Inspections for the day of: Monday, January 28, 2019.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD18-03208 FIRE-Final Inspection1/28/20191/28/20191/28/2019 4:21:39 PMPFAIL
Point of contact was not on site when inspection could be performed, spoke with assistant manager on the phone an she did not know where the city approved documentation was, inspection will need to rescheduled.

Tim or Terry @ ###-#### Phone #: ###-####
FIR19-00064 INSP-Final Inspection1/28/20191/28/20191/28/2019 3:56:19 PMPPASS
Final fire alarm inspection for area of work complete.

Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
FIR18-00209 INSP-Final Inspection1/28/20191/28/20191/28/2019 3:35:42 PMPFAIL
Add fire sprinkler in coridor next to kitchen on top level as discussed.

Phone #: ###-#### Inspection requested via web by Sam Ball
FIR18-00510 INSP-Sprinkler Rough-in/Hydro1/28/20191/28/20191/28/2019 2:57:52 PMPPART
Hydrostatic test for level 2 overehad fire sprinkler piping witnessed, no pressure loss observed. No rough to cover ispection was perfromed due to time constraints.

Phone #: ###-#### Inspection requested via web by Sam Ball
BLD17-03016 FIRE-Final Inspection1/28/20191/28/20191/28/2019 2:05:56 PMPCANC
Keith Phone #: ###-####
BLD17-03016 FIRE-Final Inspection1/25/20191/28/20191/28/2019 2:05:45 PMAPASS
Fire sprinkler inspection is complete, fire alarm inspection is complete, hood suppression system inspection is complete, fire extinguishers are placed with current inspection tags. Final life fire safety inspection complete.

.

early am please- Keith Phone #: ###-####
BLD17-04133 FIRE-Final Inspection1/28/20191/28/20191/28/2019 1:36:44 PMPFAIL
FIR permits for fire alarm, fire alarm communicator and hood suppression system needs to be completed and finaled before life fire safety inspection can be completed.

Phone #: ###-#### Inspection requested via web by JT Turner
BLD18-00230 FIRE-Final Inspection1/28/20191/28/20191/28/2019 1:35:48 PMPFAIL
FIR permits for fire alarm, fire alarm communicator and hood suppression system needs to be completed and finaled before life fire safety inspection can be completed.

Phone #: ###-#### Inspection requested via web by JT Turner
FIR18-00673 INSP-Sprinkler Rough-in/Hydro1/26/20191/28/20191/28/2019 1:33:32 PMPCANC
Cancelled per conversation with point of contact, inspection request will be rescheduled by contractor.

Phone #: ###-#### Inspection requested via web by Shane Lesteberg
FIR18-00495 INSP-Sprinkler Rough-in/Hydro1/23/20191/28/20191/28/2019 1:31:20 PMAFAIL
Smoke detectors in server room are to close to HVAC registers, need a minimum of 36 inshes from air flow edge to smoke detectors. Verify allowed clearance around nozzles as well as distance from wall.

.

Jeremy Phone #: ###-####
FIR17-00508 INSP-Final Inspection1/25/20191/28/20191/28/2019 9:26:49 AMPCANC
Cancelled per conversation with GC, inspection will be rescheduled for a later date.

TCO for area A Phone #: ###-#### Inspection requested via web by Shane Lesteberg
BLD17-01000 FIRE-Final Inspection1/25/20191/28/20191/28/2019 9:26:33 AMACANC
Cancelled per conversation with GC, inspection will be rescheduled for a later date.

Bruce Phone #: ###-####
FIR17-00474 INSP-Final Inspection1/25/20191/28/20191/28/2019 9:25:36 AMACANC
Cancelled per conversation with GC, inspection will be rescheduled for a later date.

Mark Jensen is the contact. Phone #: ###-#### Inspection requested via web by Stan Beus
FIR18-00305 INSP-Final Inspection1/25/20191/28/20191/28/2019 8:36:05 AMAPASS
Permit finaled.

Richard Phone #: ###-####
FIR18-00902 INSP-Final Inspection1/24/20191/28/20191/28/2019 8:34:06 AMAPASS
Final fire alarm inspection for area of work complete.

Can we try to schedule this at 7AM, so that we can activate the horn strobes before anyone is in the building? Phone #: ###-#### Inspection requested via web by John Lopez
FIR18-00673 INSP-Sprinkler Rough-in/Hydro1/24/20191/28/20191/26/2019 9:17:51 AMACANC
Dry system air test Phone #: ###-#### >> Inspection requested via web by Shane Lesteberg Inspection cancelled from web by: Shane Lesteberg