Inspections for the day of: Tuesday, October 22, 2019.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00113 INSP-Final Inspection10/22/201910/22/201910/22/2019 3:37:58 PMPPASS
Final fire sprinkler inspection for scope of work complete.

John Phone #: ###-####
FIR19-00562 INSP-Sprinkler Rough-in10/22/201910/22/201910/22/2019 3:37:15 PMPPASS
Rough in inspection for scope of work complete.

Jogn Phone #: ###-####
BLD19-03142 FIRE-Final Inspection10/21/201910/22/201910/22/2019 3:18:17 PMPCANC
Cancelled per conversation with point of contact, life fire safety inspection will be rescheduled to coincide with fire alarm inspection.

Fire Life/Safety sign off. Fire Alarm and Fire Sprinkler are on separate Permit # FIR19-00578. Phone #: ###-#### Inspection requested via web by Kirsten Dallmann
FIR19-00418 INSP-Final Inspection10/21/201910/22/201910/22/2019 2:23:58 PMPFAIL
Backflow installed for fire sprinklers is a RPBA (reduce pressure backflow assembly), calculations for sprinkler system were designed with a double check, not and RP. System will need to be re-calculated for water flow demand or install double check as shown on city approved drawings.

Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR19-00254 INSP-Final Inspection10/21/201910/22/201910/22/2019 1:17:28 PMAFAIL
Provide annual inspection for backflow. Irrigation shutdown on flow switch activation not hooked up coorectly at time of inspection, no flow test completed.

Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR19-00666 INSP-Sprinkler Rough-in10/22/201910/22/201910/22/2019 12:34:42 PMAPASS
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.

Phone #: ###-#### Inspection requested via web by Jonathan LaFond
BLD19-01635 FIRE-Final Inspection10/21/201910/22/201910/22/2019 12:06:09 PMAPASS
No fire sprinkler modifications, no fire alarm modifications, fire extinguishers are in common areas with current inspection tags. Final life fire safety inspection for area of work complete, signature card not available at time of inspection, no signature provided.

Steve Phone #: ###-####
BLD17-00066 FIRE-Final Inspection10/22/201910/22/201910/22/2019 11:43:40 AMPPART
Partial final inspection for fire life safety is complete, TCO for elevator use is approved per conversation with Ron Johnson with Boise Fire, contingent upon fire alarm inspection for job attached FIR permit is finaled. This permit can be finaled when mentioned fire alarm permit is finaled.

KELLY Phone #: ###-####
BLD19-04040 FIRE-Final Inspection10/21/201910/22/201910/22/2019 11:27:58 AMAPASS
No fire sprinklers, no fire alarms, fire extinguisher is in common area with a current inspection tag, suite number to be installed when received. Final life fire safety inspection complete, signature provided on signature card.

Call to meet // Shane Phone #: ###-####
BLD19-00317 FIRE-Final Inspection10/21/201910/22/201910/22/2019 11:01:34 AMAPASS
Previously noted items have been corrected, no fire sprinklers, no fire alarms, fire extinguishers are placed with current inspection tags, permenant fire lane signage to be placed at a later date, temp signage is placed as of this entry. Final life fire safety inspection for bldg 9 complete.

Larry Phone #: ###-####
FIR17-00178 INSP-Alarm Testing10/22/201910/22/201910/22/2019 10:29:35 AMAFAIL
Started inspection in level 10, section 90 of the city approved drawings, notated 7 areas that need corrected where candella settings due not match what was submitted as well as a/v devices that have been added that are not on city approved drawings, inspection stopped due to defecincies noted.

Requesting for 10/22 AM
BLD18-03423 FIRE-Final Inspection10/21/201910/22/201910/22/2019 9:23:34 AMACANC
Reference noted entered by Troy on 21OCT2019 for life fire safety, this request is cancelled.

Eric Phone #: ###-####
FIR19-00610 INSP-Final Inspection10/21/201910/22/201910/22/2019 9:22:36 AMAFAIL
Reloacte audio visual device tghat is blocked by ductwork. Mag locks on access control are not interfaced with fire alarm system, per IFC access controled mag lock doors must release on general fire alarm. Provide weather proof audio visual devices in restrooms, no header/lintel provided in shower area making it a seperate compartment. Provide A/V device in staff locker room as discussed.

Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
FIR19-00570 INSP-Final Inspection10/21/201910/22/201910/22/2019 9:19:34 AMAPASS
Final fire sprinkler inspection for area of work complete.

Rick Fry Phone #: ###-#### Inspection requested via web by Brodie Stenquist
FIR19-00614 INSP-Sprinkler Rough-in10/21/201910/22/201910/21/2019 9:29:56 AMPCANC
Contact Noemi Carrero ###-#### 30 min prior to RTC Insp. start please.

Thank YOU


Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank