BLD18-02911
| FIRE-Final Inspection | 1/7/2019 | 1/7/2019 | 1/7/2019 3:46:19 PM | P | PASS |
|
|
No fire sprinklers, no fire alarms, fire extinguishers are placed with current inspection tags, other address on building that is not 6434 to be removed before building final. Final life fire safety inspection for area of work complete.
Eric Phone #: ###-####
|
FIR17-00708
| INSP-Sprinkler Rough-in | 1/7/2019 | 1/7/2019 | 1/7/2019 3:15:52 PM | P | FAIL |
|
|
Sprinklers need adjusted so the escutcheons fit tight against ceiling. Fire sprinkler heads need to be added in little entry to room behind kitchen with sliding glass doors as well as corridor next to glass doors.
Phone #: ###-#### Inspection requested via web by Todd Walter
|
NAF18-00117
| INSP-Final | 1/7/2019 | 1/7/2019 | 1/7/2019 3:13:27 PM | P | DONE |
|
|
Final life fire safety inspection for area of work complete.
Call prior to going Phone #: 2005147600 >> Inspection requested via mobile web by AJ
|
FIR18-00618
| INSP-Final Inspection | 1/7/2019 | 1/7/2019 | 1/7/2019 1:45:03 PM | P | PASS |
|
|
Final fire sprinkler inspection complete.
Please call Anthony before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR18-00715
| INSP-Sprinkler Rough-in/Hydro | 1/4/2019 | 1/7/2019 | 1/7/2019 11:46:59 AM | P | DONE |
|
|
Undergorund supply hydrostatic test witnessed, no pressure loss observed.
Todd Ketterling is the contact. Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00869
| INSP-Final Inspection | 1/4/2019 | 1/7/2019 | 1/7/2019 11:31:09 AM | A | PASS |
|
|
Final fire sprinkler inspection for area of work complete.
Contact Hunter Anderson ###-#### 30 min prior to Fire Final Insp please
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
FIR17-00474
| INSP-Sprinkler Rough-in/Hydro | 1/4/2019 | 1/7/2019 | 1/7/2019 10:43:14 AM | A | DONE |
|
|
Undergorund supply hydrostatic test witnessed, no pressure loss observed.
Jeff Chaney is the contact. Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD18-04573
| FIRE-Final Inspection | 1/4/2019 | 1/7/2019 | 1/7/2019 10:41:27 AM | A | PASS |
|
|
No fire sprinklers, no fire alarms, fire exitnguisher is in place and will be tagged with a current inspection tag. Final life fire safety inspection for area of work complete.
Kathryn Phone #: ###-####
|
FIR17-00474
| INSP-Supply line flush | 1/4/2019 | 1/7/2019 | 1/7/2019 10:10:29 AM | P | CANC |
|
|
Inspection rescheduled per conversation with point of contact, this request is cancelled.
Jeff Chaney is the contact. Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00826
| INSP-Sprinkler Rough-in | 1/4/2019 | 1/7/2019 | 1/7/2019 10:08:27 AM | A | PART |
|
|
Tentin in Unit B-HC level 3 has been corrected, Unit B-HC level 3 approved for cover, remaining level 3 to be inspected at a later date.
3rd floor tinting. Gerarrdo is the contact. Thank you. Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD18-03713
| FIRE-Final Inspection | 1/4/2019 | 1/7/2019 | 1/7/2019 10:05:35 AM | A | PASS |
|
|
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection for area of work complete.
Tom Phone #: ###-####
|
FIR18-00862
| INSP-Sprinkler Rough-in | 1/4/2019 | 1/7/2019 | 1/7/2019 9:49:30 AM | A | PART |
|
|
Rough to cover inspection for level 1 wet system sprinkler piping complete, level 1 wet system approved for cover.
Contact Noemi Carrero - ###-#### 30 Min prior to RTC Insp for 1st floor wet system please
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
FIR18-00887
| INSP-Sprinkler Rough-in | 1/3/2019 | 1/7/2019 | 1/7/2019 9:17:39 AM | A | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.
Plans are on site Phone #: ###-#### Inspection requested via web by Sam Ball
|
BLD19-00005
| FIRE-Final Inspection | 1/4/2019 | 1/7/2019 | 1/7/2019 8:53:57 AM | A | CANC |
|
|
Inspection request will need to be rescheduled, could not gain access at time that inspection could be performed, point of contact is going to reschedule inspection request, this request is cancelled.
Call 20 mins for access- Richard Phone #: ###-####
|
BLD18-03083
| FIRE-Final Inspection | 1/4/2019 | 1/7/2019 | 1/7/2019 8:47:58 AM | A | FAIL |
|
|
Could not find city approved drawings, emergency illumination for exit discharge needs to be installed on main entry on the north side as well as desiganted exit on the south side. Fire extinguisher needs to be inspected and tagged as well as lowered to below 48 inches to be code compliant.
Phone #: ###-#### Inspection requested via web by Will Thomason
|
BLD18-01191
| FIRE-Final Inspection | 1/4/2019 | 1/7/2019 | 1/7/2019 8:30:53 AM | A | FAIL |
|
|
Fire truck access on southeast side of school is less than 20 feet wide, entrance needs to be 20 feet or larger to be code compliant. New fire hydrant on southeast side is still bagged, need bag removed and hydrant needs ro be put into service.
Requesting a Fire Life Safety re inspection and Fire Final. Thank you Phone #: ###-#### Inspection requested via web by Markus Schlegel
|
FIR18-00777
| INSP-Final Inspection | 1/4/2019 | 1/7/2019 | 1/4/2019 2:00:27 PM | P | CANC |
|
|
Please call John Lopez Phone #: ###-#### >> Inspection requested via web by Jessia Maxwell Inspection cancelled from web by: Jessia Maxwell
|
FIR18-00718
| INSP-Final Inspection | 1/4/2019 | 1/7/2019 | 1/4/2019 2:00:05 PM | P | CANC |
|
|
please call chris ford Phone #: ###-#### >> Inspection requested via web by Jessia Maxwell Inspection cancelled from web by: Jessia Maxwell
|