BLD18-03208
| FIRE-Final Inspection | 1/28/2019 | 1/28/2019 | 1/28/2019 4:21:39 PM | P | FAIL |
|
|
Point of contact was not on site when inspection could be performed, spoke with assistant manager on the phone an she did not know where the city approved documentation was, inspection will need to rescheduled.
Tim or Terry @ ###-#### Phone #: ###-####
|
FIR19-00064
| INSP-Final Inspection | 1/28/2019 | 1/28/2019 | 1/28/2019 3:56:19 PM | P | PASS |
|
|
Final fire alarm inspection for area of work complete.
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
FIR18-00209
| INSP-Final Inspection | 1/28/2019 | 1/28/2019 | 1/28/2019 3:35:42 PM | P | FAIL |
|
|
Add fire sprinkler in coridor next to kitchen on top level as discussed.
Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR18-00510
| INSP-Sprinkler Rough-in/Hydro | 1/28/2019 | 1/28/2019 | 1/28/2019 2:57:52 PM | P | PART |
|
|
Hydrostatic test for level 2 overehad fire sprinkler piping witnessed, no pressure loss observed. No rough to cover ispection was perfromed due to time constraints.
Phone #: ###-#### Inspection requested via web by Sam Ball
|
BLD17-03016
| FIRE-Final Inspection | 1/28/2019 | 1/28/2019 | 1/28/2019 2:05:56 PM | P | CANC |
|
|
Keith Phone #: ###-####
|
BLD17-03016
| FIRE-Final Inspection | 1/25/2019 | 1/28/2019 | 1/28/2019 2:05:45 PM | A | PASS |
|
|
Fire sprinkler inspection is complete, fire alarm inspection is complete, hood suppression system inspection is complete, fire extinguishers are placed with current inspection tags. Final life fire safety inspection complete.
.
early am please- Keith Phone #: ###-####
|
BLD17-04133
| FIRE-Final Inspection | 1/28/2019 | 1/28/2019 | 1/28/2019 1:36:44 PM | P | FAIL |
|
|
FIR permits for fire alarm, fire alarm communicator and hood suppression system needs to be completed and finaled before life fire safety inspection can be completed.
Phone #: ###-#### Inspection requested via web by JT Turner
|
BLD18-00230
| FIRE-Final Inspection | 1/28/2019 | 1/28/2019 | 1/28/2019 1:35:48 PM | P | FAIL |
|
|
FIR permits for fire alarm, fire alarm communicator and hood suppression system needs to be completed and finaled before life fire safety inspection can be completed.
Phone #: ###-#### Inspection requested via web by JT Turner
|
FIR18-00673
| INSP-Sprinkler Rough-in/Hydro | 1/26/2019 | 1/28/2019 | 1/28/2019 1:33:32 PM | P | CANC |
|
|
Cancelled per conversation with point of contact, inspection request will be rescheduled by contractor.
Phone #: ###-#### Inspection requested via web by Shane Lesteberg
|
FIR18-00495
| INSP-Sprinkler Rough-in/Hydro | 1/23/2019 | 1/28/2019 | 1/28/2019 1:31:20 PM | A | FAIL |
|
|
Smoke detectors in server room are to close to HVAC registers, need a minimum of 36 inshes from air flow edge to smoke detectors. Verify allowed clearance around nozzles as well as distance from wall.
.
Jeremy Phone #: ###-####
|
FIR17-00508
| INSP-Final Inspection | 1/25/2019 | 1/28/2019 | 1/28/2019 9:26:49 AM | P | CANC |
|
|
Cancelled per conversation with GC, inspection will be rescheduled for a later date.
TCO for area A Phone #: ###-#### Inspection requested via web by Shane Lesteberg
|
BLD17-01000
| FIRE-Final Inspection | 1/25/2019 | 1/28/2019 | 1/28/2019 9:26:33 AM | A | CANC |
|
|
Cancelled per conversation with GC, inspection will be rescheduled for a later date.
Bruce Phone #: ###-####
|
FIR17-00474
| INSP-Final Inspection | 1/25/2019 | 1/28/2019 | 1/28/2019 9:25:36 AM | A | CANC |
|
|
Cancelled per conversation with GC, inspection will be rescheduled for a later date.
Mark Jensen is the contact. Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00305
| INSP-Final Inspection | 1/25/2019 | 1/28/2019 | 1/28/2019 8:36:05 AM | A | PASS |
|
|
Permit finaled.
Richard Phone #: ###-####
|
FIR18-00902
| INSP-Final Inspection | 1/24/2019 | 1/28/2019 | 1/28/2019 8:34:06 AM | A | PASS |
|
|
Final fire alarm inspection for area of work complete.
Can we try to schedule this at 7AM, so that we can activate the horn strobes before anyone is in the building? Phone #: ###-#### Inspection requested via web by John Lopez
|
FIR18-00673
| INSP-Sprinkler Rough-in/Hydro | 1/24/2019 | 1/28/2019 | 1/26/2019 9:17:51 AM | A | CANC |
|
|
Dry system air test Phone #: ###-#### >> Inspection requested via web by Shane Lesteberg Inspection cancelled from web by: Shane Lesteberg
|