BLD18-02699
| FIRE-Final Inspection | 1/4/2019 | 1/4/2019 | 1/4/2019 3:19:58 PM | P | FAIL |
|
|
Fire sprinkler permit is still in issued status, fire sprinkler permit needs to be completed and in finaled status before life fire safety inspection can be performed as stated in past notes.
Please call Todd ahead 15 min Phone #: ###-#### Inspection requested via web by Todd Weltner
|
BLD18-03786
| FIRE-Final Inspection | 1/4/2019 | 1/4/2019 | 1/4/2019 3:19:41 PM | P | FAIL |
|
|
Fire sprinkler permit is still in issued status, fire sprinkler permit needs to be completed and in finaled status before life fire safety inspection can be performed as stated in past notes.
Please call Todd ahead 15 min Phone #: ###-#### Inspection requested via web by Todd Weltner
|
BLD18-03870
| FIRE-Final Inspection | 1/4/2019 | 1/4/2019 | 1/4/2019 3:16:49 PM | P | PART |
|
|
Final life fire safety inspection for units 101 and 402 complete, level 3 unit to be completed at a later date. Will need to test fire alarms in effected units before permit can be finaled.
John- Phone #: ###-####
|
FIR18-00731
| INSP-Final Inspection | 1/4/2019 | 1/4/2019 | 1/4/2019 3:15:28 PM | P | CANC |
|
|
Irrigation timers are not hooked up to the zone solenoids, inspection cancelled per conversation with point of contact, will be rescheduled for a later date.
Call Alicia before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR18-00491
| INSP-Final Inspection | 1/4/2019 | 1/4/2019 | 1/4/2019 3:15:11 PM | P | CANC |
|
|
Irrigation timers are not hooked up to the zone solenoids, inspection cancelled per conversation with point of contact, will be rescheduled for a later date.
Call Alicia before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR18-00715
| INSP-Supply line flush | 1/3/2019 | 1/4/2019 | 1/4/2019 1:31:50 PM | P | DONE |
|
|
Underground supply flush complete.
Todd Ketterling is the contact.. Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00846
| INSP-Sprinkler Rough-in | 1/4/2019 | 1/4/2019 | 1/4/2019 1:31:20 PM | P | PASS |
|
|
Rough to cover inspection for undergorund supply complete, approved for cover.
cover // jeremy Phone #: ###-####
|
FIR19-00002
| INSP-Sprinkler Rough-in | 1/4/2019 | 1/4/2019 | 1/4/2019 1:18:00 PM | P | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.
Kerry Phone #: ###-####
|
BLD18-04333
| FIRE-Final Inspection | 1/3/2019 | 1/4/2019 | 1/4/2019 10:40:00 AM | A | PASS |
|
|
Previously noted items have been corrected, final life fire safety inspection complete.
Rebecca Phone #: ###-####
|
FIR18-00618
| INSP-Final Inspection | 1/4/2019 | 1/4/2019 | 1/4/2019 10:31:04 AM | P | CANC |
|
|
Call Alicia before heading out, thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
|
BLD18-04340
| FIRE-Final Inspection | 1/3/2019 | 1/4/2019 | 1/4/2019 10:27:50 AM | A | PASS |
|
|
Final life fire safety inspection for area of work complete.
Larren Phone #: ###-####
|
BLD18-02699
| FIRE-Final Inspection | 1/3/2019 | 1/4/2019 | 1/4/2019 10:05:46 AM | A | FAIL |
|
|
Fire sprinkler inspection failed. All foil on fire sprinkler heads needs to be removed. Fire extinguisher is mount to high and is not code compliant, extinguisher needs to be lowered and tagged with a current inspection tag.
Call 15 minutes ahead // Todd Phone #: ###-####
|
BLD18-03786
| FIRE-Final Inspection | 1/3/2019 | 1/4/2019 | 1/4/2019 10:05:28 AM | A | FAIL |
|
|
Fire sprinkler inspection failed. All foil on fire sprinkler heads needs to be removed. Fire extinguisher is mount to high and is not code compliant, extinguisher needs to be lowered and tagged with a current inspection tag.
Call 15 minutes ahead // Todd Phone #: ###-####
|
FIR18-00869
| INSP-Final Inspection | 1/3/2019 | 1/4/2019 | 1/4/2019 10:03:08 AM | A | FAIL |
|
|
Provide fire sprinkler under duct where head is overspaced. Provide fire sprinkler next to duct work where head is blocked as discussed. All foil needs to be removed from heads before life fire safety inspection.
Contact Hunter Anderson ###-#### 30 Min prior to Fire Final Start please
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
FIR18-00676
| INSP-Final Inspection | 1/3/2019 | 1/4/2019 | 1/4/2019 9:19:12 AM | A | PASS |
|
|
Final fire alarm inspeciton for area of work complete.
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah Froese
|
FIR18-00914
| INSP-Final Inspection | 1/3/2019 | 1/4/2019 | 1/4/2019 9:18:40 AM | A | PASS |
|
|
Final fire sprinkler ninspection for area of work complete.
Ron Phone #: ###-####
|