Inspections for the day of: Wednesday, January 30, 2019.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR18-00956 INSP-Final Inspection1/30/20191/30/20191/30/2019 4:22:12 PMPPART
Final inspection for temperature sensors in dog house/over builds complete.
BLD17-04133 FIRE-Final Inspection1/30/20191/30/20191/30/2019 3:56:38 PMAPART
TCO for fire life safety approved per conversation with Ron Johnson for 30 days for vendor/employee training only. Once fire alarm permit is finaled then life fire safety can be signed off as finaled.

Schedule to come at the same time as the Fire Alarm inspection. Thanks Phone #: ###-#### Inspection requested via web by JT Turner
BLD18-00230 FIRE-Final Inspection1/30/20191/30/20191/30/2019 3:56:19 PMAPART
TCO for fire life safety approved per conversation with Ron Johnson for 30 days for vendor/employee training only. Once fire alarm permit is finaled then life fire safety can be signed off as finaled.

Schedule to come at the same time as the Fire Alarm inspection. Thanks Phone #: ###-#### Inspection requested via web by JT Turner
FIR18-00956 INSP-Final Inspection1/29/20191/30/20191/30/2019 3:50:27 PMPPART
Fire alarm inspection for initiating devices and notification complete, a follow up inspection will be required to verify possible spacing issues with smoke detector placement, as of these notes a 30 day TCO is authorized by Ron Johnson for occupancy. If smoke detectors space correctly on the install then the fire alarm permit can be finaled but as mentioned, a follow up inspection will be required.

Phone #: ###-#### Inspection requested via web by Ken Webster
BLD18-03091 FIRE-Final Inspection1/29/20191/30/20191/30/2019 12:54:39 PMAFAIL
Fire extinguishers need to be inspected and tagged with a current inspection tag, last inspection on extinguisher tags was 2015. Slide bolt on rear door of warehouse needs to be removed. Install addressing on building with a minimum of 4 inches tall, 1/2 inch wide numbering as discussed to be code compliant.

Mark Phone #: ###-####
FIR18-00673 INSP-Sprinkler Rough-in/Hydro1/26/20191/30/20191/30/2019 10:20:34 AMADONE
24 hour air test on the 3 dry systems complete.

Phone #: ###-#### Inspection requested via web by Shane Lesteberg
BLD18-03949 FIRE-Final Inspection1/30/20191/30/20191/30/2019 9:53:12 AMAFAIL
No point of contact information provided. Need emergency lighting in restrooms to be code compliant. Install code compliant door hardware on level 4 restroom doors. Verify that door hardware on stall doors is code compliant.
FIR17-00508 INSP-Final Inspection1/29/20191/30/20191/30/2019 9:30:57 AMAFAIL
Contractor not on site at time of inspection, could not wait for contractor to show up, inspection will need to rescheduled.

Re-inspect for Area A TCO - remote mic issues resolved. Phone #: ###-#### Inspection requested via web by Shane Lesteberg
BLD18-04014 FIRE-Final Inspection1/29/20191/30/20191/30/2019 9:19:00 AMAFAIL
Fire alarms did not pass inspection. Room has been added that is not on the site drawings, site drawings are not stamped, need city approved drawings for life fire safety inpspection.

Russ Phone #: ###-####
FIR18-00955 INSP-Final Inspection1/29/20191/30/20191/30/2019 9:18:02 AMAFAIL
Smoke detector in tenant space is to close to HVAC register, need to be 36 inches or more away to be code compliant. Room has been added, appears to be a small conference room per GC, need verification of room due to possible addition of speaker strobe to be code compliant.

Hi, we are ready for you. Give me a call to coordinate schedules. -Neal Timmerman ###-#### Phone #: ###-#### Inspection requested via web by Neal Timmerman
FIR18-00510 INSP-Sprinkler Rough-in/Hydro1/29/20191/30/20191/30/2019 8:50:33 AMACANC
Hydro static test for third floor. Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball
FIR19-00018 INSP-Sprinkler Rough-in1/29/20191/30/20191/30/2019 8:34:43 AMAPASS
Overhead fire sprinkler piping/tenting inspection complete, all tenting installed at time of inspection, cover is approved.

Tenting inspection, confirmed complete and ready for inspection. Please let Alicia know if there are any issues. Thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
BLD18-00596 FIRE-Final Inspection1/29/20191/30/20191/30/2019 12:00:00 AMPCANC
Michael Phone #: ###-####-1--30-19 Mike called and cancelled
BLD18-01401 FIRE-Final Inspection1/29/20191/30/20191/30/2019 12:00:00 AMPCANC
Michael Phone #: ###-####-1-30-19 Mike called and cancelled
FIR17-00474 INSP-Final Inspection1/28/20191/30/20191/28/2019 11:22:48 AMACANC
The contact is Todd Ketterling. Thank you for your help! Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus