FIR19-00919
| INSP-Sprinkler Rough-in | 1/16/2020 | 1/17/2020 | 1/17/2020 2:25:23 PM | P | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.
Plans are on site Phone #: ###-#### Inspection requested via web by Sam Ball
|
BLD19-02053
| FIRE-Conference | 1/17/2020 | 1/17/2020 | 1/17/2020 1:26:49 PM | P | DONE |
|
|
Fire conference complete.
Ronald Phone #: ###-####
|
BLD18-01083
| FIRE-Conference | 1/16/2020 | 1/17/2020 | 1/17/2020 11:56:01 AM | A | DONE |
|
|
Fire conference complete.
Call ahead // Mike Phone #: ###-####
|
FIR19-00655
| INSP-Sprinkler Rough-in/Hydro | 1/16/2020 | 1/17/2020 | 1/17/2020 10:37:54 AM | A | FAIL |
|
|
Hydrostatic test not accepted, plans onsite are not city approved drawings.
Contact is Raul Phone #: ###-#### Inspection requested via web by Chris Green
|
FIR19-00845
| INSP-Sprinkler Rough-in/Hydro | 1/16/2020 | 1/17/2020 | 1/17/2020 10:37:03 AM | A | FAIL |
|
|
Hydrostatic test is not accepted, no rough in inspection has been performed and plans onsite are not city approved drawings. Replace couplings with T's and plugs on dry heads, couplings are not acceptable as shown on manufactures specifications.
Contact is Raul Phone #: ###-#### Inspection requested via web by Chris Green
|
FIR19-00489
| INSP-Sprinkler Rough-in | 1/17/2020 | 1/17/2020 | 1/17/2020 9:45:18 AM | A | FAIL |
|
|
Numerous upright heads have been painted in the classroom closets, sprinkler heads will need to be replaced per 2016 NFPA13, section 6.2.6.2.2, sprinkler heads cannot be cleaned.
|
FIR19-00489
| INSP-Sprinkler Rough-in | 1/16/2020 | 1/17/2020 | 1/17/2020 9:41:05 AM | A | PART |
|
|
Partial rough to cover inspection for overhead fire sprinkler piping complete, notated city approved drawings with red ink areas approved for cover.
Todd Ketterling is the contact for this RTC inspection. We appreciate your help. Thank you. Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00819
| INSP-Sprinkler Rough-in | 1/16/2020 | 1/17/2020 | 1/17/2020 9:36:30 AM | A | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping above suspended ceiling complete, a couple of areas has plywood supporting grid, plywood nees to be treated wood or replaced with non-combustible material, if wood is not treated and remains then upright heads will be required.
Plans on site Phone #: ###-#### Inspection requested via web by Sam Ball
|
BLD19-01427
| FIRE-Conference | 1/16/2020 | 1/17/2020 | 1/17/2020 12:00:00 AM | A | CANC |
|
|
Jon Phone #: ###-#### // canceled per Jon 1-17-20
|