FIR19-00489
| INSP-Sprinkler Rough-in | 1/16/2020 | 1/16/2020 | 1/16/2020 3:58:59 PM | P | CANC |
|
|
Rescheduled for 17JAN2020, this request is cancelled.
Todd Ketterling is the contact. Thanks for all you do! Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD19-01465
| FIRE-Final Inspection | 1/15/2020 | 1/16/2020 | 1/16/2020 3:58:27 PM | P | PASS |
|
|
Fire sprinkler inspection is complete, no fire alarm modifications, fire extinguishers are in common areas with current inspection tags. Final life fire safety inspection for area of work complete, signature card not provided at time of inspection.
Fire life safety inspection on boise center front vestibule. Phone #: ###-#### Inspection requested via web by Jake Wilson
|
BLD19-00658
| FIRE-Conference | 1/15/2020 | 1/16/2020 | 1/16/2020 3:57:11 PM | A | CANC |
|
|
Josh ###-####
|
BLD19-00278
| FIRE-Final Inspection | 1/16/2020 | 1/16/2020 | 1/16/2020 2:01:37 PM | P | FAIL |
|
|
Ceiling was installed under southeast stairs, sprinkler head in room is overspaced, provide fire sprinkler under southeast stairs.
Fire/Life/ Safety. Please call when headed to the site. Phone #: ###-#### Inspection requested via web by Corey Hockersmith
|
FIR19-00589
| INSP-Sprinkler Rough-in/Hydro | 1/15/2020 | 1/16/2020 | 1/16/2020 12:46:46 PM | P | DONE |
|
|
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed at riser provided guage.
Please contact Troy Nelson for an inspection time. Phone #: ###-#### Inspection requested via web by Daniel Buccino
|
FIR19-00589
| INSP-Sprinkler Rough-in | 1/16/2020 | 1/16/2020 | 1/16/2020 12:44:25 PM | P | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping complete. Notated city approved plans with red ink areas approved for cover. South side tenant spaces show grided ceiling being installed, grid to be installed with future tenants. City approved plans need to reflect deletion of pendant heads.
|
FIR19-00642
| INSP-Final Inspection | 1/15/2020 | 1/16/2020 | 1/16/2020 11:14:31 AM | A | FAIL |
|
|
Fire panel showed communication trouble at time of inspection. Speaker strobes are not intelelligibly audible, troubleshoot for audio level.
Christin - Phone #: ###-####
|
FIR19-00935
| INSP-Final Inspection | 1/15/2020 | 1/16/2020 | 1/16/2020 11:14:15 AM | A | FAIL |
|
|
Fire panel showed communication trouble at time of inspection. Speaker strobes are not intelelligibly audible, troubleshoot for audio level.
Test needs to be after 9:00 am Phone #: ###-#### Inspection requested via web by Kristin Dolan
|
FIR19-00906
| INSP-Sprinkler Rough-in | 1/15/2020 | 1/16/2020 | 1/16/2020 10:22:24 AM | A | PASS |
|
|
Remaining pipe for tie in inspection complete, approved for cover.
Call James before heading out, he will make sure the blanket is off and pipe is visible. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
BLD19-00294
| FIRE-Final Inspection | 1/15/2020 | 1/16/2020 | 1/16/2020 10:07:16 AM | A | PASS |
|
|
No fire sprinklers, no fire alarms, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for scope of work is complete.
Nate Phone #: ###-####
|
BLD19-01331
| FIRE-Final Inspection | 1/15/2020 | 1/16/2020 | 1/16/2020 10:06:56 AM | A | PASS |
|
|
No fire sprinklers, no fire alarms, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for scope of work is complete.
Nate Phone #: ###-####
|
BLD19-02117
| FIRE-Final Inspection | 1/16/2020 | 1/16/2020 | 1/16/2020 10:05:53 AM | A | PASS |
|
|
Fire alarm inspection complete, no fire sprinklers, fire extinguishers not required for this scope, final life fire safety inspection for scope of work complete, signature card not available at time of inspection, no signatures provided.
|
BLD19-03650
| FIRE-Final Inspection | 1/15/2020 | 1/16/2020 | 1/16/2020 9:19:55 AM | A | PART |
|
|
Partial final life fire safety inspection complete, fire alarm inspection is complete, fire sprinkler inspection is complete, fire extiguishers are placed with current inspection tags. Premenant doors for elevator lobby are on order, temporary doors have been placed for smoke control. 30 day TCO authorized.
zach Phone #: ###-####
|
FIR20-00002
| INSP-Final Inspection | 1/15/2020 | 1/16/2020 | 1/16/2020 9:17:19 AM | A | PASS |
|
|
Final fire alarm inspection for area of work complete.
please call 1/2hour prior. thanks Phone #: ###-#### Inspection requested via web by Rick Groom
|