Inspections for the day of: Friday, January 25, 2019.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR18-00209 INSP-Final Inspection1/24/20191/25/20191/25/2019 4:19:31 PMACANC
Inspection will need to be rescheduled due to time constraints.

After nine o’clock please Phone #: ###-#### Inspection requested via web by Sam Ball
FIR18-00790 INSP-Final Inspection1/25/20191/25/20191/25/2019 4:18:57 PMPCANC
Issues with monitoring module for hood, will be addressed with fire alarm vendor.

Call ahead 20 // Richard Phone #: ###-####
FIR18-00305 INSP-Final Inspection1/25/20191/25/20191/25/2019 4:18:13 PMPCANC
Final hood suppression system inspection complete.
FIR19-00018 INSP-Sprinkler Rough-in/Hydro1/25/20191/25/20191/25/2019 4:13:52 PMPDONE
Hydrostatic test for overhead fire sprinkler piping witnessed with anti-freeze, no pressure loss observed.
FIR18-00673 INSP-Sprinkler Rough-in/Hydro1/24/20191/25/20191/25/2019 4:12:27 PMPPART
Rough to cover inspection for east side area B complete, area inspected approved for cover.

Phone #: ###-#### Inspection requested via web by Shane Lesteberg
FIR19-00018 INSP-Sprinkler Rough-in/Hydro1/24/20191/25/20191/25/2019 2:09:02 PMAPART
Rough in inspection for overhead fire sprinkler piping complete, piping located between conditioned spaqces approved for cover, tenting is required before cover in areas where piping is in attic spaces.

Call Alicia before heading out, will be ready early. This is up off Bogus Basin Rd. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR19-00010 INSP-Final Inspection1/24/20191/25/20191/25/2019 1:14:20 PMACANC
Called point of contact but there was no answer, inspection request will need to be rescheduled, this request is cancelled.

Re-inspection of the electrical trip test. Phone #: ###-#### Inspection requested via web by Don Kartchner
FIR18-00510 INSP-Sprinkler Rough-in1/24/20191/25/20191/25/2019 12:44:40 PMAPART
Inspection turned into a conference, cover material that was installed before piping was inspected needs to be removed, un-interuptable heat needs to be established before water is introduced to the fire sprinkler system, once water is on then temperature of all areas effected will need to be 40 degrees or above, if temperature falls below 40 degrees in areas that piping has been made wet then a re-hydro will be required.

Third floor rough in. Phone #: ###-#### Inspection requested via web by Sam Ball
FIR13-00545 INSP-Final Inspection1/24/20191/25/20191/25/2019 11:30:42 AMACANC
Cancelled per conversation with point of contact.

Ray McQueen, inspecting technician Phone #: ###-#### Inspection requested via web by Rose Peterson
FIR18-00956 INSP-Final Inspection1/24/20191/25/20191/25/2019 11:30:19 AMAPART
Fire alarm notification inspection complete, sprinkler monitoring complete, still need to test hood monitoring, in duct detectors and temperature sensors.

Phone #: ###-#### Inspection requested via web by Ken Webster
FIR18-00765 INSP-Sprinkler Rough-in1/24/20191/25/20191/25/2019 11:29:13 AMADONE
Fire pump commissioning complete.

Todd Ketterling is the contact for this inspection. He is needing a pump commissioning inspection. He is hoping for a call before hand to let him know what time appointment will be tomorrow so he can be ready. We thank you for your help. Have a nice day. Phone #: ###-#### Inspection requested via web by Stan Beus
FIR18-00241 INSP-Final Inspection1/24/20191/25/20191/25/2019 11:28:41 AMAPASS
Final underground supply inspection complete.

Richard Phone #: ###-####
FIR18-00464 INSP-Final Inspection1/24/20191/25/20191/25/2019 11:27:51 AMPPASS
Final fire sprinkler inspection complete.

Matt is the contact Phone #: ###-#### Inspection requested via web by jeremiah robison
FIR18-00827 INSP-Sprinkler Rough-in1/24/20191/25/20191/25/2019 7:08:27 AMAPASS
Rough to cover inspection for overhead fire sprinkler piping/yenting complete, approved for cover.

Gerarrdo is the contact. Phone #: ###-#### Inspection requested via web by Stan Beus
FIR19-00028 INSP-Final Inspection1/24/20191/25/20191/25/2019 6:38:19 AMAFAIL
Three to four different strobe patterns in the same area, horn strobes need to sync for final inspection.

As early as possible Phone #: 2085905075 >> Inspection requested via mobile web by Barney
FIR18-00902 INSP-Final Inspection1/24/20191/25/20191/24/2019 3:23:33 PMPCANC
Phone #: ###-#### >> Inspection requested via web by John Lopez Inspection cancelled from web by: John Lopez
FIR18-00673 INSP-Sprinkler Rough-in/Hydro1/23/20191/25/20191/24/2019 1:50:46 PMACANC
Phone #: ###-#### >> Inspection requested via web by Shane Lesteberg Inspection cancelled from web by: Shane Lesteberg