Inspections for the day of: Thursday, October 10, 2019.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00703 INSP-Sprinkler Rough-in10/10/201910/10/201910/10/2019 3:53:52 PMPPART
Rough to cover inspection for overhead fire sprinkler piping in hardlid dome area complete, area inspected approved for cover, remaining areas to be inspected at a later date.

rough to cover // Mike Phone #: ###-####
FIR19-00570 INSP-Sprinkler Rough-in10/10/201910/10/201910/10/2019 3:52:26 PMPPASS
Rough to cover inspection for remaining overhead fire sprinkler piping in area of work complete, area of work approved for cover.

rough to cover // Mike Phone #: ###-####
FIR19-00709 INSP-Final Inspection10/9/201910/10/201910/10/2019 2:22:45 PMPCANC
Permit has fees due at time of inspection request, per conversation with Joe Bruce, Fire Section Supervisor, fees must be paid before inspection can be performed, this request is cancelled and a new inspection will need to be requested after fees are paid.

Chris Phone #: ###-####
BLD19-03617 FIRE-Final Inspection10/10/201910/10/201910/10/2019 1:40:29 PMPPASS
No fire sprinklers, no fire alarms (smoke detector is stand alone and not monitored), fire extinguisher is placed with a current inspection tag, sticker above door will be placed before BLD inspection reading "Door to remain unlocked while building is occupied". Final life fire safety inspection complete, signature provided on final signature card.

Jennifer Phone #: ###-####
FIR19-00729 INSP-Sprinkler Rough-in10/10/201910/10/201910/10/2019 12:45:27 PMPPASS
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.

Logan Phone #: ###-#### Inspection requested via web by Brodie Stenquist
FIR19-00551 INSP-Sprinkler Rough-in/Hydro10/9/201910/10/201910/10/2019 12:36:37 PMPPART
Rough in inspection for overhead fire sprinkler piping complete, levels 1 and 2 are approved for cover, tenting to be installed at a later date on level 3, cover for level 3 is not approved until tenting inspection is performed.
Hydrostatic test was not performed due to temperature, until permenant heat is established and 40 degrees is maintained per NFPA 13 an official hydro will not be completed.

Robert Chambers is the contact for this RTC /Hydro inspection. We appreciate your help. Thank you! Phone #: ###-#### Inspection requested via web by Stan Beus
BLD19-01112 FIRE-Final Inspection10/9/201910/10/201910/10/2019 10:59:19 AMAPASS
Fire sprinkler inspection is complete, fire alarm inspection is complete, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for area of work complete, signatures provided for associated trades on project signature card.

Laren Phone #: ###-####
FIR19-00429 INSP-Final Inspection10/9/201910/10/201910/10/2019 10:57:59 AMPPASS
Previously noted items have been corrected, final fire alarm inspection for area of work complete.

Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
FIR19-00573 INSP-Final Inspection10/7/201910/10/201910/10/2019 9:32:23 AMACANC
Core and shell permits need to be finaled before TI final, this final needs to be coordinated with the fire alarm contractor to finish fire sprinkler alarm related devides, this request is cancelled per conversation with Rick Fry.

Adam Phone #: ###-####
FIR19-00573 INSP-Sprinkler Rough-in10/7/201910/10/201910/10/2019 9:15:03 AMAPASS
Rough to cover inspection for remaining overhead fire sprinkler piping is complete, approved for cover.

Adam Phone #: ###-####
FIR19-00401 INSP-Final Inspection10/9/201910/10/201910/10/2019 6:42:58 AMACANC
Please call 1/2 hour before arriving. Thanks Phone #: ###-#### >> Inspection requested via web by david davis Inspection cancelled from web by: david davis
FIR19-00431 INSP-Final Inspection10/9/201910/10/201910/10/2019 6:42:55 AMACANC
Please call 1/2 hour before arriving. Thanks Phone #: ###-#### >> Inspection requested via web by david davis Inspection cancelled from web by: david davis