Inspections for the day of: Wednesday, October 24, 2018.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR18-00777 INSP-Final Inspection10/23/201810/24/201810/24/2018 3:42:16 PMPCANC
Final fire alarm inspection will be completed with fire sprinkler final, this request is cancelled after discussion with Clarence.

John Phone #: ###-####
FIR18-00718 INSP-Final Inspection10/23/201810/24/201810/24/2018 3:40:51 PMPFAIL
Need to re-hydro overhead fire sprinkler piping due to past freeze issues. Cannot find notes on underground and remote FDC hydro, need to perform hydrostatic test on all associated fire sprinkler componenets before final can be completed. Make corrections in discussed locations.

Can we please have the fire alarm inspection as well FIr18-00777. this permit is not showing up online Phone #: ###-#### Inspection requested via web by Jessia Maxwell
FIR18-00686 INSP-Sprinkler Rough-in/Hydro10/23/201810/24/201810/24/2018 1:21:06 PMPPART
Hydrostatic test for basement overhead firte sprinkler piping witnessed, no pressure loss observed.

basement // Ron Phone #: ###-####
FIR18-00490 INSP-Final Inspection10/23/201810/24/201810/24/2018 1:06:50 PMPPASS
Final fire sprinkler inspection complete.

Call Anthony to coordinate, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR18-00684 INSP-Sprinkler Rough-in10/23/201810/24/201810/24/2018 12:14:29 PMAPART
Partial rough to cover inspection for overhead fire sprinkler piping in area of work complete, notated the city approved drawings with yellow highlighter areas approved for cover.

Phone #: ###-#### Inspection requested via web by Sam Ball
FIR18-00565 INSP-Sprinkler Rough-in10/24/201810/24/201810/24/2018 11:50:04 AMPDONE
Hydrostatic test for both underground mains witnessed, no pressure loss observed.

Johnathon-hydro underground east and west bldg Phone #: ###-####
FIR18-00769 INSP-Sprinkler Rough-in10/23/201810/24/201810/24/2018 11:10:58 AMAPASS
Rough to cover inspection for overhead fire sprinkler pipng in area of work complete, approved for cover.

RANDY Phone #: ###-#### Inspection requested via web by Nathan Stenquist
FIR18-00540 INSP-Sprinkler Rough-in/Hydro10/23/201810/24/201810/24/2018 10:57:06 AMADONE
Hydro for undergorund supply witnessed, no pressure loss observd at provided gauge.

Hydro- Troy Phone #: ###-####
FIR16-00563 INSP-Sprinkler Rough-in/Hydro10/23/201810/24/201810/24/2018 10:46:55 AMADONE
Hydrostatic test for levels 1, 2 and 3 are complete.

Coordinate Hydro with Lonnie Greenfield Phone #: ###-#### Inspection requested via web by Christophe Wilson
BLD18-03430 FIRE-Final Inspection10/23/201810/24/201810/24/2018 10:46:00 AMAPASS
Final life fire safety inspection for area of work complete.

Mark Phone #: ###-####
BLD18-02633 FIRE-Final Inspection10/24/201810/24/201810/24/2018 10:44:30 AMAPASS
Final life fire safety inspction for vanilla space complete.
FIR18-00464 INSP-Sprinkler Rough-in10/23/201810/24/201810/24/2018 9:48:35 AMAPART
Rough in spection for overhead fire sprinkler piping in requested area complete, notated city approved drawings with red ink area inspected. Cover is not approved until documentation can be provided for heat maintenance in attic spaces.

Part A Phone #: ###-#### Inspection requested via web by Matthew Lewis
BLD18-02561 FIRE-Final Inspection10/23/201810/24/201810/24/2018 8:52:08 AMPFAIL
Provide emergency lighting in receptionist area (emergency lighting provided thoughout tenant space, none shown in receptionist lobby) Racking permit BLD18-03747 needs to be finaled for life safety before tenant space life fire safety inspection can be completed.

Tim Phone #: ###-####
FIR18-00611 INSP-Final Inspection10/19/201810/24/201810/24/2018 8:41:53 AMAPASS
Final fire sprinkler inspection for area of work complete.

Todd Ketterling is the contact for this final inspection. Thank you for your help. Phone #: ###-#### Inspection requested via web by Stan Beus
FIR18-00718 INSP-Final Inspection10/23/201810/24/201810/23/2018 9:05:23 PMACANC
Can we please have the fire alarm inspection as well FIr18-00777. this permit is not showing up online Phone #: ###-#### >> Inspection requested via web by Jessia Maxwell Inspection cancelled from web by: Jessia Maxwell