Inspections for the day of: Thursday, October 24, 2019.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD19-04201 FIRE-Final Inspection10/24/201910/24/201910/24/2019 3:22:12 PMPPASS
No fire sprinklers, no fire alarms, firee xtinguisher is placed with a current inspection tag. Final life fire safety inspection for area of work complete, signature provided on signature card.

Todd Phone #: ###-####
FIR19-00268 INSP-Final Inspection10/24/201910/24/201910/24/2019 3:05:35 PMPFAIL
Relocate smoke detectors that are to close to HVAC registers. Provide weather proof A/V devides in prep area behind surgical suites. Verify if door hold magnets are going to stay in place, if door holds stay then smoke detectors will be required for door release.

Phone #: ###-#### Inspection requested via web by Kristin Dolan
FIR19-00580 INSP-Sprinkler Rough-in10/24/201910/24/201910/24/2019 1:34:18 PMPCANC
Wrong permit requested, this request is cancelled.

George Jess is Contact. Thanks for all you do! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR19-00654 INSP-Sprinkler Rough-in10/24/201910/24/201910/24/2019 1:33:48 PMPPASS
Rough to cover inspection for overhead fire sprinkler piping above suspended ceiling is complete, approved for cover. Will verify roof top sprinklers on the east side of open ceiling rooms at a later date, 4 more needed to be re-installed per approved plans. Sidewalls from old roll up doors above ceiling grid to be removed, will verify during a later inspection.

BLD19-00775 FIRE-Final Inspection10/23/201910/24/201910/24/2019 12:30:52 PMAFAIL
Fire alarm defecincies need to be corrected and fire alarm inspection needs to be completed and finaled before life fire safety inspection can be completed.

CORY Phone #: ###-####
BLD19-03943 FIRE-Final Inspection10/23/201910/24/201910/24/2019 9:21:11 AMAFAIL
Two pendant fire sprinklers are still in place from where a ceiling has been removed, sprinkler heads mentioned need to be removed and plugged, a seperate permit is required for any and all fire sprinkler modifications. Provide annual inspection for fire extinguisher that is in space. Provide a maximum occupancy sign with the correct number of occupants based on city approved documents.

Andy Phone #: ###-####