BLD17-01549
| FIRE-Final Inspection | 1/7/2020 | 1/8/2020 | 1/8/2020 4:05:57 PM | A | FAIL |
|
|
Per project description, no occupancy under this permit, items/vehicles are parked/stored inside, a seperate permit for occupancy needs to be issued or items need to be removed from space as discussed.
Phone #: ###-#### Inspection requested via web by Ron Goff
|
FIR19-00750
| INSP-Final Inspection | 1/6/2020 | 1/8/2020 | 1/8/2020 4:04:24 PM | P | PASS |
|
|
Final fire sprinkler inspection for area of work complete. Signature provide on the BLD permit sign off card.
Rick Phone #: ###-####
|
FIR19-00762
| INSP-Final Inspection | 1/6/2020 | 1/8/2020 | 1/8/2020 4:04:08 PM | P | PASS |
|
|
Final fire alarm inspection for scope of work complete, as-builts will be sent to Lee Meridith showing a wall that was removed and an A/V device that did not need to be relocated.
Signature provided on the BLD permit sign off card.Technician, Kc Strykowski Phone #: ###-#### Inspection requested via web by John Siewert
|
BLD19-04732
| FIRE-Final Inspection | 1/8/2020 | 1/8/2020 | 1/8/2020 2:16:01 PM | P | PASS |
|
|
No fire sprinklers, no fire alarms, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection for area of work complete, signature provided on permit sign off card.
Please give me a 30 minute or so phone call and I will meet you there. Thanks, Elliott ###-#### Inspection requested via web by Elliott Sheffield Jr
|
BLD19-04414
| FIRE-Final Inspection | 1/7/2020 | 1/8/2020 | 1/8/2020 2:10:10 PM | P | PASS |
|
|
Previously noted items have been corrected, fire sprinkler inspection is complete, fire aalrm inspection is complete, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for area of work complete.
Phone #: 2088694278 >> Inspection requested via mobile web by Ian
|
FIR19-00928
| INSP-Final Inspection | 1/3/2020 | 1/8/2020 | 1/8/2020 1:53:47 PM | P | CANC |
|
|
Fire alarm panel had previous issues before work was started, point of contact cancelled inspection request per phone conversation prior to showing up. This inspection request is cancelled and will be rescheduled for a later date after issues are resolved. Point of contact will pull a seperate permit if fire panel motherboard needs to be replaced.
elevator inspector will be there at 1pm // Nick Phone #: ###-####
|
FIR19-00779
| INSP-Sprinkler Rough-in | 1/7/2020 | 1/8/2020 | 1/8/2020 1:51:34 PM | P | PASS |
|
|
Previously noted items have been corrected, rough to cover inspection for overhead fire sprinkler piping complete, all tenting in place at time of inspection. Cover is approved, sticker provided for cover. Piping before backflow, per plumbing code and SUEZ requirements piping must be suitable for potable water, black iron pipe is not suitable for potable water, black iron pipe before the backflow will need to be replaced, will verify piping change during next inspection.
As built approved. Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR18-00892
| INSP-Sprinkler Rough-in/Hydro | 1/7/2020 | 1/8/2020 | 1/8/2020 1:48:31 PM | A | DONE |
|
|
Hydrostatic test witnessed for overhead fire sprinkler piping, no pressure loss observed.
overhead hydro 1st and 2nd floor Phone #: ###-#### Inspection requested via web by Connie Danes
|
FIR19-00863
| INSP-Final Inspection | 1/8/2020 | 1/8/2020 | 1/8/2020 11:48:15 AM | P | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Don Kartchner Inspection cancelled from web by: Don Kartchner
|
FIR19-00774
| INSP-Sprinkler Rough-in | 1/8/2020 | 1/8/2020 | 1/8/2020 11:12:33 AM | P | FAIL |
|
|
Provide protective coding on all thread rod being used on the restraint at the IBR or remove all thread rod, IBR has thrust block installed. Cover is not approved.
Kyle Phone #: ###-####
|
FIR19-00773
| INSP-Sprinkler Rough-in | 1/8/2020 | 1/8/2020 | 1/8/2020 11:08:06 AM | P | PASS |
|
|
Rough to cover inspection for undergorund supply complete, approved for cover.
Kyle Phone #: ###-####
|
FIR19-00776
| INSP-Sprinkler Rough-in | 1/8/2020 | 1/8/2020 | 1/8/2020 11:00:26 AM | P | PART |
|
|
Partial cover inspection for underground supply complete. 45 degree fittings were added around another buried pipe, need an approved protective coating to be added to the rebar used for the deadman thrust blocks. Cover is approved west of the 45 degree fittings, a follow up inspection will be required for coating of rebar before cover can be approved.
which required a dead man thrust Kyle Phone #: ###-####
|
BLD19-01247
| FIRE-Final Inspection | 1/7/2020 | 1/8/2020 | 1/8/2020 10:22:29 AM | A | PART |
|
|
Previously noted iems have been corrected with exception to door hardware on exterior door and fire alarm corrections, A/V devices were changed but a different model was used, a fire alarm permit is required for fire alarm modifcations. Per conversation with Troy Cobbley, a 90 day TCO for life fire safety has been authorized by Ron Johnson. Signatures provided on permit sign off card for associated trades.
with Boise fireEric Phone #: ###-####
|
FIR19-00799
| INSP-Sprinkler Rough-in | 1/8/2020 | 1/8/2020 | 1/8/2020 10:17:17 AM | P | CANC |
|
|
Call James before heading out, tenting re-inspection Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
|
BLD17-01549
| FIRE-Sprinkler Rough-in | 1/7/2020 | 1/8/2020 | 1/8/2020 9:33:47 AM | A | CANC |
|
|
Wrong inspection type requested, this request is cancelled.
Phone #: ###-#### Inspection requested via web by Ron Goff
|
BLD17-01549
| FIRE-Alarm Testing | 1/7/2020 | 1/8/2020 | 1/8/2020 9:33:10 AM | A | CANC |
|
|
Wrong inspection type requested, this request is cancelled.
Phone #: ###-#### Inspection requested via web by Ron Goff
|
BLD19-00101
| FIRE-Final Inspection | 1/7/2020 | 1/8/2020 | 1/8/2020 8:58:31 AM | A | PART |
|
|
Per conversation with Troy Cobbley, 90 Day TCO authorized by Ron Johnson with Boise Fire, signature provided on permit card for 90 day TCO.
Lenor Phone #: ###-####
|
GRD18-00092
| GRD-Final | 1/7/2020 | 1/8/2020 | 1/8/2020 8:58:10 AM | A | PART |
|
|
Per conversation with Troy Cobbley, 90 Day TCO authorized by Ron Johnson with Boise Fire, signature provided on permit card for 90 day TCO.
Lenor Phone #: ###-####
|
FIR19-00390
| INSP-Supply line flush | 1/7/2020 | 1/8/2020 | 1/8/2020 12:00:00 AM | A | PASS |
|
|
**PASS Flush of underground and remote FDC piping** MAS** 9:30 with Suez Phone #: ###-#### >> Inspection requested via web by Matthew Lewis
|
BLD19-00278
| FIRE-Final Inspection | 1/7/2020 | 1/8/2020 | 1/7/2020 12:59:02 PM | A | PART |
|
|
Inspection for fire dpartment radio coverage complete and passed per email from Ron Johnson.
request per Jim Page Phone #: ###-####
|