Inspections for the day of: Tuesday, January 21, 2020.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD19-00278 FIRE-Final Inspection1/20/20201/21/20201/21/2020 5:48:46 PMPPART
Partial final inspection for life fire safety inspection is complete. Last remaining items are permanent signage for FACP/Fire Sprinkler Riser room and Hood Designation for manual acvtivation pull stations, temp signage in place at time of inspection. 90 day TCO authorized for life fire safety.

Fire/Life/Safety for TCO Phone #: ###-#### Inspection requested via web by Corey Hockersmith
FIR19-00589 INSP-Final Inspection1/20/20201/21/20201/21/2020 3:36:19 PMPCANC
Fire alarm inspection is scheduled for 22JAN2020, this inspection will need to be rescheduled to coincide with final fire alarm inspection, this request is cancelled.

Please contact Rick Fry for inspection time. Phone #: ###-#### Inspection requested via web by Daniel Buccino
FIR18-00358 INSP-Alarm Testing1/15/20201/21/20201/21/2020 3:35:15 PMAPART
Fire aalrm testing for AES communicator is complete. Submittal shows an indorr antenna being used, an outdoor antenna has been installed, all functions have been tested, submittal package needs to show antenna that is installed. Once reviewed, accepted and fees are paid then permit can be finaled.

Call Jake Adams. District and Alarm Co personnel will be onsite. Phone #: ###-#### Inspection requested via web by Jeff Gooch
FIR20-00024 INSP-Final Inspection1/17/20201/21/20201/21/2020 1:52:34 PMPPASS
Final fire alarm inspection for scope of work complete.

Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
FIR19-00703 INSP-Sprinkler Rough-in1/20/20201/21/20201/21/2020 10:55:13 AMAPASS
Rough to cover inspection for overhead fire sprinkler piping on level 4 complete, 2 heads are less than 4 inches off of wall/corner of wall, a minimum of 4 inches is required. Will verfiy relocate during final inspection. Cover is approved.

Mike Oswald-4th floor please Phone #: ###-#### Inspection requested via web by Brodie Stenquist
FIR19-00944 INSP-Final Inspection1/20/20201/21/20201/21/2020 10:37:41 AMAPASS
Final fire sprinkler inspection for scope of work complete, signature provided on permit sign off card.

Ken will Attend Phone #: ###-#### Inspection requested via web by Connie Danes
FIR19-00655 INSP-Sprinkler Rough-in/Hydro1/20/20201/21/20201/21/2020 10:27:16 AMAPART
Was informed that permenant heat was established to building, temporary heat is what is keeping the building at 40 degrees and above. Hydrostatic test is unofficial, no pressure loss observed. Periodic check in will be done, if building is below 40 degrees then a re-hydro will be required.

Contact is Raul Phone #: ###-#### Inspection requested via web by Chris Green
FIR19-00845 INSP-Sprinkler Rough-in/Hydro1/20/20201/21/20201/21/2020 10:25:33 AMAPART
Was informed that permenant heat was established to builindg, temporary heat is what is keeping the building at 40 degrees and above. Hydrostsic test is unofficial, no pressure loss observed. Periodic check ins will be done, if building is below 40 degrees then a re-hydro will be required.

Contact is Raul Phone #: ###-#### Inspection requested via web by Chris Green
FIR19-00751 INSP-Sprinkler Rough-in1/20/20201/21/20201/21/2020 9:23:49 AMAPART
Rough to cover inspection for overhead fire sprinkler piping above ceiling grid complete, approved for cover.

rick fry Phone #: ###-#### Inspection requested via web by Brodie Stenquist
BLD19-04124 FIRE-Final Inspection1/17/20201/21/20201/21/2020 9:22:53 AMAPASS
Fire sprinkler inspection is complete, fire alarm inspection is complete, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection for area of work complete, signatures provided on permit sign off card.

Albert Phone #: ###-####
FIR19-00634 INSP-Final Inspection1/14/20201/21/20201/21/2020 8:11:54 AMACANC
We would like this inspection at 8:00 am per the tenant''s request.
Please call Nate at ###-#### with inspection time. Phone #: ###-#### >> Inspection requested via web by Lori Brungardt Inspection cancelled from web by: Lori Brungardt