Inspections for the day of: Tuesday, January 7, 2020.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00390 INSP-Sprinkler Rough-in/Hydro1/7/20201/7/20201/7/2020 3:47:05 PMPDONE
Hydrostatic test for underground supply witnessed, no pressure loss observed.

UG Hydro. Troy Phone #: ###-#### Inspection requested via web by Nathan Stenquist
FIR19-00743 INSP-Sprinkler Rough-in1/3/20201/7/20201/7/2020 3:46:20 PMPPART
Rough to cover ispection for hardlids and attic piping, wing A complete, attic piping approved for cover. Heads on east side of draft stop on Wing A are overspaced, will verify head coverage correction during next inspection. Area inspected on wing A approved for cover.

Contact Tanner Loomis - ###-#### 30 min prior to RTC insp start please this will be for Side A.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
FIR19-00845 INSP-Sprinkler Rough-in1/6/20201/7/20201/7/2020 3:44:15 PMPPASS
Rough to cover inspection for underground supply complete, approved for cover.

This is for Underground Rough In trying to aim for 3:00 ish. Contact is Raul Phone #: ###-#### Inspection requested via web by Chris Green
FIR19-00264 INSP-Final Inspection1/6/20201/7/20201/7/2020 10:19:45 AMPPASS
Knox box is mounted next to main entry, south side, final fire alarm inspection for scope of work complete.

Phone #: ###-#### Inspection requested via web by Robert Gobler
BLD19-04226 FIRE-Final Inspection1/7/20201/7/20201/7/2020 10:12:45 AMPPASS
Previously noted items have been corrected. Fire sprinkler inspection complete, no fire alarm modifications, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection for area of work complete, signatures provided on permit sign off card.

Have (2)trim rings on FS that where missing and Fire Extinguisher placed in the space. Phone #: ###-#### Inspection requested via web by Michael McHargue
FIR19-00703 INSP-Sprinkler Rough-in1/7/20201/7/20201/7/2020 9:45:47 AMAPART
Rough to cover inspection for overhead fire sprinkler piping east of column line 5 complete, area inspected is notated on city approved drawings with red ink, approved for cover east of column line 5.

MIKE OSWALD Phone #: ###-#### Inspection requested via web by Brodie Stenquist
BLD19-04414 FIRE-Final Inspection1/6/20201/7/20201/7/2020 9:03:39 AMPFAIL
Provide code compliant door hardware on main lobby door to TI, thumb turn deadbolts are in place, double keyed deadbolts were in place at time of inspection. Provide signage at main lobby door reading "Door to remain unlocked while space is occupied".

Phone #: 2088694278 >> Inspection requested via mobile web by Ian
FIR19-00638 INSP-Final Inspection1/6/20201/7/20201/7/2020 7:25:53 AMACANC
Contact is Dirk. Phone #: ###-#### >> Inspection requested via web by Morgan Ahten Inspection cancelled from web by: Morgan Ahten