Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD18-03237 FIRE-Final Inspection1/31/20191/31/20191/31/2019 7:42:29 PMPPART
TCO authorized for 14 days for life fire safety inspection per conversation with Ron Johnson contingent on the permit for the access control door release permit (FIR19-00076) is inspected and finaled. Life fire safety can be finaled when mentioned permit is complete and finalized as well.
FIR18-00673 INSP-Sprinkler Rough-in/Hydro1/29/20191/31/20191/31/2019 5:02:13 PMPDONE
Hydrostatic test for all overehad fire sprinkler piping witnessed, no pressure loss observed.

Phone #: ###-#### Inspection requested via web by Shane Lesteberg
BLD18-01401 FIRE-Final Inspection1/30/20191/31/20191/31/2019 3:21:34 PMPPASS
Final life fire safety inspection for office TI space complete.

Michael Phone #: ###-####
BLD18-00596 FIRE-Final Inspection1/30/20191/31/20191/31/2019 3:20:55 PMPPASS
Final life fire safety inspection for core and shell complete.

Michael Phone #: ###-####
FIR18-00884 INSP-Final Inspection1/30/20191/31/20191/31/2019 3:20:20 PMPPASS
Final fire sprinkler inspection for area of work complete.

Todd Ketterling is the contact. Thank you for your help! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR18-00715 INSP-Final Inspection1/31/20191/31/20191/31/2019 3:19:46 PMPPASS
Final undergorund supply inspection complete.

301 open on shell bld
BLD18-03091 FIRE-Final Inspection1/31/20191/31/20191/31/2019 1:33:51 PMPPASS
Previously noted items have been corrected, final life fire safety inspection complete. Noted that main entry has thumbturn deadbolt on door.

Mark Phone #: ###-####
FIR18-00954 INSP-Sprinkler Rough-in1/30/20191/31/20191/31/2019 1:32:45 PMAPASS
Rough to cover ispection for overhead fire sprinkler piping complete, approved for cover.

Will Phone #: ###-####
FIR19-00069 INSP-Sprinkler Rough-in1/30/20191/31/20191/31/2019 1:31:53 PMADONE
Rough in inspection complete

Will Phone #: ###-####
FIR17-00508 INSP-Final Inspection1/31/20191/31/20191/31/2019 10:33:23 AMPCANC
This request is cancelled, reference notes entered on 31JAN2019.

Phone #: ###-#### Inspection requested via web by Gary Gambino
FIR18-00419 INSP-Final Inspection1/31/20191/31/20191/31/2019 10:32:32 AMPPASS
Final fire alarm inspection for scope of work has been completed.

Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
FIR18-00615 INSP-Final Inspection1/31/20191/31/20191/31/2019 10:31:24 AMPPASS
Final fire alarm inspeciton for area of work has been completed.

Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
FIR17-00508 INSP-Final Inspection1/30/20191/31/20191/31/2019 10:30:29 AMAFAIL
No inspection was performed on the fire alarm system, Boise school district has a permit still in issued status for an AES communicator install (FIR18-00167). The communicator attached to the mentioned permit has never been inspected. Due to the type of install, the communicator will not report out a general fire alarm if there is a trouble on the main fire panel. Boise High School has had troubles on the fire alarm panel and during the trouble event the school is not monitored for general fire alarm events. No further inspection will be completed on the fire alarm addition to the gymnasium until the AES communicator permit is inspected, passed and operational. Per the conversation with Ron Johnson with Boise Fire, this permit will not be finaled for any type of occupancy until the communicator is inspected and finaled.

Area A re-inspect Phone #: ###-#### Inspection requested via web by Shane Lesteberg
FIR18-00594 INSP-Final Inspection1/30/20191/31/20191/31/2019 9:08:47 AMAPART
Fire alarm inspection for area of work complete, waiting room has a door to an enclosed patio that does not have any notification, need to have a weather proof audio visual device added before peremit can be finaled.

Phone #: ###-#### Inspection requested via web by Jim Shilton
FIR13-00545 INSP-Final Inspection1/25/20191/31/20191/31/2019 8:29:14 AMAPASS
Final fire alarm inspection for area of work complete.

Ray McQueen, inspecting technician, ###-####, 7:00am start time please Phone #: ###-#### Inspection requested via web by Rose Peterson
BLD18-03237 FIRE-Final Inspection1/31/20191/31/20191/31/2019 12:00:00 AMPCANC
Garett Phone #: ###-####-as -per Garrett cancel insp