FIR19-00338
| INSP-Final Inspection | 10/23/2019 | 10/23/2019 | 10/23/2019 3:46:10 PM | P | PASS |
|
|
Final fire alarm inspection complete.
Brian Phone #: ###-####
|
FIR19-00627
| INSP-Sprinkler Rough-in | 10/23/2019 | 10/23/2019 | 10/23/2019 3:31:57 PM | P | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.
Randy Phone #: ###-####
|
FIR19-00111
| INSP-Final Inspection | 10/23/2019 | 10/23/2019 | 10/23/2019 3:21:28 PM | P | FAIL |
|
|
Provide restricted orifice for inspectors test. Provide annual inspection for backflow assembly. Repair visible leak on riser piping.
Contact Noemi Carrero ###-#### 30 min prior to Final Insp start please
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
FIR19-00254
| INSP-Final Inspection | 10/22/2019 | 10/23/2019 | 10/23/2019 1:47:50 PM | P | PASS |
|
|
Previously noted items have been corrected, final fire sprinkler inspection is complete.
Backflow test is scheduled to be complete by noon. Please call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR19-00614
| INSP-Supply line flush | 10/21/2019 | 10/23/2019 | 10/23/2019 1:44:02 PM | P | DONE |
|
|
Underground main line flush complete.
Contact Tanner Loomis - ###-#### 30 min prior to UG Flush start please, Stacy Stuart can do this at 1 or 2 pm ###-####.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
BLD19-00864
| FIRE-Final Inspection | 10/22/2019 | 10/23/2019 | 10/23/2019 12:29:14 PM | A | PASS |
|
|
No fire sprinkler modifications, no fire alarm modifications, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection complete, signatures provided on sign off card.
Shane Phone #: ###-####
|
FIR19-00634
| INSP-Final Inspection | 10/21/2019 | 10/23/2019 | 10/23/2019 11:51:26 AM | A | CANC |
|
|
Could not perform inspection, request was cancelled per point of contact, will be rescheduled for a later date.
Please call Nate at ###-#### with inspection time. Phone #: ###-#### Inspection requested via web by Lori Brungardt
|
FIR19-00536
| INSP-Sprinkler Rough-in | 10/21/2019 | 10/23/2019 | 10/23/2019 11:48:50 AM | A | PART |
|
|
Provide fire sprinklers above ceiling grid in areas where TGI's are installed due to more than 6 inches between ceiling grid and TGI's(kitchen area, east and west corridors), remaining areas approved for cover, TGI areas not approved for cover.
Phone #: ###-#### Inspection requested via web by Matthew Lewis
|
BLD18-03657
| FIRE-Final Inspection | 10/22/2019 | 10/23/2019 | 10/23/2019 11:02:33 AM | A | FAIL |
|
|
Fire alarm failed inspection, fire alarm must be finaled before life fire safety can be completed.
Casey Phone #: ###-####
|
FIR19-00168
| INSP-Final Inspection | 10/22/2019 | 10/23/2019 | 10/23/2019 11:01:57 AM | A | PASS |
|
|
Final fire sprinkler inspection for area of work complete.
contact Lonnie to cordinate final inpsection Phone #: ###-#### Inspection requested via web by Christophe Wilson
|
FIR19-00268
| INSP-Final Inspection | 10/22/2019 | 10/23/2019 | 10/23/2019 11:01:11 AM | A | FAIL |
|
|
Occupancy is a B occupancy, provide notification in post op and pre op rooms. Relocate notification in areas as discussed. No devices tested.
Call ahead to Damien @ ###-#### Phone #: ###-#### Inspection requested via web by Kristin Dolan
|