Inspections for the day of: Tuesday, October 15, 2019.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00573 INSP-Final Inspection10/15/201910/15/201910/15/2019 4:35:13 PMPPASS
Final fire sprinkler inspection for area of work complete.

Phone #: ###-#### Inspection requested via web by Matthew Lewis
FIR19-00663 INSP-Final Inspection10/15/201910/15/201910/15/2019 4:34:38 PMPPASS
Fire sprinkler riser monitoring verified, final fire alarm inspection complete,

Buck Phone #: ###-####
BLD18-04470 FIRE-Final Inspection10/15/201910/15/201910/15/2019 4:33:56 PMPPASS
Fire sprinkler inspection is complete, fire alarm permit under tenant improvement permit, fire extinguishers provided by tenant improvement. Final life fire safety inspection for this scope of work complete.

Looking for Life, Fire, Safety Inspection so T.I. contractor can get his final.
Thank you. Phone #: ###-#### Inspection requested via web by Gary Band
FIR19-00233 INSP-Final Inspection10/15/201910/15/201910/15/2019 4:31:49 PMPPASS
Final fire sprinkler inspection for core and shell complete.

Phone #: ###-#### Inspection requested via web by Matthew Lewis
BLD19-02489 FIRE-Final Inspection10/15/201910/15/201910/15/2019 2:05:31 PMPPASS
Fire alarm inspection for area of work complete, no fire sprinkler modifications, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for area of work complete, signature card not provided at time of inspection.

BLD19-00955 FIRE-Final Inspection10/15/201910/15/201910/15/2019 2:03:13 PMPPASS
Fire sprinkler inspection is complete, no fire alarm modifications, fire exitnguisher is placed with a current inspection tag. Final life fire safety inspection for area of work is complete, signatures provided on signature card.

tOBY- PLEASWE CALL, LOCK BOX Phone #: ###-####
BLD19-03335 FIRE-Final Inspection10/15/201910/15/201910/15/2019 1:46:25 PMPFAIL
Provide fire alarm notification in exam rooms as discussed, a seperate fire alarm permit will be required for fire alarm modificaitons. Sprinkler head in small storage room has sprinkler head closer than 4 inches too wall, relocate to be code compliant. Provide code compliant door hardware for pocket door as discussed.
FIR19-00127 INSP-Final Inspection10/14/201910/15/201910/15/2019 1:23:55 PMPFAIL
Fire sprinkler, fire alarm and fire alarm communicator trades need to be coordinated together to complete this inspection. Provide a record of testing from the monitoring service as discussed. Smoke detector in dayroom is over 23 feet from corner, relocate for code compliance. Provide fan shutdown on large ceiling fan on appuratus floor. Fire alarm system is an engineered system, a resubmittal for plan mod is required to show the addition of the smoke detector in the captians quarters and the addition of the fan shutdown relay. No devices were tested and monitoring was not verified.


Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
BLD19-03696 FIRE-Final Inspection10/11/201910/15/201910/15/2019 11:13:28 AMAPASS
No fire sprinkler modifications, no fire alarm modifications, fire extinguisher is placed and will have annual inspection performed/tagged accordingly, suite number according to city approved documents is to be suite 200, not 100, numbers were oerderd at time of inspection and will be placed when received. Final life fire safety inspection for area of work complete.

Jason Phone #: ###-####
FIR19-00168 INSP-Sprinkler Rough-in10/15/201910/15/201910/15/2019 9:41:30 AMAPART
Rough to cover inspection for overhead fire sprinkler piping above hardlid and suspeneded ceiling, west coridor complete, area inspected approved for cover.

Phone #: ###-#### Inspection requested via web by Lonnie Greenfield
BLD19-01795 FIRE-Final Inspection10/14/201910/15/201910/15/2019 8:29:26 AMAPART
Exit signage and emergency lighting that was noted on the past life safety inspections has been replaced and operational, sprinkler and fire alarm modifications are required due to the change in occupancy for area of work, fire alarm and fire sprinkler modifications are being designed and submitted for review. Partial final inspection for life fire safety is complete, fire exitnguisher is placed, inspection tag for fire exitguisher expired in september of 2019, fire extinguishers will need annual inspection performed before next final life fire safety inspection, annual inspection of fire extinguihsers will be verified at that time. Reccomend replacing the 2 fire sprinklers above dryers to a higher temp head, heads in place appear to be 165 degree heads. Per conversation with Ron Johnson with Boise Fire a 90 day TCO is authorized for life fire safety contingent upon fire sprinkler and fire alarm modifications being submitted, approved, inspected and passed. A follow up inspection will be required for life fire safety when the fire sprinkler and fire alarm modifications have been finaled.

Dennis Phone #: ###-####
BLD16-03440 FIRE-Final Inspection10/11/201910/15/201910/14/2019 1:17:07 PMACANC
For Fire Alarm Final Phone #: ###-#### >> Inspection requested via web by Dillon Barresi Inspection cancelled from web by: Dillon Barresi