FIR18-00777
| INSP-Final Inspection | 10/23/2018 | 10/24/2018 | 10/24/2018 3:42:16 PM | P | CANC |
|
|
Final fire alarm inspection will be completed with fire sprinkler final, this request is cancelled after discussion with Clarence.
John Phone #: ###-####
|
FIR18-00718
| INSP-Final Inspection | 10/23/2018 | 10/24/2018 | 10/24/2018 3:40:51 PM | P | FAIL |
|
|
Need to re-hydro overhead fire sprinkler piping due to past freeze issues. Cannot find notes on underground and remote FDC hydro, need to perform hydrostatic test on all associated fire sprinkler componenets before final can be completed. Make corrections in discussed locations.
Can we please have the fire alarm inspection as well FIr18-00777. this permit is not showing up online Phone #: ###-#### Inspection requested via web by Jessia Maxwell
|
FIR18-00686
| INSP-Sprinkler Rough-in/Hydro | 10/23/2018 | 10/24/2018 | 10/24/2018 1:21:06 PM | P | PART |
|
|
Hydrostatic test for basement overhead firte sprinkler piping witnessed, no pressure loss observed.
basement // Ron Phone #: ###-####
|
FIR18-00490
| INSP-Final Inspection | 10/23/2018 | 10/24/2018 | 10/24/2018 1:06:50 PM | P | PASS |
|
|
Final fire sprinkler inspection complete.
Call Anthony to coordinate, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR18-00684
| INSP-Sprinkler Rough-in | 10/23/2018 | 10/24/2018 | 10/24/2018 12:14:29 PM | A | PART |
|
|
Partial rough to cover inspection for overhead fire sprinkler piping in area of work complete, notated the city approved drawings with yellow highlighter areas approved for cover.
Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR18-00565
| INSP-Sprinkler Rough-in | 10/24/2018 | 10/24/2018 | 10/24/2018 11:50:04 AM | P | DONE |
|
|
Hydrostatic test for both underground mains witnessed, no pressure loss observed.
Johnathon-hydro underground east and west bldg Phone #: ###-####
|
FIR18-00769
| INSP-Sprinkler Rough-in | 10/23/2018 | 10/24/2018 | 10/24/2018 11:10:58 AM | A | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler pipng in area of work complete, approved for cover.
RANDY Phone #: ###-#### Inspection requested via web by Nathan Stenquist
|
FIR18-00540
| INSP-Sprinkler Rough-in/Hydro | 10/23/2018 | 10/24/2018 | 10/24/2018 10:57:06 AM | A | DONE |
|
|
Hydro for undergorund supply witnessed, no pressure loss observd at provided gauge.
Hydro- Troy Phone #: ###-####
|
FIR16-00563
| INSP-Sprinkler Rough-in/Hydro | 10/23/2018 | 10/24/2018 | 10/24/2018 10:46:55 AM | A | DONE |
|
|
Hydrostatic test for levels 1, 2 and 3 are complete.
Coordinate Hydro with Lonnie Greenfield Phone #: ###-#### Inspection requested via web by Christophe Wilson
|
BLD18-03430
| FIRE-Final Inspection | 10/23/2018 | 10/24/2018 | 10/24/2018 10:46:00 AM | A | PASS |
|
|
Final life fire safety inspection for area of work complete.
Mark Phone #: ###-####
|
BLD18-02633
| FIRE-Final Inspection | 10/24/2018 | 10/24/2018 | 10/24/2018 10:44:30 AM | A | PASS |
|
|
Final life fire safety inspction for vanilla space complete.
|
FIR18-00464
| INSP-Sprinkler Rough-in | 10/23/2018 | 10/24/2018 | 10/24/2018 9:48:35 AM | A | PART |
|
|
Rough in spection for overhead fire sprinkler piping in requested area complete, notated city approved drawings with red ink area inspected. Cover is not approved until documentation can be provided for heat maintenance in attic spaces.
Part A Phone #: ###-#### Inspection requested via web by Matthew Lewis
|
BLD18-02561
| FIRE-Final Inspection | 10/23/2018 | 10/24/2018 | 10/24/2018 8:52:08 AM | P | FAIL |
|
|
Provide emergency lighting in receptionist area (emergency lighting provided thoughout tenant space, none shown in receptionist lobby) Racking permit BLD18-03747 needs to be finaled for life safety before tenant space life fire safety inspection can be completed.
Tim Phone #: ###-####
|
FIR18-00611
| INSP-Final Inspection | 10/19/2018 | 10/24/2018 | 10/24/2018 8:41:53 AM | A | PASS |
|
|
Final fire sprinkler inspection for area of work complete.
Todd Ketterling is the contact for this final inspection. Thank you for your help. Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00718
| INSP-Final Inspection | 10/23/2018 | 10/24/2018 | 10/23/2018 9:05:23 PM | A | CANC |
|
|
Can we please have the fire alarm inspection as well FIr18-00777. this permit is not showing up online Phone #: ###-#### >> Inspection requested via web by Jessia Maxwell Inspection cancelled from web by: Jessia Maxwell
|