Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00559 INSP-Final Inspection1/13/20201/15/20201/15/2020 4:08:30 PMPPART
Inspection performed by Lee Meridith, reference notes entered under Jim Page name on the 15JAN2019 for remaining items that need to be tested as well as correction items.

We are ready for a gander -Neal T. ###-#### Phone #: ###-#### Inspection requested via web by Neal Timmerman
BLD19-00658 FIRE-Conference1/15/20201/15/20201/15/2020 3:53:02 PMPDONE
Follow up conference scheduled for 16JAN2020 for question asked about attic sprinkler coverage, need further verification for sprinkler head coverage in question.

Josh Phone #: ###-####
BLD19-04756 FIRE-Final Inspection1/15/20201/15/20201/15/2020 3:50:39 PMPCANC
Alice Phone #: ###-####
FIR19-00940 INSP-Sprinkler Rough-in1/14/20201/15/20201/15/2020 3:50:27 PMPPASS
Rough to cover inspection for underground supply and remote FDC complete, approved for cover.

Underground rough to cover. Call James before heading out. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
BLD19-04765 FIRE-Final Inspection1/15/20201/15/20201/15/2020 3:46:56 PMPPASS
Previously noted items by Mike Jordan have been corrected, no fire sprinklers, no fire alarms, fire exitnguishers are placed with current inspection tags. Final life fire safety inspection for area of work complete, signature provided on permit sign off card.
FIR18-00858 INSP-Final Inspection1/14/20201/15/20201/15/2020 2:32:55 PMPPART
No noted items for level 1 walkthrough.

Call prior to going Phone #: 2086810381 >> Inspection requested via mobile web by Doug Lessa
FIR18-00840 INSP-Final Inspection1/14/20201/15/20201/15/2020 2:31:47 PMPFAIL
Items requiring correction have been notated on city approved draiwngs. Level 1 has an A/V device missing, candella setings that do not match the plans and a couple of A/V's that are overspaced.

Call prior to going Phone #: 2086810381 >> Inspection requested via mobile web by Doug Lessa
FIR19-00906 INSP-Sprinkler Rough-in1/14/20201/15/20201/15/2020 11:03:18 AMACANC
Piping was covered in snow and concrete blanket, piping/fitting could not be seen in the trench, inspection will need to be rescheduled when pipe is visible, this request is cancelled.

Underground rough to cover. Call James before heading out. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
BLD19-03936 FIRE-Final Inspection1/14/20201/15/20201/15/2020 11:01:55 AMAFAIL
2 areas have fire sprinklers that are less than 6 feet apart, fire sprinkler modifications are required for area of work to be compliant with NFPA13. Any and all fire sprinkler modifications requires a seperate permit.

are will be onsite after 9am. Phone #: ###-#### Inspection requested via web by Kirsten Dallmann
BLD19-04374 FIRE-Final Inspection1/15/20201/15/20201/15/2020 10:21:20 AMAPASS
Previously noted items have been corrected, final life fire safety inspection for area of work complete, signatures provided on permit sign off card.
FIR20-00025 INSP-Final Inspection1/14/20201/15/20201/15/2020 9:38:20 AMAPASS
Final fire alarm inspection for area of work complete.

Inspecting technician: Ray McQueen, building has open access Phone #: ###-#### Inspection requested via web by Rose Peterson
BLD18-01083 FIRE-Conference1/14/20201/15/20201/15/2020 9:16:12 AMACANC
Conference anceled per voicemail from point of contact, will be rescheduled for a later date.

call prior mike Phone #: ###-####
BLD19-03650 FIRE-Final Inspection1/14/20201/15/20201/15/2020 9:15:24 AMACANC
Fire alarm permit is still in issued status, needs finaled before life fire safety can be completed, this request is cancelled.

Zach Phone #: ###-####
BLD19-00416 FIRE-Final Inspection1/14/20201/15/20201/15/2020 9:12:18 AMAPASS
Previously noted items have been corrected, final life fire safety inspection for area of work complete.

Bruce Phone #: ###-####
BLD19-04945 FIRE-Final Inspection1/14/20201/15/20201/14/2020 9:53:37 AMAPASS
No fire sprinkler modifications, no fire alarm modifications, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection for area of work complete, signatures provided on permit sign off card.

Tim Phone #: ###-####