BLD19-00278
| FIRE-Final Inspection | 1/20/2020 | 1/21/2020 | 1/21/2020 5:48:46 PM | P | PART |
|
|
Partial final inspection for life fire safety inspection is complete. Last remaining items are permanent signage for FACP/Fire Sprinkler Riser room and Hood Designation for manual acvtivation pull stations, temp signage in place at time of inspection. 90 day TCO authorized for life fire safety.
Fire/Life/Safety for TCO Phone #: ###-#### Inspection requested via web by Corey Hockersmith
|
FIR19-00589
| INSP-Final Inspection | 1/20/2020 | 1/21/2020 | 1/21/2020 3:36:19 PM | P | CANC |
|
|
Fire alarm inspection is scheduled for 22JAN2020, this inspection will need to be rescheduled to coincide with final fire alarm inspection, this request is cancelled.
Please contact Rick Fry for inspection time. Phone #: ###-#### Inspection requested via web by Daniel Buccino
|
FIR18-00358
| INSP-Alarm Testing | 1/15/2020 | 1/21/2020 | 1/21/2020 3:35:15 PM | A | PART |
|
|
Fire aalrm testing for AES communicator is complete. Submittal shows an indorr antenna being used, an outdoor antenna has been installed, all functions have been tested, submittal package needs to show antenna that is installed. Once reviewed, accepted and fees are paid then permit can be finaled.
Call Jake Adams. District and Alarm Co personnel will be onsite. Phone #: ###-#### Inspection requested via web by Jeff Gooch
|
FIR20-00024
| INSP-Final Inspection | 1/17/2020 | 1/21/2020 | 1/21/2020 1:52:34 PM | P | PASS |
|
|
Final fire alarm inspection for scope of work complete.
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
FIR19-00703
| INSP-Sprinkler Rough-in | 1/20/2020 | 1/21/2020 | 1/21/2020 10:55:13 AM | A | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping on level 4 complete, 2 heads are less than 4 inches off of wall/corner of wall, a minimum of 4 inches is required. Will verfiy relocate during final inspection. Cover is approved.
Mike Oswald-4th floor please Phone #: ###-#### Inspection requested via web by Brodie Stenquist
|
FIR19-00944
| INSP-Final Inspection | 1/20/2020 | 1/21/2020 | 1/21/2020 10:37:41 AM | A | PASS |
|
|
Final fire sprinkler inspection for scope of work complete, signature provided on permit sign off card.
Ken will Attend Phone #: ###-#### Inspection requested via web by Connie Danes
|
FIR19-00655
| INSP-Sprinkler Rough-in/Hydro | 1/20/2020 | 1/21/2020 | 1/21/2020 10:27:16 AM | A | PART |
|
|
Was informed that permenant heat was established to building, temporary heat is what is keeping the building at 40 degrees and above. Hydrostatic test is unofficial, no pressure loss observed. Periodic check in will be done, if building is below 40 degrees then a re-hydro will be required.
Contact is Raul Phone #: ###-#### Inspection requested via web by Chris Green
|
FIR19-00845
| INSP-Sprinkler Rough-in/Hydro | 1/20/2020 | 1/21/2020 | 1/21/2020 10:25:33 AM | A | PART |
|
|
Was informed that permenant heat was established to builindg, temporary heat is what is keeping the building at 40 degrees and above. Hydrostsic test is unofficial, no pressure loss observed. Periodic check ins will be done, if building is below 40 degrees then a re-hydro will be required.
Contact is Raul Phone #: ###-#### Inspection requested via web by Chris Green
|
FIR19-00751
| INSP-Sprinkler Rough-in | 1/20/2020 | 1/21/2020 | 1/21/2020 9:23:49 AM | A | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping above ceiling grid complete, approved for cover.
rick fry Phone #: ###-#### Inspection requested via web by Brodie Stenquist
|
BLD19-04124
| FIRE-Final Inspection | 1/17/2020 | 1/21/2020 | 1/21/2020 9:22:53 AM | A | PASS |
|
|
Fire sprinkler inspection is complete, fire alarm inspection is complete, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection for area of work complete, signatures provided on permit sign off card.
Albert Phone #: ###-####
|
FIR19-00634
| INSP-Final Inspection | 1/14/2020 | 1/21/2020 | 1/21/2020 8:11:54 AM | A | CANC |
|
|
We would like this inspection at 8:00 am per the tenant''s request. Please call Nate at ###-#### with inspection time. Phone #: ###-#### >> Inspection requested via web by Lori Brungardt Inspection cancelled from web by: Lori Brungardt
|