BLD17-04451
| FIRE-Final Inspection | 10/2/2018 | 10/2/2018 | 10/2/2018 2:29:13 PM | P | PASS |
|
|
No fire sprinklers, no fire alarms, fire extinguishers are placed with current inspection tags, final life fire safety inspection complete.
|
FIR18-00159
| INSP-Sprinkler Rough-in/Hydro | 10/1/2018 | 10/2/2018 | 10/2/2018 2:28:28 PM | P | PART |
|
|
Hydrostatic test for overhead fire sprinkler piping on levls 2, 3 and 4 complete, level 1 and standpipes to be tested at a later date.
Phone #: ###-#### Inspection requested via web by Matthew Lewis
|
FIR18-00598
| INSP-Sprinkler Rough-in | 10/1/2018 | 10/2/2018 | 10/2/2018 2:25:52 PM | P | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover. Fire sprinkler head in west cooler in main kitchen has head to far off of wall, fire sprinkler head in cooler will need to be relocated, will verify reloaction at final inspection.
Tom Phone #: ###-####
|
BLD18-00032
| FIRE-Final Inspection | 10/2/2018 | 10/2/2018 | 10/2/2018 2:24:35 PM | P | PASS |
|
|
Final life fire safety inspection for scope of work complete.
Dusty Phone #: ###-####
|
BLD17-03696
| FIRE-Final Inspection | 10/1/2018 | 10/2/2018 | 10/2/2018 2:02:50 PM | P | PASS |
|
|
Plan mod for new floor plan has been provided and approved, final life fire safety inspection for area of work complete.
call half hour before // Shane Phone #: ###-####
|
FIR18-00679
| INSP-Sprinkler Rough-in | 10/1/2018 | 10/2/2018 | 10/2/2018 11:44:52 AM | P | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover. The fire sprinkler riser room will need to have an exterior door installed to a rated riser room or a wall mount post indicator valve will need to be installed to be code compliant before final inspection.
Rick Phone #: ###-####
|
FIR18-00731
| INSP-Sprinkler Rough-in | 10/1/2018 | 10/2/2018 | 10/2/2018 9:33:10 AM | A | PASS |
|
|
Tenting inspection complete, cover approved for overhead fire sprinkler piping.
Tenting inspection. Please let Anthony know if there are any issues. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR18-00491
| INSP-Sprinkler Rough-in | 10/1/2018 | 10/2/2018 | 10/2/2018 9:32:46 AM | A | PASS |
|
|
Tenting inspection complete, cover approved for overhead fire sprinkler piping.
Tenting inspection. Please let Anthony know if there are any issues. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR18-00611
| INSP-Sprinkler Rough-in | 10/1/2018 | 10/2/2018 | 10/2/2018 9:02:09 AM | A | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping above hardlids in area of work complete, hardlids approved for cover.
Aron Foster is the contact for this rough to cover inspection. He is needing the rough to cover in the bathrooms also. Thank you for your help. Phone #: ###-#### Inspection requested via web by Stan Beus
|