BLD18-03431
| FIRE-Final Inspection | 10/16/2018 | 10/17/2018 | 10/17/2018 1:15:34 PM | P | FAIL |
|
|
Provide fire extinguisher with inspection tag and mount in discussed location. Provide sticker on main entry reading "Door to remain unlocked while building is occupied". Provide code compliant door hardware for restroom door.
Ken Phone #: ###-####
|
FIR18-00686
| INSP-Sprinkler Rough-in/Hydro | 10/16/2018 | 10/17/2018 | 10/17/2018 1:13:50 PM | A | PART |
|
|
Hydrostatic terst for overhead fire sprinkler piping in chapel/sanctuary section complete, remianing sprinkler piping to have hydrostatic test completed at a later date.
sanctuary- Ron Phone #: ###-####
|
FIR18-00738
| INSP-Conference | 10/17/2018 | 10/17/2018 | 10/17/2018 11:09:19 AM | P | DONE |
|
|
Conference for undergorund supply complete.
|
FIR18-00738
| INSP-Sprinkler Rough-in | 10/17/2018 | 10/17/2018 | 10/17/2018 11:07:32 AM | P | CANC |
|
|
Reuqest was for conference, this request is canceeld.
UG Cover Troy Nelson Phone #: ###-#### Inspection requested via web by Nathan Stenquist
|
FIR17-00612
| INSP-Sprinkler Rough-in | 10/16/2018 | 10/17/2018 | 10/17/2018 11:06:59 AM | A | DONE |
|
|
24 hour test complete on 4 new dry systems.
Jeff is requesting a 24 hr. air test. Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00706
| INSP-Final Inspection | 10/17/2018 | 10/17/2018 | 10/17/2018 9:41:32 AM | A | PASS |
|
|
Final fire alarm ispection complete for area of work.
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
FIR18-00710
| INSP-Sprinkler Rough-in | 10/16/2018 | 10/17/2018 | 10/17/2018 8:22:24 AM | A | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping above hardlids in area of work complete, hardlid approved for cover.
Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD18-01938
| FIRE-Final Inspection | 10/16/2018 | 10/17/2018 | 10/17/2018 7:34:42 AM | A | PASS |
|
|
Previously noted deficiencies on the fire sprinkler system have been corrected, final life fire safety inspection for area of work complete.
Aaron Phone #: ###-####
|
FIR18-00760
| INSP-Final Inspection | 10/16/2018 | 10/17/2018 | 10/17/2018 7:26:38 AM | A | PASS |
|
|
Final fire alarm inspection for area of work completre.
Hi Jim If possible we would like to schedule the inspection at 7:00am to help from disrupting building operations. Please call me and let me know if this will work. Thank you Mike Timmerman Phone #: ###-#### Inspection requested via web by Neal Timmerman
|
BLD18-00445
| FIRE-Conference | 10/16/2018 | 10/17/2018 | 10/16/2018 9:37:25 AM | A | CANC |
|
|
Noah Phone #: ###-#### //cancllled per Noah 10/16/18 @ 9:30am
|