FIR19-00390
| INSP-Sprinkler Rough-in/Hydro | 1/7/2020 | 1/7/2020 | 1/7/2020 3:47:05 PM | P | DONE |
|
|
Hydrostatic test for underground supply witnessed, no pressure loss observed.
UG Hydro. Troy Phone #: ###-#### Inspection requested via web by Nathan Stenquist
|
FIR19-00743
| INSP-Sprinkler Rough-in | 1/3/2020 | 1/7/2020 | 1/7/2020 3:46:20 PM | P | PART |
|
|
Rough to cover ispection for hardlids and attic piping, wing A complete, attic piping approved for cover. Heads on east side of draft stop on Wing A are overspaced, will verify head coverage correction during next inspection. Area inspected on wing A approved for cover.
Contact Tanner Loomis - ###-#### 30 min prior to RTC insp start please this will be for Side A.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
FIR19-00845
| INSP-Sprinkler Rough-in | 1/6/2020 | 1/7/2020 | 1/7/2020 3:44:15 PM | P | PASS |
|
|
Rough to cover inspection for underground supply complete, approved for cover.
This is for Underground Rough In trying to aim for 3:00 ish. Contact is Raul Phone #: ###-#### Inspection requested via web by Chris Green
|
FIR19-00264
| INSP-Final Inspection | 1/6/2020 | 1/7/2020 | 1/7/2020 10:19:45 AM | P | PASS |
|
|
Knox box is mounted next to main entry, south side, final fire alarm inspection for scope of work complete.
Phone #: ###-#### Inspection requested via web by Robert Gobler
|
BLD19-04226
| FIRE-Final Inspection | 1/7/2020 | 1/7/2020 | 1/7/2020 10:12:45 AM | P | PASS |
|
|
Previously noted items have been corrected. Fire sprinkler inspection complete, no fire alarm modifications, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection for area of work complete, signatures provided on permit sign off card.
Have (2)trim rings on FS that where missing and Fire Extinguisher placed in the space. Phone #: ###-#### Inspection requested via web by Michael McHargue
|
FIR19-00703
| INSP-Sprinkler Rough-in | 1/7/2020 | 1/7/2020 | 1/7/2020 9:45:47 AM | A | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping east of column line 5 complete, area inspected is notated on city approved drawings with red ink, approved for cover east of column line 5.
MIKE OSWALD Phone #: ###-#### Inspection requested via web by Brodie Stenquist
|
BLD19-04414
| FIRE-Final Inspection | 1/6/2020 | 1/7/2020 | 1/7/2020 9:03:39 AM | P | FAIL |
|
|
Provide code compliant door hardware on main lobby door to TI, thumb turn deadbolts are in place, double keyed deadbolts were in place at time of inspection. Provide signage at main lobby door reading "Door to remain unlocked while space is occupied".
Phone #: 2088694278 >> Inspection requested via mobile web by Ian
|
FIR19-00638
| INSP-Final Inspection | 1/6/2020 | 1/7/2020 | 1/7/2020 7:25:53 AM | A | CANC |
|
|
Contact is Dirk. Phone #: ###-#### >> Inspection requested via web by Morgan Ahten Inspection cancelled from web by: Morgan Ahten
|