BLD18-02978
| FIRE-Final Inspection | 1/15/2019 | 1/16/2019 | 1/16/2019 12:57:22 PM | A | FAIL |
|
|
FIR permit for fire sprinklers is still in issued status, need to perfrom fire sprinkler inspection and verify all combustible material above ceilings has been covered and that mentioned items on fire sprinkler rough in inspection have been completed.
Megual Phone #: ###-####
|
FIR17-00508
| INSP-Final Inspection | 1/15/2019 | 1/16/2019 | 1/16/2019 12:53:44 PM | A | FAIL |
|
|
Networking is not set up between panel and monitoring, did not test any signals due to no verification of alarm through monitoring, no other items were inspected.
request late morning - between 11 and noon inspection. Contact Gary for specific time. Thanks! Phone #: ###-#### Inspection requested via web by Shane Lesteberg
|
FIR17-00474
| INSP-Final Inspection | 1/15/2019 | 1/16/2019 | 1/16/2019 12:52:22 PM | A | FAIL |
|
|
Radius ceiling tiles hang down 7 inches from the ceiling, tile locations to sprinkler heads are not code compliant based on tables 8.6.5.1.2 for standard spray sprinklers and table 8.8.5.1.2 for the extended coverage heads per NFPA13. No other items were inspected.
Mark Jensen is the contact. Thank you! Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD14-03039
| FIRE-Final Inspection | 1/10/2019 | 1/16/2019 | 1/16/2019 11:17:42 AM | A | PASS |
|
|
Fire sprinkler inspection for core and shell complete, final fire alarm inspection for core and shell complete, fire extinguishers are placed with current inspection tags, knox box is located by front entry. Final life fire safety inspection for core and shell complete, no occupancy allowed under this permit, a seperate permit will be required for tenant occupancy.
Antonio Phone #: ###-####
|
FIR18-00541
| INSP-Sprinkler Rough-in | 1/15/2019 | 1/16/2019 | 1/16/2019 10:34:19 AM | A | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping above hardlids in locker room areas complete, notated city approved drawings with red ink areas appropved for cover.
Kurt Phone #: ###-####
|
BLD18-02463
| FIRE-Final Inspection | 1/9/2019 | 1/16/2019 | 1/16/2019 10:08:05 AM | A | PASS |
|
|
No fire sprinklers, no fire alarm modifications, fire extinguisher will be placed in discussed location. Final life fire safety inspection for area of work complete.
Call 10 minutes ahead // Shane Phone #: ###-####
|
FIR18-00842
| INSP-Final Inspection | 1/10/2019 | 1/16/2019 | 1/16/2019 9:34:25 AM | A | PASS |
|
|
Final fire alarm inspection for scope of work complete.
Please call Jason Petty roughly 15-20 minutes prior to arrival. ###-#### or ###-#### x611 Phone #: ###-#### Inspection requested via web by jason petty
|
FIR14-00912
| INSP-Final Inspection | 1/10/2019 | 1/16/2019 | 1/16/2019 8:30:27 AM | P | CANC |
|
|
Final fire sprinkler inspection for core and shell was complete under FIR18-00718.
Antonio Phone #: ###-####
|
FIR15-00052
| INSP-Final Inspection | 1/10/2019 | 1/16/2019 | 1/16/2019 8:28:53 AM | P | CANC |
|
|
Final inspection for fire alarm system was completed under FIR18-00777.
Antonio Phone #: ###-####
|