Inspections for the day of: Wednesday, October 23, 2019.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00338 INSP-Final Inspection10/23/201910/23/201910/23/2019 3:46:10 PMPPASS
Final fire alarm inspection complete.

Brian Phone #: ###-####
FIR19-00627 INSP-Sprinkler Rough-in10/23/201910/23/201910/23/2019 3:31:57 PMPPASS
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.

Randy Phone #: ###-####
FIR19-00111 INSP-Final Inspection10/23/201910/23/201910/23/2019 3:21:28 PMPFAIL
Provide restricted orifice for inspectors test. Provide annual inspection for backflow assembly. Repair visible leak on riser piping.

Contact Noemi Carrero ###-#### 30 min prior to Final Insp start please

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
FIR19-00254 INSP-Final Inspection10/22/201910/23/201910/23/2019 1:47:50 PMPPASS
Previously noted items have been corrected, final fire sprinkler inspection is complete.

Backflow test is scheduled to be complete by noon. Please call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR19-00614 INSP-Supply line flush10/21/201910/23/201910/23/2019 1:44:02 PMPDONE
Underground main line flush complete.

Contact Tanner Loomis - ###-#### 30 min prior to UG Flush start please, Stacy Stuart can do this at 1 or 2 pm ###-####.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
BLD19-00864 FIRE-Final Inspection10/22/201910/23/201910/23/2019 12:29:14 PMAPASS
No fire sprinkler modifications, no fire alarm modifications, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection complete, signatures provided on sign off card.

Shane Phone #: ###-####
FIR19-00634 INSP-Final Inspection10/21/201910/23/201910/23/2019 11:51:26 AMACANC
Could not perform inspection, request was cancelled per point of contact, will be rescheduled for a later date.

Please call Nate at ###-#### with inspection time. Phone #: ###-#### Inspection requested via web by Lori Brungardt
FIR19-00536 INSP-Sprinkler Rough-in10/21/201910/23/201910/23/2019 11:48:50 AMAPART
Provide fire sprinklers above ceiling grid in areas where TGI's are installed due to more than 6 inches between ceiling grid and TGI's(kitchen area, east and west corridors), remaining areas approved for cover, TGI areas not approved for cover.

Phone #: ###-#### Inspection requested via web by Matthew Lewis
BLD18-03657 FIRE-Final Inspection10/22/201910/23/201910/23/2019 11:02:33 AMAFAIL
Fire alarm failed inspection, fire alarm must be finaled before life fire safety can be completed.

Casey Phone #: ###-####
FIR19-00168 INSP-Final Inspection10/22/201910/23/201910/23/2019 11:01:57 AMAPASS
Final fire sprinkler inspection for area of work complete.

contact Lonnie to cordinate final inpsection Phone #: ###-#### Inspection requested via web by Christophe Wilson
FIR19-00268 INSP-Final Inspection10/22/201910/23/201910/23/2019 11:01:11 AMAFAIL
Occupancy is a B occupancy, provide notification in post op and pre op rooms. Relocate notification in areas as discussed. No devices tested.

Call ahead to Damien @ ###-#### Phone #: ###-#### Inspection requested via web by Kristin Dolan