-Final Inspection1/15/20191/15/20191/15/2019 9:53:14 AMPPASS
Final fire sprinkler inspection for area of work complete.

Phone #: ###-#### Inspection requested via web by Jeff Packham
BLD18-00884 FIRE-Final Inspection1/14/20191/15/20191/15/2019 9:07:07 AMAPART
Life fire safety inspection for TCO of cafeteria expansion complete.

Please call Kevin Phone #: ###-#### Inspection requested via web by Chris Fuhrman
FIR18-00740 INSP-Alarm Testing1/14/20191/15/20191/15/2019 9:06:12 AMADONE
Fire alarm testing for TCO requested area of cafeteria complete, horn strobes are in place, speaker strobes to be installed for final inspection.

As early as possible Phone #: 2088990672 >> Inspection requested via mobile web by Josiah Froese