Inspections for the day of: Wednesday, January 16, 2019.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD18-02978 FIRE-Final Inspection1/15/20191/16/20191/16/2019 12:57:22 PMAFAIL
FIR permit for fire sprinklers is still in issued status, need to perfrom fire sprinkler inspection and verify all combustible material above ceilings has been covered and that mentioned items on fire sprinkler rough in inspection have been completed.

Megual Phone #: ###-####
FIR17-00508 INSP-Final Inspection1/15/20191/16/20191/16/2019 12:53:44 PMAFAIL
Networking is not set up between panel and monitoring, did not test any signals due to no verification of alarm through monitoring, no other items were inspected.

request late morning - between 11 and noon inspection. Contact Gary for specific time. Thanks! Phone #: ###-#### Inspection requested via web by Shane Lesteberg
FIR17-00474 INSP-Final Inspection1/15/20191/16/20191/16/2019 12:52:22 PMAFAIL
Radius ceiling tiles hang down 7 inches from the ceiling, tile locations to sprinkler heads are not code compliant based on tables 8.6.5.1.2 for standard spray sprinklers and table 8.8.5.1.2 for the extended coverage heads per NFPA13. No other items were inspected.

Mark Jensen is the contact. Thank you! Phone #: ###-#### Inspection requested via web by Stan Beus
BLD14-03039 FIRE-Final Inspection1/10/20191/16/20191/16/2019 11:17:42 AMAPASS
Fire sprinkler inspection for core and shell complete, final fire alarm inspection for core and shell complete, fire extinguishers are placed with current inspection tags, knox box is located by front entry. Final life fire safety inspection for core and shell complete, no occupancy allowed under this permit, a seperate permit will be required for tenant occupancy.

Antonio Phone #: ###-####
FIR18-00541 INSP-Sprinkler Rough-in1/15/20191/16/20191/16/2019 10:34:19 AMAPART
Rough to cover inspection for overhead fire sprinkler piping above hardlids in locker room areas complete, notated city approved drawings with red ink areas appropved for cover.

Kurt Phone #: ###-####
BLD18-02463 FIRE-Final Inspection1/9/20191/16/20191/16/2019 10:08:05 AMAPASS
No fire sprinklers, no fire alarm modifications, fire extinguisher will be placed in discussed location. Final life fire safety inspection for area of work complete.

Call 10 minutes ahead // Shane Phone #: ###-####
FIR18-00842 INSP-Final Inspection1/10/20191/16/20191/16/2019 9:34:25 AMAPASS
Final fire alarm inspection for scope of work complete.

Please call Jason Petty roughly 15-20 minutes prior to arrival. ###-#### or ###-#### x611 Phone #: ###-#### Inspection requested via web by jason petty
FIR14-00912 INSP-Final Inspection1/10/20191/16/20191/16/2019 8:30:27 AMPCANC
Final fire sprinkler inspection for core and shell was complete under FIR18-00718.

Antonio Phone #: ###-####
FIR15-00052 INSP-Final Inspection1/10/20191/16/20191/16/2019 8:28:53 AMPCANC
Final inspection for fire alarm system was completed under FIR18-00777.

Antonio Phone #: ###-####